Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ETE MV200P2S1 is a 200 VA single-phase multi-voltage control transformer with 20/0/380/420 V primary terminals, selectable 55 V or 110 V AC secondary connections, Class E insulation, 10% voltage regulation and EPH 2 or EPN 1 enclosure compatibility.
£36.15
The ETE MV200P2S1 is a versatile 200 VA single-phase multi-voltage control transformer designed for industrial electrical control panels, machinery and automation systems requiring reliable AC voltage transformation. Part of the ETE MV multi-voltage control transformer range, this model features 20/0/380/420 V primary terminals and 0/55/110 V secondary terminals, providing selectable 55 V AC or 110 V AC output connections for compatible industrial control equipment.
The MV200P2S1 is particularly useful for installations involving industrial AC supplies where different control voltage requirements must be accommodated. Its primary winding incorporates terminals marked 380 V and 420 V, together with a 20 V primary adjustment tap. This additional connection provides voltage adjustment flexibility, although the exact permitted terminal combinations must be confirmed with ETE before installation.
On the secondary side, the 0/55/110 V tapped winding allows the transformer to supply nominal 55 V AC or 110 V AC, depending on the selected connections. This arrangement makes the MV200P2S1 suitable for appropriately rated contactor coils, electromagnetic relays, signalling devices, solenoids and other industrial AC control components.
With a rated apparent power of 200 VA, Class E insulation and 10% voltage regulation, the MV200P2S1 offers a practical combination of output capacity and connection flexibility. Measuring 96 × 87 × 103 mm and weighing 2.8 kg, it is suitable for integration into industrial electrical cabinets. The specified compatible enclosure references are ETE EPH 2 or EPN 1.
The ETE MV200P2S1 provides a practical solution for industrial electrical installations requiring a choice of 55 V AC or 110 V AC control voltage. Its 20/0/380/420 V primary terminal arrangement and 0/55/110 V secondary winding make it suitable for control panel designs where the available supply and required control voltage must be considered together.
The primary winding includes connections marked 380 V and 420 V, together with a 20 V adjustment tap. This additional connection must not be interpreted as a standalone 20 V supply input. The exact function of the adjustment tap, permitted terminal combinations and appropriate connection for the available supply should be confirmed against ETE's approved wiring information before the transformer is energised.
The secondary winding provides nominal 55 V AC and 110 V AC connection options. The intermediate 55 V tap can be used for compatible lower-voltage control equipment, while the full 110 V connection provides the higher nominal secondary voltage. Where an application requires a centre-tapped 110 V supply, the appropriate terminal and earthing arrangement must be verified rather than assumed solely from the terminal markings.
The 200 VA apparent power rating corresponds to a calculated nominal full-load secondary current of approximately 1.82 A at 110 V AC. Dividing the same apparent power by 55 V gives a theoretical current equivalent of approximately 3.64 A. However, this calculation does not independently establish the permissible current through the individual 55 V winding section. The manufacturer's tap-specific current limits must be confirmed before applying the full transformer rating to an intermediate secondary connection.
The specified 10% voltage regulation is important when selecting industrial control components that must operate reliably under varying load conditions. Secondary voltage may change as connected equipment switches on or off, particularly where electromagnetic devices such as contactors, relays and solenoids have a higher initial energisation demand than their normal operating consumption. Designers should consider both steady-state apparent power and simultaneous switching requirements.
With Class E insulation, compact dimensions of 96 × 87 × 103 mm and a weight of 2.8 kg, the MV200P2S1 is suited to appropriately designed industrial electrical cabinets. The specified EPH 2 or EPN 1 enclosure references provide compatible housing options where additional physical protection is required.
