Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ETE DV250P6S5 is a 250 VA single-phase dual-input-voltage industrial control transformer with selectable 240 V AC or 415 V AC primary connections, a 240 V AC secondary output, Class E insulation, 8% voltage regulation and EPH 3 or EPN 2 enclosure references.
£45.38
The ETE DV250P6S5 is a versatile 250 VA single-phase industrial control transformer designed to provide a nominal 240 V AC secondary output from either a 240 V AC or 415 V AC primary supply. Manufactured by Eastern Transformers & Equipment (ETE), this transformer forms part of the established ETE DV dual-input-voltage stock control transformer range, developed for electrical panel builders, machinery manufacturers and industrial automation applications requiring flexible primary voltage connections.
Unlike a conventional single-input-voltage transformer, the DV250P6S5 features a 0/240/415 V primary terminal arrangement, allowing the installer to select the appropriate primary connection for the available electrical supply. Its 0/240 V secondary terminals provide a single nominal 240 V AC output, making it a practical solution for industrial control circuits and auxiliary electrical equipment operating at this voltage.
With a rated apparent power of 250 VA, Class E insulation and 8% voltage regulation, the ETE DV250P6S5 offers dependable performance for appropriately sized control circuit loads. Its continuous-duty construction, IP20 touch-proof terminals, Class H varnish impregnation and dedicated core earth connection support integration into industrial electrical installations.
Measuring 120 × 88 × 120 mm and weighing 3.9 kg, the DV250P6S5 is designed for installation in electrical control cabinets and machinery panels. Its specified EPH 3 or EPN 2 enclosure references provide suitable enclosure options where additional physical protection is required.
The ETE DV250P6S5 is designed for industrial electrical systems where the available primary supply may be either 240 V AC or 415 V AC. Its tapped primary winding features 0/240/415 V terminals, allowing the appropriate input connection to be selected during installation. When correctly connected to the matching primary voltage, the transformer provides a nominal 240 V AC secondary output through its 0/240 V secondary terminals.
This dual-input arrangement is particularly beneficial for OEM machinery manufacturers and electrical panel builders producing equipment for different industrial supply configurations. The DV250P6S5 can accommodate either supported primary voltage without requiring separate transformer models for each installation. When supplied from 415 V AC, it steps the voltage down to 240 V AC; when supplied from 240 V AC, it provides a nominal 240 V AC secondary supply through the transformer. The correct primary terminals must always be selected according to the available supply and the manufacturer's connection instructions.
The transformer's 250 VA continuous rating provides a calculated full-load secondary current of approximately 1.04 A at its nominal 240 V AC output. This calculation is based on the rated apparent power divided by the secondary voltage. When selecting the transformer, engineers should also consider the combined apparent power of connected devices, operating characteristics, permissible voltage variation and any short-duration inrush requirements.
The specified 8% voltage regulation describes the secondary voltage variation between no-load and rated-load conditions under the applicable test conditions. This characteristic is important when supplying contactors, relays and other control equipment with defined operating voltage tolerances. The nominal 240 V AC output should not be interpreted as a perfectly constant voltage under every loading condition.
