ETE DV400P6S4 is a 400 VA single-phase dual-input-voltage control transformer with selectable 240 V or 415 V AC primary connections, a 110 V AC secondary output, Class E insulation, 8% voltage regulation and EPH 3 or EPN 2 enclosure compatibility for industrial control applications.
£65.03
The ETE DV400P6S4 is a robust 400 VA single-phase industrial control transformer designed to provide a nominal 110 V AC secondary output from either a 240 V AC or 415 V AC primary supply. Manufactured by Eastern Transformers & Equipment (ETE), this transformer belongs to the established DV dual-input-voltage control transformer series, developed for industrial electrical control panels, machinery and automation systems requiring flexible input voltage selection.
The DV400P6S4 features a tapped primary winding with 0/240/415 V terminals, allowing installers to select the appropriate connection for the available electrical supply. Its 0/110 V secondary terminals provide a dedicated 110 V AC output for compatible contactor coils, electromagnetic relays, solenoids, signalling devices and industrial control equipment. The dual-input arrangement is particularly useful for OEM machinery manufacturers and panel builders producing equipment for different industrial supply configurations.
With a rated apparent power of 400 VA, Class E insulation and 8% voltage regulation, the DV400P6S4 combines dependable voltage transformation with practical industrial construction. Measuring 120 × 108 × 120 mm and weighing 5.5 kg, it is suitable for integration into industrial electrical cabinets. The specified compatible enclosure references are ETE EPH 3 or EPN 2.
The ETE DV400P6S4 provides a practical solution for industrial installations requiring a dedicated 110 V AC control supply where the available primary voltage may be either 240 V AC or 415 V AC. Its dual-input-voltage arrangement enables the correct primary connection to be selected during installation, allowing one transformer model to accommodate different supply configurations without changing the nominal secondary voltage.
For a 240 V AC input, the transformer uses its designated 0/240 V primary terminals. For a 415 V AC input, the designated 0/415 V primary terminals are used. Both configurations provide a nominal 110 V AC secondary output. These primary connections are alternative voltage selections and must not be energised simultaneously from independent electrical supplies.
The 400 VA continuous apparent power rating corresponds to a calculated nominal full-load secondary current of approximately 3.64 A at 110 V AC. This capacity makes the transformer suitable for appropriately sized industrial control circuits containing compatible contactor coils, electromagnetic relays, solenoids and signalling equipment. The combined steady-state apparent power of connected devices should remain within the transformer rating, with additional consideration given to simultaneous energisation requirements.
For electromagnetic control applications, the published selection figures for the 400 VA transformer size are 900 VA at 95% secondary voltage and 1500 VA at 90% secondary voltage. These figures help electrical designers assess short-duration contactor energisation requirements while considering acceptable secondary voltage conditions. They do not increase the transformer's continuous output rating beyond 400 VA.
The specified 8% voltage regulation describes the variation in secondary voltage between no-load and rated-load conditions. This characteristic is important when designing control circuits containing voltage-sensitive equipment or loads that change during machinery operation. Correct consideration of voltage regulation, control coil operating tolerances and inrush requirements helps support dependable switching and control performance.
The DV400P6S4 incorporates Class E insulation, Class H varnish impregnation, IP20 touch-proof terminals and a protective core earth connection. Its continuous-rated construction is designed to EN 61558-1, with a specified ambient operating temperature range of −10 to +35 °C.
For installation within industrial control cabinets, the transformer measures 120 × 108 × 120 mm and has fixing centres of 90 × 90 mm with 5 mm fixing holes. The compatible EPH 3 or EPN 2 enclosure references provide options for installations requiring additional physical protection. Suitable primary and secondary circuit protection, conductor sizing, protective earthing and ventilation should be incorporated into the electrical design.
Although the transformer may be connected across two suitable phases of a three-phase electrical system where the phase-to-phase voltage is 415 V AC, the DV400P6S4 remains a single-phase transformer. Its 0/110 V secondary winding provides a nominal 110 V AC output and should not be confused with a centre-tapped 55/0/55 V arrangement used in certain construction-site applications.
Tick the specs you need, then view products that match.