The MV200P2S1 provides AC voltage transformation and does not incorporate a rectifier or regulated DC output stage. Equipment requiring DC control voltage will need suitable additional power conversion components. Correct primary tap selection, secondary connections, circuit protection, conductor sizing, protective earthing where applicable and adequate ventilation should be considered during installation.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 200 VA | |
|---|---|---|
| Primary Voltage | 20/0/380/420V | |
| Secondary Voltage | 0/55/110V | |
| Phase | Single Phase | |
| Brand | ETE | |
| Manufacturer part number | MV200P2S1 | |
| Product family | MV Multi-Voltage Control Transformers | |
| Product category | Industrial Control Transformers | |
| Transformer configuration | Multi-tapped primary and secondary | |
| Number of phases | Single-phase | |
| Rated apparent power | 200 VA | |
| Primary terminal arrangement | 20/0/380/420 V | |
| Primary voltage terminal markings | 380 V and 420 V | |
| Primary adjustment tap | 20 V | |
| Primary connection note | Confirm the correct 20 V adjustment tap connections with ETE before energising. | |
| Secondary terminal arrangement | 0/55/110 V | |
| Nominal secondary output options | 55 V AC or 110 V AC | |
| Calculated nominal full-load secondary current at 110 V | Approximately 1.82 A | |
| Theoretical current equivalent at 55 V | Approximately 3.64 A, calculated from 200 VA ÷ 55 V; permissible individual tap loading requires confirmation. | |
| Calculated apparent-power current equivalent at 380 V | Approximately 0.53 A | |
| Calculated apparent-power current equivalent at 420 V | Approximately 0.48 A | |
| Insulation class | E | |
| Voltage regulation | 10% | |
| Length | 96 mm | |
| Width | 87 mm | |
| Height | 103 mm | |
| Overall dimensions (L × W × H) | 96 × 87 × 103 mm | |
| Weight | 2.8 kg | |
| Compatible enclosure references | EPH 2 or EPN 1 | |
| Typical installation | Industrial electrical control panels and machinery cabinets | |
| Catalogue reference | ETE Stock Control Transformer Range, March 2026 |
The ETE MV200P2S1 is a 200 VA single-phase multi-voltage control transformer designed to provide selectable 55 V AC or 110 V AC secondary connections for compatible industrial control equipment.
The primary terminal markings are 20/0/380/420 V. The correct connection arrangement, particularly the function of the 20 V adjustment tap, must be confirmed with ETE.
The 20 V primary adjustment tap provides an additional winding connection. Its precise relationship to the 0, 380 V and 420 V terminals must be verified using ETE's approved connection information before installation.
The transformer has primary terminals marked 380 V and 420 V, together with a 20 V adjustment tap. The correct connection arrangement for a nominal 400 V AC supply must be confirmed with ETE rather than inferred from the terminal markings alone.
The secondary terminals are marked 0/55/110 V, providing nominal 55 V AC or 110 V AC output connections when wired correctly.
The 0/55/110 V secondary arrangement includes an intermediate 55 V tap on the 110 V winding. The suitability of this arrangement for a particular centre-tapped application, including any centre-point earthing requirements, must be confirmed from ETE's connection information.
The MV200P2S1 has a rated apparent power of 200 VA. The connected load must remain within the applicable transformer and winding ratings.
At 200 VA and 110 V AC, the calculated nominal full-load secondary current is approximately 1.82 A.
Not without confirmation. Although 200 VA divided by 55 V gives a theoretical current equivalent of approximately 3.64 A, the allowable current through the individual 55 V winding section must be confirmed with ETE.
Dividing the rated apparent power by the marked primary voltages gives approximately 0.53 A at 380 V and 0.48 A at 420 V. These are mathematical apparent-power equivalents rather than independently verified operating input currents.
The transformer provides AC output. It does not incorporate a rectifier or regulated DC power supply.
The transformer has Class E insulation and a specified 10% voltage regulation.
The transformer measures 96 mm long × 87 mm wide × 103 mm high and weighs 2.8 kg.
The specified compatible enclosure references are ETE EPH 2 or EPN 1. Final enclosure selection should account for the installation environment, mounting requirements and ventilation.
Yes. Its 200 VA rating, selectable secondary voltage connections and compact construction make it suitable for appropriately designed industrial control panels using compatible AC control equipment.
The specified 10% voltage regulation indicates that secondary voltage changes with loading. Connected control equipment should have suitable operating voltage tolerances, particularly where electromagnetic devices produce high energisation demands.
The correct wiring information should be obtained from ETE or its approved technical documentation. This is especially important when using the 20 V primary adjustment tap or configuring the secondary winding for a particular control circuit.
The ETE MV200P2S1 combines a 200 VA rating with flexible primary connections and selectable 55 V or 110 V AC secondary outputs. Its Class E insulation, 10% voltage regulation and compact construction make it a practical component for electrical panel builders, machinery manufacturers and maintenance engineers requiring adaptable industrial AC control power.
We use cookies