Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ETE MV500P2S1 is a 500 VA single-phase multi-voltage control transformer with 20/0/380/420 V primary terminals, selectable 55 V or 110 V AC secondary connections, Class E insulation, 8% voltage regulation and EPH 3 or EPN 2 enclosure compatibility.
£74.33
The ETE MV500P2S1 is a 500 VA single-phase multi-voltage control transformer designed for industrial electrical control panels, machinery and automation systems requiring selectable AC control voltages. Part of the ETE MV multi-voltage control transformer range, this model features 20/0/380/420 V primary terminals and 0/55/110 V secondary terminals, providing nominal 55 V AC or 110 V AC output connections for compatible industrial control equipment.
The MV500P2S1 combines a substantial 500 VA apparent power rating with a tapped secondary winding, making it a practical choice for control circuits with higher aggregate electrical loads. Its primary winding incorporates terminals marked 380 V and 420 V, together with a 20 V primary adjustment tap. The precise function and permitted connection combinations of this adjustment tap must be confirmed with ETE before installation.
The secondary winding features a 0/55/110 V terminal arrangement, allowing nominal 55 V AC or 110 V AC connections according to the intended control circuit. This flexibility is useful when specifying transformers for compatible contactors, electromagnetic relays, signalling devices, solenoids and other AC-operated industrial equipment.
Featuring Class E insulation and 8% voltage regulation, the ETE MV500P2S1 provides defined electrical characteristics for industrial transformer selection. Its dimensions of 120 × 120 × 120 mm and weight of 6.2 kg support integration into suitably designed electrical cabinets. The specified compatible enclosure references are ETE EPH 3 or EPN 2.
The ETE MV500P2S1 is designed for industrial electrical installations where the available AC supply must be transformed to a suitable control voltage. Its 20/0/380/420 V primary arrangement and 0/55/110 V secondary winding provide flexibility for control panel builders and machinery manufacturers working with compatible industrial electrical systems.
The primary winding includes terminals marked 380 V and 420 V, together with a 20 V adjustment tap. This adjustment terminal should not be treated as a standalone 20 V supply connection. The exact permitted terminal combinations and intended adjustment function must be verified using ETE's approved connection information before the transformer is energised.
The secondary winding incorporates an intermediate 55 V tap and a full 110 V connection. This provides selectable nominal secondary voltages for compatible industrial control equipment. Where the transformer is being considered for a centre-tapped 110 V application, the intended connection arrangement and any centre-point earthing requirements must be checked against the manufacturer's documentation.
The 500 VA apparent power rating corresponds to a calculated nominal full-load current of approximately 4.55 A at 110 V AC. This is derived by dividing the transformer rating by the nominal full secondary voltage. The permitted current through the intermediate 55 V winding section has not been specified separately and must be confirmed before loading that tap. The full 500 VA rating should not automatically be assumed to be available independently from the 55 V connection.
The specified 8% voltage regulation is an important consideration when selecting control transformers for circuits containing electromagnetic loads. Contactors, relays and solenoids can have different apparent power demands during energisation and normal operation. Electrical designers should consider the total steady-state load, simultaneous switching requirements and the acceptable voltage range of connected equipment.
With Class E insulation, dimensions of 120 × 120 × 120 mm and a weight of 6.2 kg, the MV500P2S1 can be incorporated into appropriately designed industrial control cabinets. Its specified EPH 3 or EPN 2 enclosure references provide compatible housing options where additional physical protection is required.
