Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ETE MV400P2S3 is a 400 VA single-phase multi-voltage control transformer with 20/0/380/420 V primary terminals, dual 0/12 V secondary windings configurable for 12 V parallel or 24 V series output, a 20 V primary adjustment tap requiring ETE connection confirmation, Class E insulation and 8% voltage regulation.
£63.98
The ETE MV400P2S3 is a 400 VA single-phase multi-voltage control transformer designed for industrial electrical installations requiring flexible primary voltage connections and selectable low-voltage AC outputs. Part of the ETE MV multi-voltage transformer series, it features 20/0/380/420 V primary terminals and two separate secondary windings, each marked 0/12 V.
The MV400P2S3 supports a nominal 12 V AC output with the secondary windings connected in parallel or a nominal 24 V AC output with the secondary windings connected in series. This flexibility makes it suitable for industrial control panels, OEM machinery and automation equipment requiring compatible 12 V or 24 V AC control supplies.
The transformer incorporates a 20 V primary adjustment tap alongside its 0/380/420 V primary terminal markings. This provides an additional connection facility within the primary winding arrangement. The correct use of the 20 V adjustment tap and the required primary terminal connections must be confirmed with ETE before installation. The terminal markings should not be used to infer an unverified adjustment connection.
With Class E insulation, 8% voltage regulation, dimensions of 120 × 108 × 120 mm and a weight of 5.5 kg, the ETE MV400P2S3 offers a practical solution for industrial control power distribution. Its associated enclosure references are EPH 3 or EPN 2, supporting enclosure selection and electrical panel planning.
The ETE MV400P2S3 provides a practical solution for industrial installations requiring a dedicated low-voltage AC supply from a compatible higher-voltage primary source. Its 20/0/380/420 V primary terminal arrangement incorporates nominal 380 V and 420 V connection positions alongside a 20 V adjustment tap. The correct primary supply and adjustment connections must be confirmed with ETE before energising the transformer.
A key feature is the provision of two separate 0/12 V secondary windings. When connected correctly in parallel, the windings provide a nominal 12 V AC output. Parallel operation combines the available current contribution of the two windings while retaining the transformer's overall 400 VA rating. Matching winding voltages and correct polarity are essential because incorrect parallel connections can produce damaging circulating currents.
When connected correctly in series, the two secondary windings provide a nominal 24 V AC output. This configuration adds the voltages of the individual 12 V windings while retaining the overall transformer apparent power rating. Correct winding polarity and terminal identification are essential, as an incorrect series connection may result in voltage cancellation or an unsuitable output.
At the rated 400 VA capacity, the calculated nominal secondary current is approximately 33.33 A at 12 V AC with the windings connected in parallel, or 16.67 A at 24 V AC with the windings connected in series. These figures are calculated from the transformer apparent power rating and nominal output voltages rather than separately verified manufacturer current ratings. The 400 VA rating applies to the transformer as a whole and must not be interpreted as 400 VA independently available from each secondary winding.
The specified 8% voltage regulation is relevant when evaluating secondary voltage variation under changing load conditions. Actual output voltage depends on the primary supply, selected terminals, winding configuration and connected load. Equipment with narrow operating voltage tolerances should be checked for compatibility, particularly where control relays, contactor coils, solenoids or other inductive devices introduce changing loads and starting currents.
