Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ETE MV100P1S1 is a 100 VA single-phase multi-voltage control transformer with 10/0/220/240 V primary terminals, selectable 55 V or 110 V AC secondary connections, Class E insulation, 12% voltage regulation and EPH 1 or EPN 1 enclosure compatibility.
£26.10
The ETE MV100P1S1 is a compact, versatile 100 VA single-phase multi-voltage control transformer designed for industrial electrical control panels, machinery and automation equipment requiring selectable AC control voltages. Manufactured by Eastern Transformers & Equipment (ETE), this transformer belongs to the established ETE MV multi-voltage transformer series, offering flexible primary connections and a tapped secondary winding for applications requiring 55 V AC or 110 V AC.
The MV100P1S1 features a 10/0/220/240 V primary terminal arrangement and a 0/55/110 V secondary terminal arrangement. The secondary winding provides nominal 55 V and 110 V output connection options, making the transformer suitable for compatible control relays, contactors, signalling devices and other industrial electrical equipment. The manufacturer also identifies the secondary configuration as 55/0/55 V (0/55/110 V), allowing consideration of a centre-tapped 110 V arrangement where the correct terminal configuration is confirmed.
A distinguishing feature of this model is its 10 V primary adjustment tap, which provides additional connection flexibility beyond the conventional 220 V and 240 V primary terminals. Because the exact relationship of this adjustment tap to the other primary connections must be established from the manufacturer's connection diagram, the correct wiring arrangement should be confirmed with ETE before installation.
With a rated apparent power of 100 VA, Class E insulation and 12% voltage regulation, the MV100P1S1 offers practical control voltage transformation in a compact format. Measuring just 85 × 70 × 93 mm and weighing 1.5 kg, it is particularly suitable for smaller control cabinets. Compatible enclosure references are ETE EPH 1 or EPN 1, and the manufacturer identifies a DIN rail mounting option for this transformer size.
The ETE MV100P1S1 is designed for electrical installations requiring flexibility in both primary and secondary voltage connections. Its 10/0/220/240 V primary arrangement and 0/55/110 V secondary arrangement make it particularly useful where control circuits must accommodate different voltage requirements without using separate transformer models.
For conventional primary supply connections, the transformer provides nominal 220 V AC and 240 V AC input options. The additional 10 V primary adjustment tap offers further flexibility, but it must not be treated as an independent 10 V supply input. The exact winding relationship and permitted adjustment connections should be confirmed against ETE's engineering drawing or directly with the manufacturer before energisation.
On the secondary side, the transformer provides 55 V AC and 110 V AC connection options. ETE also describes this secondary arrangement as 55/0/55 V (0/55/110 V), identifying the potential for a centre-tapped 110 V output. The correct terminal references, centre-point connection and earthing arrangement must be confirmed for the intended application.
The 100 VA rated apparent power corresponds to a calculated nominal full-load current of approximately 0.91 A at 110 V AC. Dividing the same total apparent power by 55 V gives a theoretical current equivalent of approximately 1.82 A; however, the allowable current through an individual secondary section or tap depends on the winding arrangement. The full transformer rating must not automatically be assumed to be available from every individual tap.
The specified 12% voltage regulation describes the secondary voltage variation between no-load and rated-load conditions. This is particularly relevant when supplying electromagnetic control devices, which may draw considerably greater apparent power during initial energisation than during normal operation. Electrical designers should assess both continuous loading and simultaneous contactor or relay inrush requirements.
The MV100P1S1 features a Class E insulation system, Class H varnish impregnation, IP20 touch-proof terminals and a protective core earth connection. Its continuous-rated construction is designed to EN 61558-1 and is specified for operation at 50/60 Hz within an ambient temperature range of −10 to +35 °C.
With compact dimensions of 85 × 70 × 93 mm and a weight of 1.5 kg, the transformer is well suited to smaller electrical control panels. A DIN rail mounting option supports flexible cabinet assembly, while the specified EPH 1 or EPN 1 enclosure references provide additional installation options where protective housing is required.
