Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ETE MV10000P1S1 is a 10000 VA (10 kVA) single-phase multi-voltage control transformer with 10/0/220/240V primary terminals, 0/55/110V secondary terminals, 55V or 110V output taps, a 10V primary adjustment tap requiring connection confirmation with ETE, Class F insulation, 2% voltage regulation, ETS 1 enclosure reference, dimensions of 300 x 360 x 330 mm and a weight of 90 kg.
£847.50
The ETE MV10000P1S1 is a heavy-duty 10000 VA (10 kVA) single-phase multi-voltage control transformer designed for industrial electrical installations requiring substantial AC control and auxiliary power capacity. Part of the ETE MV multi-voltage control transformer range, it features primary terminals marked 10/0/220/240V and secondary terminals marked 0/55/110V, providing a tapped voltage arrangement for compatible industrial machinery, control panels and electrical equipment.
The MV10000P1S1 offers a specified 55 V or 110 V AC tapped secondary output, making it suitable for consideration where industrial control equipment requires one of these nominal voltages. Its primary terminal arrangement includes a 10 V adjustment tap, which must be connected only in accordance with the manufacturer's confirmed instructions. ETE should be consulted to verify the correct primary adjustment tap connections before the transformer is installed or energised.
With Class F insulation, specified 2% voltage regulation and an ETS 1 enclosure reference, the ETE MV10000P1S1 provides a substantial transformer solution for demanding industrial applications. Measuring 300 × 360 × 330 mm and weighing 90 kg, it requires appropriately designed mechanical support, suitable handling equipment and careful consideration of electrical protection and ventilation. Its technical specifications are drawn from the ETE Stock Control Transformer Range, March 2026.
The ETE MV10000P1S1 is designed for industrial installations requiring a substantial transformer capacity and a choice of specified secondary voltages. Its primary terminals are marked 10/0/220/240V, while its secondary terminals are marked 0/55/110V. The catalogue identifies 55 V or 110 V output taps, allowing the transformer to be considered for equipment requiring either nominal secondary voltage, subject to the correct connection arrangement and the manufacturer's operating limits.
The primary arrangement incorporates a 10 V adjustment tap. This adjustment facility should not be interpreted as a separate 10 V supply input or connected using assumptions based solely on the terminal markings. The relationship between the adjustment tap and the other primary terminals must be verified against the ETE connection diagram. Confirm the correct primary terminal connections directly with ETE before installation or commissioning. The transformer must only be connected to a supply compatible with the manufacturer's approved primary arrangements.
With a 10000 VA (10 kVA) rated apparent power, the MV10000P1S1 provides substantial capacity for appropriately selected AC control and auxiliary equipment. At a nominal 55 V output, dividing 10000 VA by 55 V gives approximately 181.82 A. At a nominal 110 V output, the equivalent calculation gives approximately 90.91 A. These figures are theoretical apparent-power sizing references only, not independently stated manufacturer output current ratings. The permissible current at each tap, any shared winding limitations and the total connected load must be confirmed from ETE's technical documentation. The full rated apparent power must not be assumed to be independently available at both output taps simultaneously.
The transformer's specified 2% voltage regulation is relevant when evaluating the voltage supplied to connected industrial equipment. Transformer voltage regulation generally describes the change in secondary voltage between specified loading conditions, commonly comparing no-load and rated-load operation. It does not mean that the transformer actively stabilises its output or guarantees a fixed ±2% voltage tolerance under all operating conditions. Engineers should consider the expected input supply variation, secondary loading and connected equipment voltage tolerance when assessing suitability.
The MV10000P1S1 features Class F insulation, which describes the thermal classification of its insulation system. This must not be confused with an electrical protection classification such as Class II. The catalogue also lists ETS 1 as the enclosure reference. That reference should be checked against ETE's documentation to determine the correct enclosure arrangement, associated dimensions and installation requirements. It does not independently establish an ingress protection rating or confirm suitability for any particular environmental conditions.
