ETE MV1000P2S2 is a 1000 VA single-phase multi-voltage control transformer with 20/0/380/420 V primary terminals, a 10/0/220/240 V tapped secondary requiring manufacturer-confirmed adjustment connections, Class E insulation, 4% voltage regulation and EPN 3 enclosure compatibility.
£117.68
The ETE MV1000P2S2 is a high-capacity 1000 VA (1 kVA) single-phase multi-voltage control transformer designed for industrial electrical control panels, machinery and automation systems requiring flexible AC voltage transformation. Part of the ETE MV multi-voltage control transformer range, this model features 20/0/380/420 V primary terminals and 10/0/220/240 V secondary terminals, providing a tapped secondary output arrangement for compatible industrial control circuits.
The MV1000P2S2 combines a substantial 1 kVA apparent power rating with multiple primary and secondary winding connections. Its primary winding incorporates terminals marked 380 V and 420 V, while the secondary winding includes terminals marked 220 V and 240 V, together with a 10 V adjustment tap. This arrangement offers flexibility for industrial installations where the available AC supply must be transformed to an appropriate control voltage.
The secondary output is specified as a tapped output according to the manufacturer's datasheet. The exact relationship between the 10 V adjustment terminal and the other secondary terminals must be confirmed with ETE before installation. Similarly, the permitted primary connection combinations should be verified against the manufacturer's approved wiring information rather than inferred from the terminal markings alone.
Featuring Class E insulation and 4% voltage regulation, the MV1000P2S2 provides defined electrical characteristics for industrial transformer selection. Its dimensions of 150 × 125 × 145 mm and weight of 9.8 kg support integration into appropriately designed industrial electrical cabinets. The specified compatible enclosure reference is ETE EPN 3.
Listed in the ETE Stock Control Transformer Range, March 2026, the MV1000P2S2 is a practical choice for electrical panel builders, machinery manufacturers and maintenance engineers requiring a higher-capacity transformer with configurable AC control voltage connections.
The ETE MV1000P2S2 provides a high-capacity solution for industrial electrical installations requiring a transformer with multiple primary and secondary connection options. Its 20/0/380/420 V primary winding and 10/0/220/240 V secondary winding make it suitable for applications where an industrial AC supply must be transformed to a compatible higher-voltage AC control circuit.
The primary winding incorporates terminals marked 380 V and 420 V, together with an additional 20 V terminal. These markings identify available winding connections but do not independently establish every permissible supply voltage combination. The correct primary terminal arrangement should be verified against ETE's approved connection diagram before the transformer is energised.
The secondary winding features terminals marked 220 V and 240 V, together with a 10 V adjustment tap. The manufacturer's specification describes the output as a tapped output, with the exact terminal arrangement to be determined from the approved datasheet. The 10 V terminal should not be assumed to provide an independent 10 V supply, and the relationship between the secondary connections must be confirmed with ETE.
At the total rated apparent power of 1000 VA, the calculated current equivalents are approximately 4.55 A at 220 V and 4.17 A at 240 V. These figures are derived by dividing the transformer rating by the nominal secondary voltage. They should not be interpreted as independently verified current ratings for every tapped output arrangement. The applicable winding and tap loading limits should be checked before finalising the connected load.
The specified 4% voltage regulation is relevant when selecting a transformer for control circuits containing electromagnetic loads. Contactors, relays and solenoids may draw greater apparent power during energisation than during normal operation. Electrical designers should therefore assess the total steady-state load, simultaneous switching requirements and acceptable voltage range of connected equipment.
With a rated capacity of 1 kVA, the MV1000P2S2 is particularly relevant to industrial control systems containing multiple compatible AC devices. The transformer should be selected according to the aggregate apparent power requirements of the installation, while allowing for equipment starting demands and the manufacturer's winding-specific limits.
The MV1000P2S2 features Class E insulation, dimensions of 150 × 125 × 145 mm and a weight of 9.8 kg. These characteristics should be considered when planning mounting arrangements, mechanical support and enclosure space. The specified compatible enclosure reference is ETE EPN 3.