| Rated Power (VA) | 400 VA | |
|---|---|---|
| Primary Voltage | 0/240/415V | |
| Secondary Voltage | 0/110V | |
| Phase | Single Phase | |
| Manufacturer | Eastern Transformers & Equipment (ETE) | |
| Brand | ETE | |
| Series | DV Dual-Input-Voltage Control Transformers | |
| Manufacturer part number | DV400P6S4 | |
| Product type | Industrial control circuit transformer | |
| Transformer configuration | Dual-input-voltage primary with single-voltage secondary | |
| Number of phases | Single-phase | |
| Rated apparent power | 400 VA | |
| Primary voltage options | 240 V AC or 415 V AC | |
| Primary terminals | 0/240/415 V | |
| Secondary voltage | 110 V AC | |
| Secondary terminals | 0/110 V | |
| Output connection | 110 V AC | |
| Calculated nominal full-load secondary current | Approximately 3.64 A | |
| Calculated nominal primary current at 240 V | Approximately 1.67 A, based on rated apparent power | |
| Calculated nominal primary current at 415 V | Approximately 0.96 A, based on rated apparent power | |
| Rated frequency | 50/60 Hz | |
| Duty rating | Continuous | |
| Insulation class | Class E | |
| Varnish impregnation | Class H | |
| Voltage regulation | 8% | |
| Terminal protection | IP20 touch-proof terminals | |
| Earthing provision | Core earth connection | |
| Ambient operating temperature | −10 to +35 °C | |
| Design standard | EN 61558-1 | |
| Contactor inrush selection figure at 95% secondary voltage | 900 VA | |
| Contactor inrush selection figure at 90% secondary voltage | 1500 VA | |
| Fixing centre length | 90 mm | |
| Fixing centre width | 90 mm | |
| Fixing hole diameter | 5 mm | |
| Length | 120 mm | |
| Width | 108 mm | |
| Height | 120 mm | |
| Dimensions (L × W × H) | 120 × 108 × 120 mm | |
| Weight | 5.5 kg | |
| Compatible enclosure references | EPH 3 or EPN 2 | |
| Typical installation | Industrial electrical control panels and machinery cabinets | |
| Country of manufacture | United Kingdom | |
| Product range reference | ETE Stock Control Transformer Range, March 2026 |
The ETE DV400P6S4 is a 400 VA single-phase industrial control transformer designed to provide a nominal 110 V AC output from either a 240 V AC or 415 V AC primary supply for machinery, automation equipment and electrical control panels.
Dual-input-voltage means the transformer has primary connections for two alternative supply voltages: 240 V AC and 415 V AC. The appropriate primary terminals are selected to match the available supply, while the secondary output remains nominally 110 V AC.
The transformer has 0/240/415 V primary terminals and 0/110 V secondary terminals. The installer must use the correct primary voltage tap for the available electrical supply.
The DV400P6S4 has a rated apparent power of 400 VA and is designed for continuous control circuit operation within its specified rating.
At its rated output of 400 VA and 110 V AC, the calculated nominal full-load secondary current is approximately 3.64 A.
Using the rated apparent power divided by the selected primary voltage, the nominal current equivalents are approximately 1.67 A at 240 V AC and 0.96 A at 415 V AC. Actual input current also depends on transformer losses and operating conditions.
Yes. Where a suitable 415 V AC phase-to-phase supply is available, the transformer can be connected using its designated 0/415 V primary terminals. The DV400P6S4 itself remains a single-phase transformer and must be installed with appropriate electrical protection.
The transformer provides a nominal 110 V AC secondary output. It does not incorporate a rectifier or regulated DC power supply, so equipment requiring 110 V DC needs suitable additional power conversion equipment.
The DV400P6S4 is specified with a 0/110 V secondary winding, rather than a 55/0/55 V centre-tapped secondary. It should not be assumed to provide a centre-tapped output for construction-site equipment.
The transformer has a Class E insulation system and a specified 8% voltage regulation. Its construction also incorporates Class H varnish impregnation.
The transformer measures 120 mm long × 108 mm wide × 120 mm high and weighs 5.5 kg.
The 400 VA transformer size has fixing centres of 90 × 90 mm with a specified fixing hole diameter of 5 mm.
The specified compatible enclosure references are ETE EPH 3 or EPN 2. Final enclosure selection should account for installation conditions, ventilation and the required environmental protection.
The ETE SV and DV stock transformer ranges provide a DIN rail mounting option for smaller models up to 150 VA. The DV400P6S4 is a 400 VA model, so DIN rail compatibility should not be assumed. Its specified fixing centres should be used when planning the mounting arrangement.
Yes. The DV400P6S4 incorporates IP20 touch-proof terminals and a core earth connection for protective earthing within an appropriately designed electrical installation.
The published contactor inrush selection figures are 900 VA at 95% secondary voltage and 1500 VA at 90% secondary voltage. These values assist transformer selection for control circuits containing contactors and other electromagnetic loads and do not represent continuous output ratings.
The DV400P6S4 is designed for 50/60 Hz operation with an ambient temperature range of −10 to +35 °C.
No. The 240 V and 415 V primary connections are alternative voltage selections. The installer must use the correct terminals for the available supply and must not connect independent supplies to both primary voltage taps simultaneously.
ETE DV dual-input-voltage control transformers provide flexible and dependable voltage transformation for industrial electrical installations. With its 400 VA rating, selectable 240/415 V primary connections, 110 V AC output, Class E insulation and 8% voltage regulation, the DV400P6S4 is a practical choice for electrical panel builders, machinery manufacturers and maintenance engineers requiring reliable control power across different supply configurations.