ETE DV500P6S4 is a 500 VA single-phase dual-input-voltage control transformer with selectable 240 V or 415 V AC primary connections, a 110 V AC secondary output, Class E insulation and 8% voltage regulation for industrial control panels and machinery.
£72.45
The ETE DV500P6S4 is a 500 VA single-phase dual-input-voltage control transformer designed to provide a nominal 110 V AC secondary output from either a 240 V AC or 415 V AC primary supply. Manufactured by Eastern Transformers and Equipment (ETE), this transformer belongs to the DV Dual Voltage Series, offering flexible voltage selection for industrial control panels, electrical machinery, automation systems and OEM equipment.
Featuring 0/240/415 V primary terminals and 0/110 V secondary terminals, the DV500P6S4 allows installers to select the appropriate primary voltage connection while maintaining a dedicated 110 V AC control supply. Its 500 VA rating provides a calculated secondary current capacity of approximately 4.55 A at the nominal output voltage, making it suitable for appropriately rated contactors, relays, motor control circuits and industrial switching equipment.
The transformer incorporates Class E insulation, 8% voltage regulation, IP20 touch-proof terminals, Class H varnish impregnation and a protective core earth connection. With dimensions of 135 × 105 × 125 mm and a weight of 6.2 kg, it is designed for installation within industrial electrical assemblies. The specified enclosure reference is EPN 3.
The ETE DV500P6S4 dual voltage transformer offers the flexibility of two selectable primary supply voltages. Its 0/240/415 V primary terminals allow the transformer to be connected to a 240 V AC supply or a 415 V AC supply using the designated terminal connections. This makes the unit particularly useful for panel builders and machinery manufacturers supplying equipment to installations with different electrical distribution arrangements.
The transformer provides a dedicated nominal 110 V AC secondary output through its 0/110 V secondary terminals. With a rated apparent power of 500 VA, the calculated secondary current at nominal voltage is approximately 4.55 A. Engineers should consider the combined steady-state load, switching inrush and operating characteristics of connected devices when determining transformer suitability.
Its specified 8% voltage regulation is an important consideration for applications involving varying control circuit loads. The actual secondary voltage can change with loading, so voltage-sensitive equipment should be selected and assessed accordingly. The DV500P6S4 is therefore suitable for appropriately designed industrial circuits requiring a 240/415 V to 110 V AC control transformer.
The DV500P6S4 combines a 500 VA rating with an overall size of 135 mm in length, 105 mm in width and 125 mm in height. Its 6.2 kg weight should be considered when selecting the mounting surface, fixings and supporting panel structure.
The transformer features Class E insulation, IP20 touch-proof terminals, Class H varnish impregnation and a protective core earth connection. The ETE DV series is designed for continuous-rated control circuit operation, with a specified ambient temperature range of −10 to +35 °C and construction designed to EN 61558-1.
The specified enclosure reference for this model is EPN 3. When incorporating the transformer into an electrical installation, engineers should provide suitable ventilation, electrical protection, cable management and protective earthing in accordance with the complete system design. Primary voltage selection must match the actual supply, and the connected secondary load must remain within the transformer's rating.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 500 VA | |
|---|---|---|
| Primary Voltage | 0/240/415V | |
| Secondary Voltage | 0/110V | |
| Phase | Single Phase | |
| Manufacturer | ETE (Eastern Transformers and Equipment) | |
| Manufacturer part number | DV500P6S4 | |
| Product series | DV Dual Input Voltage Control Transformers | |
| Product type | Dual-input-voltage control circuit transformer | |
| Number of phases | Single-phase | |
| Rated apparent power | 500 VA | |
| Primary terminals | 0/240/415 V | |
| Selectable primary supply | 240 V AC or 415 V AC | |
| Secondary terminals | 0/110 V | |
| Secondary output connection | 110 V AC | |
| Calculated rated secondary current | Approximately 4.55 A at 110 V and 500 VA | |
| Operating frequency | 50/60 Hz | |
| Insulation class | E | |
| Voltage regulation | 8% | |
| Terminal protection | IP20 touch-proof terminals | |
| Winding impregnation | Class H varnish | |
| Core earth connection | Provided | |
| Ambient temperature range | −10 to +35 °C | |
| Design standard | EN 61558-1 | |
| Duty rating | Continuous | |
| Length | 135 mm | |
| Width | 105 mm | |
| Height | 125 mm | |
| Dimensions (L × W × H) | 135 × 105 × 125 mm | |
| Weight | 6.2 kg | |
| Enclosure reference | EPN 3 | |
| Manufacturer catalogue reference | ETE Stock Control Transformer Range, March 2026 |
The ETE DV500P6S4 is a 500 VA single-phase dual-input-voltage control transformer used to provide a nominal 110 V AC secondary supply from either a 240 V AC or 415 V AC primary input. Typical applications include industrial control panels, contactor circuits, relays and electrical machinery.
Yes. Its 0/240/415 V primary terminal arrangement permits connection to either a 240 V AC or 415 V AC supply. The correct primary terminal must be selected for the available supply voltage; the two voltages are alternative connections rather than simultaneous inputs.
The transformer has 0/110 V secondary terminals and provides a nominal 110 V AC output when connected to the correctly selected primary supply.
At its rated capacity of 500 VA and nominal secondary voltage of 110 V AC, the calculated rated secondary current is approximately 4.55 A. The load and any switching inrush requirements should be considered when selecting the transformer.
The transformer measures 135 × 105 × 125 mm (length × width × height) and weighs 6.2 kg.
The DV500P6S4 has Class E insulation and a specified 8% voltage regulation. The ETE DV series also features Class H varnish impregnation, IP20 touch-proof terminals and a protective core earth connection.
The manufacturer's specified enclosure reference is EPN 3. The final enclosure installation should provide appropriate mechanical support, ventilation and electrical protection for the application.
The ETE DV500P6S4 combines flexible 240 V or 415 V primary voltage selection with a dedicated 110 V AC secondary output and a 500 VA rating. With Class E insulation, 8% voltage regulation and an EPN 3 enclosure reference, it is a practical control transformer choice for industrial panel builders, OEM machinery manufacturers and electrical maintenance professionals.