Correct primary tap selection, secondary winding connections, protective earthing, circuit protection, conductor sizing and ventilation are essential. Where a centre-tapped 110 V supply is required, the installation must be designed and verified for that purpose rather than assuming that all 110 V transformer configurations provide identical protective characteristics.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 100 VA | |
|---|---|---|
| Primary Voltage | 10/0/220/240V | |
| Secondary Voltage | 0/55/110V | |
| Phase | Single Phase | |
| Manufacturer | Eastern Transformers & Equipment (ETE) | |
| Brand | ETE | |
| Series | MV Multi-Voltage Control Transformers | |
| Manufacturer part number | MV100P1S1 | |
| Product type | Industrial multi-voltage control circuit transformer | |
| Transformer configuration | Multi-tapped primary and secondary windings | |
| Number of phases | Single-phase | |
| Rated apparent power | 100 VA | |
| Primary terminal arrangement | 10/0/220/240 V | |
| Nominal primary voltage options | 220 V AC and 240 V AC | |
| Primary adjustment tap | 10 V | |
| Primary adjustment connection note | Confirm the correct terminal arrangement with ETE before wiring. | |
| Secondary terminal arrangement | 0/55/110 V | |
| Alternative manufacturer secondary notation | 55/0/55 V | |
| Secondary output connection options | 55 V AC or 110 V AC | |
| Calculated nominal full-load secondary current at 110 V | Approximately 0.91 A | |
| Calculated current equivalent at 55 V | Approximately 1.82 A; verify individual winding and tap current limits before applying the full load. | |
| Calculated nominal primary current at 220 V | Approximately 0.45 A, based on rated apparent power | |
| Calculated nominal primary current at 240 V | Approximately 0.42 A, based on rated apparent power | |
| Rated frequency | 50/60 Hz | |
| Duty rating | Continuous | |
| Insulation class | Class E | |
| Varnish impregnation | Class H | |
| Voltage regulation | 12% | |
| Terminal protection | IP20 touch-proof terminals | |
| Earthing provision | Core earth connection | |
| Ambient operating temperature | −10 to +35 °C | |
| Design standard | EN 61558-1 | |
| Mounting | Conventional mounting with DIN rail mounting option | |
| Length | 85 mm | |
| Width | 70 mm | |
| Height | 93 mm | |
| Dimensions (L × W × H) | 85 × 70 × 93 mm | |
| Weight | 1.5 kg | |
| Compatible enclosure references | EPH 1 or EPN 1 | |
| Typical installation | Industrial control panels and electrical machinery cabinets | |
| Country of manufacture | United Kingdom | |
| Product range reference | ETE Stock Control Transformer Range, March 2026 | |
| Manufacturer product reference | ETE MV100P1S1 Product Information |
The ETE MV100P1S1 is a 100 VA single-phase multi-voltage control transformer designed to provide selectable 55 V AC or 110 V AC secondary connections for industrial electrical control panels, machinery and automation equipment.
The transformer has a 10/0/220/240 V primary terminal arrangement. The exact connection method for the 10 V adjustment tap should be confirmed with ETE before installation.
The 10 V primary adjustment tap provides an additional winding connection for primary voltage adjustment. Its precise relationship to the 0, 220 V and 240 V terminals must be confirmed using ETE's connection instructions. It should not be assumed to be an independent 10 V input.
The transformer has 0/55/110 V secondary terminals, providing nominal 55 V AC and 110 V AC output connection options, subject to the correct wiring arrangement.
ETE identifies the secondary configuration as 55/0/55 V (0/55/110 V), indicating a centre-tapped 110 V winding arrangement. The actual terminal identification and any centre-point earthing requirements must be confirmed before installation.
The MV100P1S1 has a rated apparent power of 100 VA and is designed for continuous control circuit operation within its specified rating.
At 100 VA and 110 V AC, the calculated nominal full-load secondary current is approximately 0.91 A.
Not necessarily. Although 100 VA divided by 55 V gives a theoretical current equivalent of approximately 1.82 A, the permissible current through an individual winding section or tap must be confirmed from ETE's winding and terminal specifications.
The transformer provides AC output. It does not incorporate a rectifier or regulated DC power supply, so equipment requiring DC voltage needs suitable additional power conversion equipment.
The transformer has a Class E insulation system and a specified 12% voltage regulation. ETE also identifies Class H varnish impregnation as part of its construction.
The transformer measures 85 mm long × 70 mm wide × 93 mm high and weighs 1.5 kg.
Yes. ETE identifies a DIN rail mounting option for this 100 VA multi-voltage transformer, allowing installation in suitable electrical control panel arrangements.
The specified compatible enclosure references are ETE EPH 1 or EPN 1. Final selection should account for installation conditions, ventilation and the required environmental protection.
Yes. ETE specifies IP20 touch-proof terminals and a core earth connection for this transformer series. Protective earthing must be implemented according to the installation requirements.
The MV100P1S1 is specified for 50/60 Hz operation and an ambient temperature range of −10 to +35 °C.
The correct wiring arrangement should be checked against the manufacturer's engineering documentation or confirmed directly with Eastern Transformers & Equipment (ETE), particularly when using the 10 V primary adjustment tap or the centre-tapped secondary configuration.
ETE MV multi-voltage control transformers provide flexible AC voltage transformation for industrial electrical installations. With its 100 VA rating, multi-tapped primary winding, selectable 55 V and 110 V secondary connections, Class E insulation and compact construction, the MV100P1S1 offers a practical solution for electrical panel builders, machinery manufacturers and maintenance engineers requiring adaptable control power.
We use cookies