The MV500P2S1 provides AC voltage transformation rather than regulated DC output. Equipment requiring DC control voltage will need suitable additional conversion components. Installation should account for correct primary tap selection, suitable circuit protection, conductor sizing, mechanical mounting, ventilation and protective earthing where applicable.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 500 VA | |
|---|---|---|
| Primary Voltage | 20/0/380/420V | |
| Secondary Voltage | 0/55/110V | |
| Phase | Single Phase | |
| Brand | ETE | |
| Manufacturer part number | MV500P2S1 | |
| Product family | MV Multi-Voltage Control Transformers | |
| Product category | Industrial Control Transformers | |
| Transformer configuration | Tapped primary and secondary windings | |
| Number of phases | Single-phase | |
| Rated apparent power | 500 VA | |
| Primary terminal arrangement | 20/0/380/420 V | |
| Primary voltage terminal markings | 380 V and 420 V | |
| Primary adjustment tap | 20 V | |
| Primary connection note | Confirm the correct 20 V adjustment tap connections with ETE before energising. | |
| Secondary terminal arrangement | 0/55/110 V | |
| Nominal secondary output options | 55 V AC or 110 V AC | |
| Calculated nominal full-load secondary current at 110 V | Approximately 4.55 A | |
| 55 V secondary tap current rating | Confirm with ETE before applying the full transformer apparent power to the intermediate tap. | |
| Insulation class | E | |
| Voltage regulation | 8% | |
| Length | 120 mm | |
| Width | 120 mm | |
| Height | 120 mm | |
| Overall dimensions (L × W × H) | 120 × 120 × 120 mm | |
| Weight | 6.2 kg | |
| Compatible enclosure references | EPH 3 or EPN 2 | |
| Typical installation | Industrial electrical control panels and machinery cabinets | |
| Catalogue reference | ETE Stock Control Transformer Range, March 2026 |
The ETE MV500P2S1 is a 500 VA single-phase multi-voltage control transformer designed to provide selectable 55 V AC or 110 V AC secondary connections for compatible industrial control equipment.
The primary terminal markings are 20/0/380/420 V. The correct connection arrangement, particularly the function of the 20 V adjustment tap, must be confirmed with ETE.
The 20 V primary adjustment tap provides an additional winding connection. Its precise relationship to the 0, 380 V and 420 V terminals must be verified using ETE's approved connection information before installation.
The transformer has primary terminals marked 380 V and 420 V, together with a 20 V adjustment tap. The correct connection arrangement for a nominal 400 V AC supply must be confirmed with ETE rather than inferred from the terminal markings alone.
The secondary terminals are marked 0/55/110 V, providing nominal 55 V AC or 110 V AC output connections when wired correctly.
The 0/55/110 V secondary arrangement includes an intermediate 55 V tap on the 110 V winding. The suitability of this arrangement for a particular centre-tapped application, including any centre-point earthing requirements, must be confirmed from ETE's connection information.
The MV500P2S1 has a rated apparent power of 500 VA. The connected load must remain within the applicable transformer and winding ratings.
At 500 VA and 110 V AC, the calculated nominal full-load secondary current is approximately 4.55 A.
Not without confirmation. The transformer has a total rated apparent power of 500 VA, but the allowable current through the individual 55 V winding section has not been specified separately. The applicable tap loading limit should be confirmed with ETE.
The transformer provides AC output. It does not incorporate a rectifier or regulated DC power supply.
The transformer has Class E insulation and a specified 8% voltage regulation.
The transformer measures 120 mm long × 120 mm wide × 120 mm high and weighs 6.2 kg.
The specified compatible enclosure references are ETE EPH 3 or EPN 2. Final enclosure selection should account for the installation environment, mounting requirements and ventilation.
Yes. Its 500 VA rating, selectable secondary voltage connections and compact construction make it suitable for appropriately designed industrial control panels using compatible AC control equipment.
The specified 8% voltage regulation indicates that secondary voltage changes with loading. Connected control equipment should have suitable operating voltage tolerances, particularly where electromagnetic devices produce high energisation demands.
The correct wiring information should be obtained from ETE or its approved technical documentation. This is especially important when using the 20 V primary adjustment tap or configuring the secondary winding for a particular control circuit.
The ETE MV500P2S1 combines a 500 VA rating with flexible primary connections and selectable 55 V or 110 V AC secondary outputs. Its Class E insulation, 8% voltage regulation and compact construction make it a practical component for industrial electrical panel builders, machinery manufacturers and maintenance engineers requiring adaptable AC control power.