ETE WV200P7S8 is a 200 VA single-phase wide-input-voltage control transformer with 380-480 V AC primary taps, dual 0/110/120 V secondary windings configurable for 110/120 V parallel or 220/240 V series output, Class E insulation and 10% voltage regulation.
£45.45
The ETE WV200P7S8 is a 200 VA single-phase wide-input-voltage control transformer designed for industrial electrical installations requiring multiple primary voltage selections and flexible secondary output configurations. Part of the ETE WV wide-input-voltage transformer series, it features 0/380/400/420/440/460/480 V primary terminals and two independent secondary winding terminal groups marked 0/110/120 V + 0/110/120 V.
The WV200P7S8 supports 110 V AC or 120 V AC output with the secondary windings connected in parallel, or 220 V AC or 240 V AC output with the secondary windings connected in series. This versatility makes it suitable for industrial control panels, OEM machinery and automation equipment requiring different AC control voltages without changing transformer models.
Its multi-tapped primary winding accommodates nominal supply selections from 380 V to 480 V AC through the appropriate primary terminals. The dual secondary winding arrangement offers further flexibility, allowing engineers to select the output voltage and winding configuration required by the connected control equipment.
With Class E insulation, 10% voltage regulation, dimensions of 96 × 87 × 103 mm and a weight of 2.8 kg, the ETE WV200P7S8 provides a compact and adaptable industrial control power solution. Associated enclosure references are EPH 2 or EPN 1, supporting enclosure selection during electrical panel design.
The ETE WV200P7S8 is designed to accommodate a range of industrial primary supply voltages while providing selectable secondary control voltages. Its primary terminals cover nominal voltage selections of 380 V, 400 V, 420 V, 440 V, 460 V and 480 V AC, making it suitable for equipment operating on different industrial electrical supply arrangements. The correct primary terminal must be selected to match the actual supply and the manufacturer's connection instructions.
A key advantage is its two separate 0/110/120 V secondary windings. When connected correctly in parallel, the windings provide a nominal 110 V AC or 120 V AC output. Parallel operation allows the current contribution of both windings to be combined, subject to the transformer's overall 200 VA rating. The windings must be connected using matching voltage taps and the correct polarity; incorrect parallel connections can cause damaging circulating currents.
When connected correctly in series, the secondary windings provide a nominal 220 V AC or 240 V AC output. This configuration combines the voltages of the two secondary windings while retaining the transformer's overall apparent power rating. Correct winding polarity and terminal identification are essential, as an incorrect series connection may result in voltage cancellation or an unsuitable output.
At the rated 200 VA capacity, the calculated nominal output currents are approximately 1.82 A at 110 V, 1.67 A at 120 V, 0.91 A at 220 V and 0.83 A at 240 V. These are calculated values based on apparent power divided by nominal voltage, not separately verified manufacturer current ratings. The 200 VA rating applies to the transformer as a whole and must not be interpreted as 200 VA available independently from each secondary winding.
The specified 10% voltage regulation is relevant when assessing secondary voltage variation under changing load conditions. Actual output voltage depends on the primary supply, selected taps and connected load. Equipment with narrow operating voltage tolerances should therefore be checked for compatibility, especially where control relays, contactor coils or other inductive devices introduce changing loads.