Weighing 90 kg and measuring 300 × 360 × 330 mm, the MV10000P1S1 requires appropriate installation planning. Suitable lifting equipment, mechanical support, fixing arrangements, access clearances and ventilation must be considered. Electrical installation should also include correctly selected primary and secondary protection, conductor sizing and load assessment, including any significant starting or inrush demands. Installation and commissioning should be performed by suitably qualified personnel in accordance with ETE's instructions and applicable electrical requirements.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 10000 VA | |
|---|---|---|
| Primary Voltage | 10/0/220/240V | |
| Secondary Voltage | 0/55/110V | |
| Phase | Single Phase | |
| Manufacturer | ETE | |
| Product range | MV Multi-Voltage Control Transformers | |
| Model / SKU | MV10000P1S1 | |
| Product type | Multi-voltage control transformer | |
| Phase configuration | Single-phase | |
| Rated apparent power | 10000 VA | |
| Rated apparent power (kVA) | 10 kVA | |
| Primary terminals | 10/0/220/240V | |
| Secondary terminals | 0/55/110V | |
| Output connection | 55 V or 110 V taps | |
| Adjustment tap note | 10 V primary adjustment tap; confirm connections with ETE | |
| Insulation class | F | |
| Voltage regulation | 2% | |
| Length | 300 mm | |
| Width | 360 mm | |
| Height | 330 mm | |
| Dimensions (L × W × H) | 300 × 360 × 330 mm | |
| Weight | 90 kg | |
| Enclosure reference | ETS 1 | |
| Catalogue reference | ETE Stock Control Transformer Range, March 2026 |
The ETE MV10000P1S1 is a 10000 VA (10 kVA) single-phase multi-voltage control transformer intended for compatible industrial control and auxiliary AC power applications. It features a tapped primary arrangement and 55 V or 110 V secondary output taps, with connections to be confirmed against ETE's documentation.
The transformer has a rated apparent power of 10000 VA, equivalent to 10 kVA. Connected loads must remain within the manufacturer's permitted operating limits.
The transformer has primary terminals marked 10/0/220/240V. The correct input connection, including the function of the 10 V adjustment tap, must be confirmed with ETE before energising the transformer.
The transformer has secondary terminals marked 0/55/110V. The specified output connection is 55 V or 110 V taps, subject to the manufacturer's approved terminal arrangement and operating limits.
The transformer has 55 V and 110 V secondary tap markings, but the permitted connection and loading arrangement must be verified with ETE. The full 10 kVA rating must not be assumed to be independently available at both taps simultaneously.
The specification identifies a 10 V primary adjustment tap within the primary terminal arrangement. Its purpose and correct connection must be confirmed directly with ETE. The terminal markings alone are not sufficient to establish the approved adjustment wiring.
The stated 2% voltage regulation describes secondary voltage variation between specified loading conditions. It does not mean that the transformer actively regulates voltage or guarantees a fixed ±2% output tolerance under all conditions.
The MV10000P1S1 has Class F insulation. This is a thermal insulation classification and should not be confused with an electrical protection classification such as Class II.
The transformer measures 300 × 360 × 330 mm (length × width × height) and weighs 90 kg. Suitable lifting arrangements and mechanical support should be provided during installation.
The ETE catalogue lists ETS 1 as the enclosure reference. The appropriate enclosure arrangement should be verified against ETE's documentation. This designation does not independently establish an ingress protection rating.
At a nominal 55 V output, 10000 VA divided by 55 V gives approximately 181.82 A. At a nominal 110 V output, the equivalent calculation gives approximately 90.91 A. These are theoretical sizing references, not independently stated manufacturer current ratings. Actual permissible output current, tap loading and connection arrangements must be confirmed with ETE.
The ETE MV10000P1S1 combines 10000 VA (10 kVA) rated apparent power with a single-phase multi-voltage control transformer design, featuring 10/0/220/240V primary terminals and 0/55/110V secondary terminals. With Class F insulation, specified 2% voltage regulation and an ETS 1 enclosure reference, it is a practical option for substantial industrial control and auxiliary power installations. The 10 V primary adjustment tap and all associated terminal connections must be confirmed with ETE before installation or commissioning.