ETE MV250P2S1 is a 250 VA single-phase multi-voltage control transformer with 20/0/380/420 V primary terminals, selectable 55 V or 110 V AC secondary connections, Class E insulation, 8% voltage regulation and EPH 3 or EPN 2 enclosure compatibility.
£47.40
The ETE MV250P2S1 is a versatile 250 VA single-phase multi-voltage control transformer designed for industrial electrical control panels, machinery and automation systems requiring selectable AC control voltages. Part of the ETE MV multi-voltage control transformer range, this model features 20/0/380/420 V primary terminals and 0/55/110 V secondary terminals, providing nominal 55 V AC or 110 V AC output connections for compatible industrial control equipment.
The MV250P2S1 offers flexibility for installations involving different industrial supply arrangements. Its primary winding includes terminals marked 380 V and 420 V, together with a 20 V primary adjustment tap. This adjustment connection provides additional flexibility when configuring the transformer, although the exact permitted terminal combinations must be confirmed with ETE before installation.
On the secondary side, the 0/55/110 V tapped winding allows installers to select the appropriate output connection for equipment requiring 55 V AC or 110 V AC. This makes the transformer suitable for appropriately rated contactor coils, electromagnetic relays, signalling devices, solenoids and other industrial AC control components.
With a rated apparent power of 250 VA, Class E insulation and 8% voltage regulation, the MV250P2S1 provides a practical combination of control power capacity and voltage selection. Measuring 120 × 88 × 120 mm and weighing 3.9 kg, it is suitable for integration into industrial electrical cabinets. The specified compatible enclosure references are ETE EPH 3 or EPN 2.
The ETE MV250P2S1 provides a flexible solution for industrial electrical installations requiring selectable 55 V AC or 110 V AC control voltage. Its 20/0/380/420 V primary arrangement and 0/55/110 V secondary winding allow the transformer to be incorporated into electrical systems where the available supply and required control voltage must be matched correctly.
The primary winding includes terminals marked 380 V and 420 V, together with a 20 V adjustment tap. The adjustment tap must not be interpreted as a standalone 20 V supply input. Its precise function, permitted terminal combinations and suitability for a particular supply voltage should be confirmed using ETE's approved wiring information before energising the transformer.
The secondary winding incorporates an intermediate 55 V tap and a full 110 V connection. This provides a choice of nominal secondary voltages for compatible industrial control components. Although the terminal arrangement includes a midpoint tap, any centre-point earthing arrangement or application requiring a centre-tapped supply must be assessed against the manufacturer's connection information and the requirements of the electrical installation.
The 250 VA apparent power rating corresponds to a calculated nominal full-load secondary current of approximately 2.27 A at 110 V AC. This calculation is based on the total transformer apparent power divided by the nominal full secondary voltage. The allowable current through the individual 55 V winding section has not been separately specified and should not be assumed to equal the total transformer rating divided by 55 V.
The specified 8% voltage regulation is relevant when designing control circuits containing electromagnetic loads. Secondary voltage may vary as connected equipment switches on and off, particularly where contactors, relays or solenoids draw greater apparent power during initial energisation than during normal operation. Electrical designers should therefore assess both steady-state load and simultaneous switching requirements.
With Class E insulation, dimensions of 120 × 88 × 120 mm and a weight of 3.9 kg, the MV250P2S1 is suited to industrial electrical control cabinets. The specified EPH 3 or EPN 2 enclosure references provide compatible housing options where additional physical protection is required.
