Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ETE WV2500P7S7 is a 2500 VA single-phase wide-input-voltage control transformer with 380-480 V primary voltage taps, dual 0/24 V secondary windings configurable for 24 V parallel or 48 V series output, Class E insulation, 3% voltage regulation and an EPN 5 enclosure reference.
£247.80
The ETE WV2500P7S7 is a high-capacity 2500 VA (2.5 kVA) single-phase wide-input-voltage control transformer designed to provide reliable low-voltage AC power for industrial control circuits, electrical panels and automation equipment. Part of the ETE WV wide-input-voltage control transformer series, it combines multiple primary voltage taps with configurable secondary windings, making it suitable for electrical panel builders, OEM machinery manufacturers and industrial automation engineers requiring substantial control power capacity.
Featuring 0/380/400/420/440/460/480 V primary terminals, the WV2500P7S7 supports six nominal primary supply voltages through dedicated winding taps. Its two 0/24 V secondary windings can be connected in parallel to provide 24 V AC or in series to provide 48 V AC. This flexible winding arrangement enables the transformer to accommodate different industrial control voltage requirements while retaining its total rated capacity of 2500 VA.
With Class E insulation and 3% voltage regulation, the ETE WV2500P7S7 offers defined electrical performance characteristics for demanding industrial control applications. Its dimensions of 192 × 161 × 185 mm, weight of 24 kg and specified EPN 5 enclosure reference provide essential information for mechanical mounting, panel layout and enclosure selection.
Industrial control transformers convert an available AC supply voltage into a suitable secondary voltage for control circuits and connected equipment. The ETE WV2500P7S7 provides a flexible solution for installations operating from nominal 380, 400, 420, 440, 460 or 480 V AC supplies. Its dedicated primary winding taps allow the appropriate voltage connection to be selected, making it suitable for industrial machinery and electrical distribution systems with different nominal supply requirements.
The transformer incorporates two 0/24 V secondary windings that can be configured according to the required control voltage. When correctly connected in parallel, they provide a nominal 24 V AC output, with the connected load shared between the windings. When correctly connected in series, they provide a nominal 48 V AC output. The total rated apparent power remains 2500 VA in either configuration. Correct winding polarity is essential for parallel operation, and all connections should follow the manufacturer's approved terminal arrangement.
At its rated capacity, the calculated nominal secondary current is approximately 104.17 A at 24 V or 52.08 A at 48 V. These values are derived from the transformer's rated apparent power and nominal output voltage; permissible loading must also comply with the manufacturer's individual winding ratings and installation requirements. The relatively high available current makes appropriate conductor sizing, terminal selection and secondary circuit protection especially important.
The specified 3% voltage regulation provides a useful performance characteristic for applications where secondary voltage stability matters. Together with Class E insulation and the EPN 5 enclosure reference, the WV2500P7S7 is suitable for integration into appropriately engineered industrial control systems. Its 24 kg weight must be considered when designing mechanical supports and mounting arrangements, while adequate ventilation and electrical clearances remain essential for dependable operation.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 2500 VA | |
|---|---|---|
| Primary Voltage | 0/380/400/420/440/460/480V | |
| Secondary Voltage | 0/24V + 0/24V | |
| Phase | Single Phase | |
| Manufacturer | ETE | |
| Series | WV Wide-Input-Voltage Control Transformers | |
| Model | WV2500P7S7 | |
| Product type | Wide-input-voltage control transformer | |
| Transformer configuration | Single-phase | |
| Rated apparent power | 2500 VA | |
| Rated capacity | 2.5 kVA | |
| Primary terminals | 0/380/400/420/440/460/480 V | |
| Primary voltage options | 380 / 400 / 420 / 440 / 460 / 480 V AC | |
| Secondary winding 1 | 0/24 V | |
| Secondary winding 2 | 0/24 V | |
| Secondary winding arrangement | Dual secondary windings | |
| Parallel secondary output | 24 V AC | |
| Series secondary output | 48 V AC | |
| Calculated total secondary current at 24 V | Approximately 104.17 A in parallel configuration, based on 2500 VA | |
| Calculated secondary current at 48 V | Approximately 52.08 A in series configuration, based on 2500 VA | |
| Voltage regulation | 3% | |
| Insulation class | E | |
| Length | 192 mm | |
| Width | 161 mm | |
| Height | 185 mm | |
| Dimensions (L × W × H) | 192 × 161 × 185 mm | |
| Weight | 24 kg | |
| Enclosure reference | EPN 5 | |
| Product range | ETE Stock Control Transformers | |
| Catalogue reference | ETE Stock Control Transformer Range, March 2026 |
The ETE WV2500P7S7 is a 2500 VA single-phase wide-input-voltage control transformer designed to supply compatible industrial control circuits, electrical panels and automation equipment with nominal 24 V or 48 V AC power.
The transformer has a rated apparent power of 2500 VA (2.5 kVA). This is its total transformer capacity and does not double when the two secondary windings are connected in parallel.
The transformer features 0/380/400/420/440/460/480 V primary terminals, providing dedicated connections for nominal 380, 400, 420, 440, 460 and 480 V AC supplies.
The WV2500P7S7 incorporates two 0/24 V secondary windings. These can be connected in parallel to provide 24 V AC or in series to provide 48 V AC, using the correct winding connections.
Yes. The two 24 V secondary windings can be connected in parallel to provide a nominal 24 V AC output. Correct winding polarity is essential to avoid circulating currents and potential transformer damage.
Yes. Connecting the two 24 V secondary windings correctly in series provides a nominal 48 V AC output. The total rated apparent power remains 2500 VA.
Based on its 2500 VA rating, the calculated total secondary current is approximately 104.17 A at 24 V in parallel configuration or 52.08 A at 48 V in series configuration. These are calculated values rather than separately verified manufacturer current ratings, and actual loading must comply with the manufacturer's winding and installation requirements.
The transformer has a specified 3% voltage regulation. This indicates a relatively small secondary voltage change between no-load and rated-load conditions and should be considered when designing control circuits.
The transformer uses Class E insulation, providing a defined thermal insulation classification for operation within its specified electrical and environmental limits.
The transformer measures 192 × 161 × 185 mm (L × W × H) and weighs 24 kg. Its dimensions and weight should be considered when planning electrical panel space, mounting strength and installation access.
The specified enclosure reference is EPN 5. Enclosure selection should also consider ventilation, installation conditions, electrical clearances and the required degree of protection.
Yes. The transformer includes a dedicated 480 V primary terminal, allowing connection to a compatible nominal 480 V AC supply when correctly installed and protected.
Installation should account for the transformer's 24 kg weight, mechanical mounting requirements, primary and secondary circuit protection, conductor sizing, ventilation and electrical clearances. The correct primary tap and secondary winding configuration must be selected in accordance with the manufacturer's instructions.
ETE WV wide-input-voltage control transformers offer a flexible solution for industrial control power applications requiring multiple primary voltage selections and configurable secondary outputs. With six primary winding taps, dual 24 V secondary windings, 3% voltage regulation and a substantial 2500 VA capacity, the WV2500P7S7 is well suited to electrical panel builders, OEM machinery manufacturers and industrial automation engineers requiring dependable high-capacity 24 V or 48 V AC control power.