With Class E insulation, a compact physical format and associated EPH 2 or EPN 1 enclosure references, the WV200P7S8 is suitable for integration into appropriately engineered industrial electrical assemblies. Installers should provide suitable mounting, primary and secondary circuit protection, conductor sizing, ventilation and electrical clearances. Series and parallel winding connections must follow the manufacturer's wiring instructions.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 200 VA | |
|---|---|---|
| Primary Voltage | 0/380/400/420/440/460/480V | |
| Secondary Voltage | 0/110/120V + 0/110/120V | |
| Phase | Single Phase | |
| Manufacturer | ETE | |
| Product series | WV Wide-Input-Voltage Control Transformers | |
| Manufacturer part number | WV200P7S8 | |
| Product type | Wide-input-voltage control transformer | |
| Transformer configuration | Single-phase | |
| Rated apparent power | 200 VA | |
| Rated capacity | 0.2 kVA | |
| Primary terminals | 0/380/400/420/440/460/480 V | |
| Nominal primary voltage options | 380 V, 400 V, 420 V, 440 V, 460 V or 480 V AC | |
| Number of secondary windings | 2 | |
| Secondary winding 1 terminals | 0/110/120 V | |
| Secondary winding 2 terminals | 0/110/120 V | |
| Parallel output option 1 | 110 V AC | |
| Parallel output option 2 | 120 V AC | |
| Series output option 1 | 220 V AC | |
| Series output option 2 | 240 V AC | |
| Secondary connection arrangement | 110/120 V parallel or 220/240 V series | |
| Calculated secondary current at 110 V parallel | Approximately 1.82 A at 200 VA | |
| Calculated secondary current at 120 V parallel | Approximately 1.67 A at 200 VA | |
| Calculated secondary current at 220 V series | Approximately 0.91 A at 200 VA | |
| Calculated secondary current at 240 V series | Approximately 0.83 A at 200 VA | |
| Insulation class | E | |
| Voltage regulation | 10% | |
| Length | 96 mm | |
| Width | 87 mm | |
| Height | 103 mm | |
| Dimensions (L × W × H) | 96 × 87 × 103 mm | |
| Weight | 2.8 kg | |
| Enclosure reference | EPH 2 or EPN 1 | |
| Product range | ETE Stock Control Transformers | |
| Catalogue reference | ETE Stock Control Transformer Range, March 2026 |
The ETE WV200P7S8 is a 200 VA single-phase wide-input-voltage control transformer used to supply compatible industrial control circuits, machinery and electrical panels with selectable 110 V, 120 V, 220 V or 240 V AC outputs.
The transformer has a rated apparent power of 200 VA (0.2 kVA). This is the overall transformer rating and applies to the combined load on its secondary windings.
The transformer features 0/380/400/420/440/460/480 V primary terminals, supporting nominal primary voltage selections of 380 V, 400 V, 420 V, 440 V, 460 V or 480 V AC using the appropriate terminal connection.
The transformer supports 110 V or 120 V AC with the secondary windings connected in parallel, and 220 V or 240 V AC with the secondary windings connected in series, using the manufacturer's specified wiring arrangements.
The WV200P7S8 has two secondary windings, each with 0/110/120 V terminals. The windings can be connected in the specified series or parallel configurations.
Yes. The two secondary windings can be connected in parallel to provide a nominal 110 V AC or 120 V AC output. Matching taps and correct winding polarity are essential, and the combined load must remain within the 200 VA rating.
Yes. The two secondary windings can be connected in series to provide a nominal 220 V AC or 240 V AC output. The correct series connection and winding polarity must be followed according to the manufacturer's instructions.
At the rated 200 VA capacity and a nominal 110 V AC parallel output, the calculated current is approximately 1.82 A. This is a calculated value rather than a separately verified manufacturer current rating.
At the rated 200 VA capacity and a nominal 120 V AC parallel output, the calculated current is approximately 1.67 A. This is a calculated value rather than a separately verified manufacturer current rating.
At the rated 200 VA capacity, the calculated current is approximately 0.91 A at 220 V AC or 0.83 A at 240 V AC with the secondary windings correctly connected in series. These are calculated values rather than separately verified manufacturer current ratings.
The WV200P7S8 has a specified 10% voltage regulation. Transformer voltage regulation describes the change in secondary voltage between defined load conditions, so connected equipment should have suitable operating voltage tolerance.
The transformer uses Class E insulation, providing a defined thermal insulation classification for its winding insulation system.
The transformer measures 96 × 87 × 103 mm (L × W × H) and weighs 2.8 kg. These details assist with electrical panel layout and mounting arrangements.
The associated enclosure references are EPH 2 or EPN 1. The appropriate enclosure and its suitability for the installation should be confirmed before selection.
Before installation, select the correct primary terminal for the supply voltage, confirm the required secondary voltage and follow the manufacturer's series or parallel wiring instructions. Check the combined connected load against the 200 VA rating and provide suitable circuit protection, conductor sizing, mounting, ventilation and electrical clearances.
ETE WV wide-input-voltage control transformers offer a flexible solution for industrial electrical applications requiring multiple primary voltage selections and configurable secondary outputs. With six nominal primary voltage options, dual 0/110/120 V secondary windings, series or parallel output connections, a 200 VA rating and Class E insulation, the WV200P7S8 provides electrical panel builders, machinery manufacturers and automation engineers with a practical option for industrial control power.