The transformer provides AC voltage transformation rather than regulated DC output. Equipment requiring DC control voltage will need appropriate additional conversion components. Installation should account for correct primary and secondary terminal selection, suitable circuit protection, conductor sizing, secure mounting, ventilation and protective earthing where applicable.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 1000 VA | |
|---|---|---|
| Primary Voltage | 20/0/380/420V | |
| Secondary Voltage | 10/0/220/240V | |
| Phase | Single Phase | |
| Brand | ETE | |
| Manufacturer part number | MV1000P2S2 | |
| Product family | MV Multi-Voltage Control Transformers | |
| Product category | Industrial Control Transformers | |
| Transformer configuration | Multi-tapped primary and secondary windings | |
| Number of phases | Single-phase | |
| Rated apparent power | 1000 VA | |
| Rated apparent power in kVA | 1 kVA | |
| Primary terminal arrangement | 20/0/380/420 V | |
| Primary voltage terminal markings | 380 V and 420 V | |
| Additional primary terminal | 20 V | |
| Primary connection requirement | Verify permitted terminal combinations with ETE. | |
| Secondary terminal arrangement | 10/0/220/240 V | |
| Secondary voltage terminal markings | 220 V and 240 V | |
| Secondary adjustment tap | 10 V | |
| Secondary output connection | Tapped output according to the manufacturer's datasheet | |
| Adjustment tap connection note | Confirm the correct 10 V adjustment tap and associated terminal connections with ETE. | |
| Calculated apparent-power current equivalent at 220 V secondary | Approximately 4.55 A | |
| Calculated apparent-power current equivalent at 240 V secondary | Approximately 4.17 A | |
| Calculated apparent-power current equivalent at 380 V primary | Approximately 2.63 A | |
| Calculated apparent-power current equivalent at 420 V primary | Approximately 2.38 A | |
| Insulation class | E | |
| Voltage regulation | 4% | |
| Length | 150 mm | |
| Width | 125 mm | |
| Height | 145 mm | |
| Overall dimensions (L × W × H) | 150 × 125 × 145 mm | |
| Weight | 9.8 kg | |
| Compatible enclosure reference | EPN 3 | |
| Typical installation | Industrial electrical control panels and machinery cabinets | |
| Catalogue reference | ETE Stock Control Transformer Range, March 2026 |
The ETE MV1000P2S2 is a 1000 VA single-phase multi-voltage control transformer designed for industrial AC control circuits requiring a tapped primary and secondary winding arrangement.
The transformer has a rated apparent power of 1000 VA, equivalent to 1 kVA. Connected equipment must remain within the applicable transformer and winding ratings.
The primary terminal markings are 20/0/380/420 V. The correct terminal combinations should be verified against ETE's approved connection information.
The secondary winding has terminals marked 10/0/220/240 V. The output is configured using the manufacturer's specified tapped connection arrangement.
The secondary includes terminals marked 220 V and 240 V. The exact nominal output available for a particular primary connection must be confirmed from ETE's wiring information.
The 10 V adjustment terminal provides an additional secondary winding connection. Its precise function and permitted use must be confirmed with ETE before installation.
This should not be assumed. The 10 V terminal forms part of the transformer's tapped winding arrangement, and its permitted connection method must be verified with ETE.
The transformer has primary terminals marked 380 V and 420 V, together with an additional 20 V terminal. The correct connection arrangement for a nominal 400 V AC supply must be confirmed with ETE rather than inferred from terminal markings alone.
At 1000 VA and 220 V, the calculated current equivalent is approximately 4.55 A, assuming the total transformer rating applies to the approved output configuration.
At 1000 VA and 240 V, the calculated current equivalent is approximately 4.17 A, assuming the total transformer rating applies to the approved output configuration.
Dividing the rated apparent power by the marked primary voltages gives approximately 2.63 A at 380 V and 2.38 A at 420 V. These are mathematical apparent-power equivalents rather than independently verified operating input currents.
The MV1000P2S2 provides AC output. It does not incorporate a rectifier or regulated DC power supply.
The transformer has Class E insulation and a specified 4% voltage regulation.
The transformer measures 150 mm long × 125 mm wide × 145 mm high and weighs 9.8 kg.
The specified compatible enclosure reference is ETE EPN 3. Final enclosure selection should account for the installation environment, mounting requirements and ventilation.
Yes. Its 1000 VA rating, multi-tapped windings and industrial construction make it suitable for appropriately designed control panels using compatible AC equipment.
The specified 4% voltage regulation describes secondary voltage variation under changing load conditions. Connected equipment should have suitable voltage tolerances for the intended application.
The correct primary and secondary wiring arrangements should be obtained from ETE or its approved technical documentation, particularly when using the 10 V adjustment tap.
The ETE MV1000P2S2 combines a substantial 1000 VA rating with flexible primary connections and a tapped secondary winding incorporating 220 V and 240 V terminals. Its Class E insulation, 4% voltage regulation and EPN 3 enclosure compatibility make it a practical component for industrial electrical panel builders, machinery manufacturers and maintenance engineers requiring higher-capacity configurable AC control power.