The MV250P2S1 provides AC voltage transformation rather than regulated DC output. Equipment requiring DC control voltage will need appropriate additional conversion equipment. Installation should include correct primary tap selection, suitable primary and secondary circuit protection, conductor sizing, mounting, ventilation and protective earthing where applicable.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 250 VA | |
|---|---|---|
| Primary Voltage | 20/0/380/420V | |
| Secondary Voltage | 0/55/110V | |
| Phase | Single Phase | |
| Brand | ETE | |
| Manufacturer part number | MV250P2S1 | |
| Product family | MV Multi-Voltage Control Transformers | |
| Product category | Industrial Control Transformers | |
| Transformer configuration | Tapped primary and secondary windings | |
| Number of phases | Single-phase | |
| Rated apparent power | 250 VA | |
| Primary terminal arrangement | 20/0/380/420 V | |
| Primary voltage terminal markings | 380 V and 420 V | |
| Primary adjustment tap | 20 V | |
| Primary connection note | Confirm the correct 20 V adjustment tap connections with ETE before energising. | |
| Secondary terminal arrangement | 0/55/110 V | |
| Nominal secondary output options | 55 V AC or 110 V AC | |
| Calculated nominal full-load secondary current at 110 V | Approximately 2.27 A | |
| Insulation class | E | |
| Voltage regulation | 8% | |
| Length | 120 mm | |
| Width | 88 mm | |
| Height | 120 mm | |
| Overall dimensions (L × W × H) | 120 × 88 × 120 mm | |
| Weight | 3.9 kg | |
| Compatible enclosure references | EPH 3 or EPN 2 | |
| Typical installation | Industrial electrical control panels and machinery cabinets | |
| Catalogue reference | ETE Stock Control Transformer Range, March 2026 |
The ETE MV250P2S1 is a 250 VA single-phase multi-voltage control transformer designed to provide selectable 55 V AC or 110 V AC secondary connections for compatible industrial control equipment.
The primary terminal markings are 20/0/380/420 V. The correct connection arrangement, particularly the function of the 20 V adjustment tap, must be confirmed with ETE.
The 20 V primary adjustment tap provides an additional winding connection. Its precise relationship to the 0, 380 V and 420 V terminals must be verified using ETE's approved connection information before installation.
The transformer has primary terminals marked 380 V and 420 V, together with a 20 V adjustment tap. The correct connection arrangement for a nominal 400 V AC supply must be confirmed with ETE rather than inferred from the terminal markings alone.
The secondary terminals are marked 0/55/110 V, providing nominal 55 V AC or 110 V AC output connections when wired correctly.
The 0/55/110 V secondary arrangement includes an intermediate 55 V tap on the 110 V winding. The suitability of this arrangement for a particular centre-tapped application, including any centre-point earthing requirements, must be confirmed from ETE's connection information.
The MV250P2S1 has a rated apparent power of 250 VA. The connected load must remain within the applicable transformer and winding ratings.
At 250 VA and 110 V AC, the calculated nominal full-load secondary current is approximately 2.27 A.
Not without confirmation. The transformer has a total rated apparent power of 250 VA, but the allowable current through the individual 55 V winding section has not been specified separately. The applicable tap loading limit should be confirmed with ETE.
The transformer provides AC output. It does not incorporate a rectifier or regulated DC power supply.
The transformer has Class E insulation and a specified 8% voltage regulation.
The transformer measures 120 mm long × 88 mm wide × 120 mm high and weighs 3.9 kg.
The specified compatible enclosure references are ETE EPH 3 or EPN 2. Final enclosure selection should account for the installation environment, mounting requirements and ventilation.
Yes. Its 250 VA rating, selectable secondary voltage connections and compact construction make it suitable for appropriately designed industrial control panels using compatible AC control equipment.
The specified 8% voltage regulation indicates that secondary voltage changes with loading. Connected control equipment should have suitable operating voltage tolerances, particularly where electromagnetic devices produce high energisation demands.
The correct wiring information should be obtained from ETE or its approved technical documentation. This is especially important when using the 20 V primary adjustment tap or configuring the secondary winding for a particular control circuit.
The ETE MV250P2S1 combines a 250 VA rating with flexible primary connections and selectable 55 V or 110 V AC secondary outputs. Its Class E insulation, 8% voltage regulation and compact construction make it a practical component for electrical panel builders, machinery manufacturers and maintenance engineers requiring adaptable industrial AC control power.