Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ETE MV4000P2S2 is a 4000 VA single-phase multi-voltage control transformer with 20/0/380/420 V primary terminals, 10/0/220/240 V tapped secondary terminals, Class F insulation, 3% voltage regulation and an EPN 6 enclosure reference.
£367.58
The ETE MV4000P2S2 is a high-capacity 4000 VA (4 kVA) single-phase multi-voltage control transformer designed to provide reliable AC power for industrial control circuits, electrical panels, switchgear and automation equipment. As part of the ETE MV multi-voltage control transformer series, it offers flexible primary voltage connections and a tapped secondary winding for industrial applications requiring dependable voltage conversion and electrical isolation.
The MV4000P2S2 features a 20/0/380/420 V primary terminal arrangement and a 10/0/220/240 V secondary terminal arrangement. The transformer supports compatible 380 V and 420 V AC primary supply configurations, with secondary voltage options of 220 V and 240 V AC. Its tapped secondary arrangement includes a 10 V adjustment tap, for which the correct terminal connections must be confirmed with ETE.
With a rated apparent power of 4000 VA, Class F insulation and 3% voltage regulation, the MV4000P2S2 is suitable for demanding industrial electrical installations. Its dimensions of 245 × 190 × 230 mm and weight of 36 kg make it suitable for installation in appropriately sized industrial control cabinets and electrical enclosures, with EPN 6 specified as the enclosure reference.
Industrial control transformers convert an AC supply into a voltage suitable for electrical control equipment while providing electrical isolation between primary and secondary circuits. The ETE MV4000P2S2 is designed for compatible 380 V and 420 V AC primary supplies, with a tapped secondary arrangement supporting 220 V and 240 V AC output requirements.
The transformer incorporates a 10/0/220/240 V secondary terminal arrangement. Its tapped winding provides voltage selection flexibility for industrial control circuits and machinery requiring a specific AC operating voltage. The 10 V adjustment tap must be connected according to the manufacturer's specified terminal arrangement, and the correct connections should be confirmed with ETE before installation.
Based on the 4000 VA rating, the theoretical full-load secondary current is approximately 16.7 A at 240 V AC or 18.2 A at 220 V AC, assuming the full rated apparent power is available at the selected output. These are calculated values rather than independently confirmed terminal current ratings; actual permissible loading must follow ETE's specifications.
The transformer's 3% voltage regulation helps limit secondary voltage variation between operating load conditions, while its Class F insulation supports dependable thermal performance. Correct terminal connections, appropriate overcurrent protection, suitable conductor sizing, secure mechanical mounting and adequate ventilation are essential for safe operation, particularly given the transformer's 36 kg weight.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 4000 VA | |
|---|---|---|
| Primary Voltage | 20/0/380/420V | |
| Secondary Voltage | 10/0/220/240V | |
| Phase | Single Phase | |
| Manufacturer | ETE | |
| Series | MV Multi-Voltage Control Transformers | |
| Model | MV4000P2S2 | |
| Product type | Multi-voltage control transformer | |
| Rated apparent power | 4000 VA (4 kVA) | |
| Number of phases | Single-phase | |
| Primary terminal arrangement | 20/0/380/420 V | |
| Nominal primary voltage options | 380/420 V AC | |
| Secondary terminal arrangement | 10/0/220/240 V | |
| Secondary voltage options | 220/240 V AC | |
| Secondary connection type | Tapped output per manufacturer datasheet | |
| Adjustment tap | 10 V; confirm terminal connections with ETE | |
| Voltage regulation | 3% | |
| Insulation class | F | |
| Length | 245 mm | |
| Width | 190 mm | |
| Height | 230 mm | |
| Dimensions (L × W × H) | 245 × 190 × 230 mm | |
| Weight | 36 kg | |
| Enclosure reference | EPN 6 | |
| Product range reference | ETE Stock Control Transformer Range, March 2026 |
The ETE MV4000P2S2 is a single-phase industrial control transformer designed to convert compatible 380 V or 420 V AC supplies into 220 V or 240 V AC for electrical control circuits, industrial machinery, switchgear and automation equipment.
The transformer has a rated apparent power of 4000 VA (4 kVA), making it suitable for industrial applications requiring a higher-capacity AC control power supply.
The transformer features a 20/0/380/420 V primary terminal arrangement for compatible 380 V and 420 V AC supplies. The correct primary terminal selection must follow ETE's connection instructions.
The transformer has a 10/0/220/240 V secondary terminal arrangement supporting 220 V and 240 V AC output configurations. The exact connections must follow the manufacturer's tapped winding diagram.
The 10 V adjustment tap forms part of the transformer's tapped voltage arrangement. Its correct terminal connections and permitted use must be confirmed with ETE to ensure the required secondary voltage is obtained safely.
Based on the 4000 VA rating, the theoretical full-load secondary current is approximately 16.7 A at 240 V AC or 18.2 A at 220 V AC, assuming the full transformer rating is available at the selected voltage. Actual permissible loading must comply with ETE's specifications.
The transformer measures 245 mm long × 190 mm wide × 230 mm high and weighs 36 kg. Suitable mounting arrangements should be provided to support its weight securely.
The MV4000P2S2 features Class F insulation and 3% voltage regulation, supporting dependable electrical and thermal performance in industrial control applications.
The specified enclosure reference is EPN 6, identifying the corresponding ETE enclosure size for installations requiring additional protective housing.
ETE MV multi-voltage control transformers provide dependable voltage conversion solutions for industrial electrical installations. The MV4000P2S2 combines a 4000 VA rating, flexible 380/420 V primary connections, 220/240 V tapped secondary options, Class F insulation and 3% voltage regulation, making it a practical choice for industrial control panel builders, machinery manufacturers and electrical maintenance engineers.