Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ETE MV150P1S1 is a 150 VA single-phase multi-voltage control transformer featuring 10/0/220/240 V primary terminals with a 10 V adjustment tap, selectable 55 V or 110 V AC secondary connections, Class E insulation and 10% voltage regulation.
£32.93
The ETE MV150P1S1 is a versatile 150 VA single-phase multi-voltage control transformer designed for industrial electrical control circuits requiring flexible primary voltage connections and selectable 55 V AC or 110 V AC secondary outputs. Manufactured by Eastern Transformers & Equipment (ETE), this transformer belongs to the ETE MV Multi-Voltage Series, providing a practical power supply solution for electrical control panels, machinery, automation equipment and OEM installations.
Featuring a 10/0/220/240 V primary terminal arrangement and 0/55/110 V secondary terminals, the MV150P1S1 offers multiple connection options for industrial control applications. Its secondary winding arrangement is also described by ETE as 55/0/55 V (0/55/110 V), allowing the appropriate output connections to be selected for the intended circuit.
The transformer has Class E insulation, 10% voltage regulation and a 150 VA rated capacity. Its compact dimensions of 96 × 76 × 103 mm and weight of 2.3 kg make it suitable for integration into industrial control cabinets. The specified enclosure references are EPH 2 or EPN 1.
Important connection note: The primary includes a 10 V adjustment tap. The exact primary connections and intended adjustment arrangement must be confirmed with ETE before installation. The terminal markings should not be interpreted as permission to apply arbitrary voltages or connect multiple supplies simultaneously.
The ETE MV150P1S1 multi-voltage transformer incorporates a 10/0/220/240 V primary terminal arrangement, providing greater connection flexibility than a transformer with a single fixed primary voltage. This configuration is particularly useful for electrical panel builders and OEM equipment manufacturers working with industrial control systems that require different nominal primary voltage connections.
The primary arrangement includes a 10 V adjustment tap. This tap is a specific feature of the P1 primary winding configuration and should only be used according to the manufacturer's wiring instructions. Confirm the exact primary terminal connections and the function of the 10 V adjustment tap with ETE before energising the transformer.
Correct primary selection is essential for obtaining the intended secondary output and avoiding incorrect excitation of the transformer winding. The supply voltage, operating frequency and connection arrangement should therefore be checked during panel design, installation and commissioning.
The MV150P1S1 features a 0/55/110 V secondary terminal arrangement, also identified by ETE as 55/0/55 V (0/55/110 V). This provides access to nominal 55 V AC and 110 V AC secondary connections, offering flexibility for industrial control circuits with different voltage requirements.
At the full 110 V AC output, the transformer has a calculated secondary current of approximately 1.36 A based on its 150 VA rating. At 55 V AC, dividing the total apparent power rating by the output voltage gives a theoretical current of approximately 2.73 A; however, the permissible current from an individual 55 V tapping must be confirmed against the manufacturer's winding and loading specifications.
The transformer's 10% voltage regulation should be considered when selecting connected equipment, particularly for circuits with varying loads or contactor energisation demands. The total connected load, permissible tap loading and inrush requirements should be assessed before the transformer is selected for an installation.
With dimensions of 96 mm in length, 76 mm in width and 103 mm in height, the ETE MV150P1S1 offers a compact footprint for industrial electrical cabinets and machinery control panels. Its 2.3 kg weight allows it to be accommodated within appropriately designed mounting arrangements.
The transformer is part of ETE's continuous-rated MV control transformer range, featuring Class E insulation, Class H varnish impregnation, IP20 touch-proof terminals and a protective core earth connection. The range is designed to EN 61558-1 and specifies an ambient operating temperature range of −10 to +35 °C.