The DV250P6S5 incorporates Class E insulation, IP20 touch-proof terminals, Class H varnish impregnation and a dedicated core earth connection. For installations requiring additional protection, the specified enclosure references are EPH 3 or EPN 2. Correct primary and secondary overcurrent protection, protective earthing, ventilation, cable sizing and mounting arrangements remain essential for safe and dependable operation.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 250 VA | |
|---|---|---|
| Primary Voltage | 0/240/415V | |
| Secondary Voltage | 0/240V | |
| Phase | Single Phase | |
| Manufacturer | Eastern Transformers & Equipment (ETE) | |
| Series | DV Dual-Input-Voltage Stock Control Transformer Range | |
| Model | DV250P6S5 | |
| Product type | Industrial control circuit transformer | |
| Transformer configuration | Dual-input-voltage primary, single-voltage secondary | |
| Number of phases | Single-phase | |
| Rated apparent power | 250 VA | |
| Primary voltage options | 240 V AC or 415 V AC | |
| Primary terminals | 0/240/415 V | |
| Secondary voltage | 240 V AC | |
| Secondary terminals | 0/240 V | |
| Output connection | 240 V | |
| Rated frequency | 50/60 Hz | |
| Duty rating | Continuous | |
| Insulation class | Class E | |
| Varnish impregnation | Class H | |
| Voltage regulation | 8% | |
| Terminal protection | IP20 touch-proof terminals | |
| Core earthing | Dedicated core earth connection | |
| Ambient operating temperature | −10 °C to +35 °C | |
| Design standard | EN 61558-1 | |
| Calculated full-load secondary current | Approximately 1.04 A | |
| Calculated nominal primary current at 240 V AC | Approximately 1.04 A, excluding losses | |
| Calculated nominal primary current at 415 V AC | Approximately 0.60 A, excluding losses | |
| Length | 120 mm | |
| Width | 88 mm | |
| Height | 120 mm | |
| Dimensions (L × W × H) | 120 × 88 × 120 mm | |
| Weight | 3.9 kg | |
| Enclosure reference | EPH 3 or EPN 2 | |
| Installation type | Electrical control panel or suitable enclosure mounting | |
| Product range reference | ETE Stock Control Transformer Range, March 2026 |
The ETE DV250P6S5 is a 250 VA single-phase dual-input-voltage control transformer designed to provide a nominal 240 V AC output from either a 240 V AC or 415 V AC primary supply. It is suitable for compatible industrial machinery control circuits and auxiliary electrical equipment.
Dual-input voltage means the transformer has 0/240/415 V primary terminals, allowing it to be connected for either a 240 V AC or 415 V AC supply. The correct primary terminal connection must be selected for the available supply voltage.
The ETE DV250P6S5 has a rated apparent power of 250 VA. Connected equipment must remain within this rating and the transformer's applicable operating limits.
The transformer has 0/240/415 V primary terminals and 0/240 V secondary terminals. When connected correctly to either supported primary voltage, it provides a nominal 240 V AC output.
Based on its 250 VA rating and 240 V AC secondary voltage, the calculated full-load secondary current is approximately 1.04 A. Actual transformer selection must also account for connected load characteristics and any inrush requirements.
The DV250P6S5 uses a Class E insulation system designed in accordance with EN 61558-1. Its windings also feature protective Class H varnish impregnation.
The transformer measures 120 mm long, 88 mm wide and 120 mm high, with a specified weight of 3.9 kg.
The ETE DV250P6S5 has a specified 8% voltage regulation. This should be considered when assessing the secondary voltage requirements of connected control equipment under changing load conditions.
The specified enclosure references are EPH 3 or EPN 2. Enclosure selection should account for the installation environment, transformer dimensions, ventilation requirements and applicable electrical safety regulations.
Yes. The DV250P6S5 is designed for industrial control applications and can be installed within a suitably designed electrical control panel or enclosure, with appropriate mounting, ventilation, circuit protection and protective earthing.
No. The ETE DV250P6S5 provides a nominal 240 V AC secondary output, not 240 V DC. Equipment requiring direct current needs a suitable DC power supply or appropriately rated rectification and conditioning equipment.
No. The 0/240/415 V primary terminals provide alternative connections for the supported input voltages. The transformer must be connected using the correct primary terminals for the available supply, following the manufacturer's instructions. It is not designed to combine two independent primary supplies.
ETE DV dual-input-voltage control transformers offer practical flexibility for industrial electrical installations. With its selectable 240 V AC or 415 V AC primary connection, 240 V AC secondary output, 250 VA continuous rating, Class E insulation, 8% voltage regulation and robust industrial construction, the ETE DV250P6S5 provides a dependable solution for OEM machinery, electrical control panels and industrial automation applications requiring a dedicated 240 V AC control supply.
We use cookies