With Class E insulation, dimensions of 120 × 108 × 120 mm and a weight of 5.5 kg, the MV400P2S3 can be incorporated into appropriately engineered industrial control assemblies. Its EPH 3 or EPN 2 enclosure references assist with enclosure planning. Installers should provide suitable mechanical support, primary and secondary circuit protection, conductor sizing, ventilation and electrical clearances, following the manufacturer's instructions for both primary and secondary winding connections.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 400 VA | |
|---|---|---|
| Primary Voltage | 20/0/380/420V | |
| Secondary Voltage | 0/12V + 0/12V | |
| Phase | Single Phase | |
| Manufacturer | ETE | |
| Product series | MV Multi-Voltage Control Transformers | |
| Manufacturer part number | MV400P2S3 | |
| Product type | Multi-voltage control transformer | |
| Transformer configuration | Single-phase | |
| Rated apparent power | 400 VA | |
| Rated capacity | 0.4 kVA | |
| Primary terminals | 20/0/380/420 V | |
| Primary voltage terminal markings | 380 V and 420 V | |
| Primary adjustment tap | 20 V | |
| Primary connection requirement | Confirm correct terminal connections with ETE | |
| Number of secondary windings | 2 | |
| Secondary winding 1 terminals | 0/12 V | |
| Secondary winding 2 terminals | 0/12 V | |
| Parallel secondary output | 12 V AC | |
| Series secondary output | 24 V AC | |
| Secondary connection arrangement | 12 V parallel or 24 V series | |
| Calculated secondary current at 12 V parallel | Approximately 33.33 A at 400 VA | |
| Calculated secondary current at 24 V series | Approximately 16.67 A at 400 VA | |
| Insulation class | E | |
| Voltage regulation | 8% | |
| Length | 120 mm | |
| Width | 108 mm | |
| Height | 120 mm | |
| Dimensions (L × W × H) | 120 × 108 × 120 mm | |
| Weight | 5.5 kg | |
| Enclosure reference | EPH 3 or EPN 2 | |
| Product range | ETE Stock Control Transformers | |
| Catalogue reference | ETE Stock Control Transformer Range, March 2026 |
The ETE MV400P2S3 is a 400 VA single-phase multi-voltage control transformer used to provide a nominal 12 V AC or 24 V AC secondary supply for compatible industrial control circuits, machinery and automation equipment.
The transformer has a rated apparent power of 400 VA (0.4 kVA). This is the overall transformer rating and applies to the combined load on its secondary windings.
The transformer features 20/0/380/420 V primary terminals. These include a 20 V adjustment tap, and the correct primary connection arrangement must be confirmed with ETE before installation.
The 20 V primary adjustment tap provides an additional connection facility within the primary winding arrangement. Its correct use and wiring configuration must be confirmed with ETE; the terminal markings alone should not be used to assume a particular adjustment connection.
The transformer supports a nominal 12 V AC output with the secondary windings connected in parallel or a nominal 24 V AC output with the windings connected in series, using the manufacturer's specified wiring arrangements.
The MV400P2S3 has two secondary windings, each with 0/12 V terminals. The windings can be connected in the specified series or parallel configurations.
Yes. The two secondary windings can be connected in parallel to provide a nominal 12 V AC output. Correct winding polarity and matching voltage connections are essential, and the total load must remain within the 400 VA rating.
Yes. The two secondary windings can be connected in series to provide a nominal 24 V AC output. The correct series connection and winding polarity must be followed according to the manufacturer's instructions.
At the rated 400 VA capacity and a nominal 12 V AC parallel output, the calculated current is approximately 33.33 A. This is a calculated value rather than a separately verified manufacturer current rating.
At the rated 400 VA capacity and a nominal 24 V AC series output, the calculated current is approximately 16.67 A. This is a calculated value rather than a separately verified manufacturer current rating.
The MV400P2S3 has a specified 8% voltage regulation. Transformer voltage regulation describes the change in secondary voltage between defined load conditions, so connected equipment should have suitable operating voltage tolerance.
The transformer uses Class E insulation, providing a defined thermal insulation classification for its winding insulation system.
The transformer measures 120 × 108 × 120 mm (L × W × H) and weighs 5.5 kg. These details assist with electrical panel layout and mounting arrangements.
The associated enclosure references are EPH 3 or EPN 2. The appropriate enclosure and its suitability for the installation should be confirmed before selection.
Before installation, confirm the correct 20/0/380/420 V primary connections and the use of the 20 V adjustment tap with ETE. Select the required 12 V parallel or 24 V series secondary arrangement, follow the manufacturer's winding connection instructions, check the connected load against the 400 VA rating and provide suitable circuit protection, conductor sizing, mounting, ventilation and electrical clearances.
ETE MV multi-voltage control transformers provide a practical solution for industrial applications requiring flexible primary connections and configurable low-voltage AC outputs. With 20/0/380/420 V primary terminals, dual 0/12 V secondary windings, selectable 12 V parallel or 24 V series output, a 400 VA rating and Class E insulation, the MV400P2S3 offers electrical panel builders, machinery manufacturers and automation engineers a versatile transformer option for industrial control power.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.