A DIN rail mounting option is available for transformers in this size range, providing additional flexibility for panel assembly. The specified enclosure references are EPH 2 or EPN 1. Appropriate mechanical support, ventilation, protective devices and wiring arrangements should be incorporated into the complete electrical installation.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 150 VA | |
|---|---|---|
| Primary Voltage | 10/0/220/240V | |
| Secondary Voltage | 0/55/110V | |
| Phase | Single Phase | |
| Manufacturer | Eastern Transformers & Equipment (ETE) | |
| Manufacturer part number | MV150P1S1 | |
| Product series | MV Multi-Voltage Series | |
| Product type | Multi-voltage control circuit transformer | |
| Number of phases | Single-phase | |
| Rated apparent power | 150 VA | |
| Primary terminal arrangement | 10/0/220/240 V | |
| Primary voltage connections | 220 V and 240 V nominal connections, with a 10 V adjustment tap requiring manufacturer confirmation | |
| Primary adjustment tap | 10 V — confirm exact connections with ETE | |
| Secondary terminal arrangement | 0/55/110 V | |
| Secondary winding arrangement | 55/0/55 V (0/55/110 V) | |
| Secondary output connections | 55 V AC or 110 V AC | |
| Calculated secondary current at 110 V | Approximately 1.36 A at 150 VA | |
| Calculated secondary current at 55 V | Approximately 2.73 A at 150 VA, subject to the manufacturer's permitted tapping and loading arrangements | |
| Operating frequency | 50/60 Hz | |
| Insulation class | E | |
| Voltage regulation | 10% | |
| Terminal protection | IP20 touch-proof terminals | |
| Winding impregnation | Class H varnish | |
| Core earth connection | Provided | |
| Ambient operating temperature | −10 to +35 °C | |
| Design standard | EN 61558-1 | |
| Duty rating | Continuous | |
| Mounting | Panel mounting with DIN rail mounting option | |
| Length | 96 mm | |
| Width | 76 mm | |
| Height | 103 mm | |
| Dimensions (L × W × H) | 96 × 76 × 103 mm | |
| Weight | 2.3 kg | |
| Enclosure references | EPH 2 or EPN 1 | |
| Manufacturer catalogue reference | ETE Stock Control Transformer Range, March 2026 |
The ETE MV150P1S1 is a 150 VA single-phase multi-voltage control transformer designed to supply compatible industrial control circuits through selectable 55 V AC or 110 V AC secondary connections. Typical applications include electrical control panels, relays, contactors and machinery control equipment.
The transformer has 10/0/220/240 V primary terminals, including a 10 V adjustment tap. The exact connections and adjustment tap arrangement must be confirmed with ETE before installation or energisation.
Yes. Its 0/55/110 V secondary terminal arrangement provides nominal 55 V AC and 110 V AC connection options. The permissible loading of each tap and any simultaneous use must be checked against the manufacturer's connection instructions.
The transformer is rated at 150 VA. At 110 V AC, the calculated secondary current is approximately 1.36 A. At 55 V AC, the theoretical value calculated from 150 VA is approximately 2.73 A, but the permissible current from the individual 55 V tapping must be confirmed with ETE.
The 10 V adjustment tap forms part of the transformer's multi-voltage primary arrangement. Its exact function and connection method must be confirmed with ETE. Installers should not assume a wiring configuration based solely on the terminal markings.
The transformer measures 96 × 76 × 103 mm (length × width × height) and weighs 2.3 kg.
The MV150P1S1 features Class E insulation and 10% voltage regulation. ETE also specifies Class H varnish impregnation, IP20 touch-proof terminals and a protective core earth connection for this transformer.
The specified enclosure references are EPH 2 or EPN 1. The final enclosure selection should account for mounting, ventilation, electrical protection and the environmental requirements of the installation.
The ETE MV150P1S1 provides a versatile solution for industrial control power requirements, combining a 150 VA rating with multi-voltage primary connections and selectable 55 V or 110 V secondary outputs. Its Class E insulation, 10% voltage regulation, compact dimensions and EPH 2 or EPN 1 enclosure options make it a practical choice for panel builders, OEM machinery manufacturers and industrial electrical engineers. The 10 V primary adjustment tap should be connected only after confirming the correct arrangement with ETE.