The WAGO 2006-1611/1000-541 is a high-quality 2-conductor fuse terminal block with integrated LED blown fuse indication, designed for reliable fused circuit protection and convenient fault identification in industrial electrical installations. As part of the established WAGO TOPJOB® S 2006 series, this DIN rail-mounted terminal block combines secure conductor termination, a pivoting fuse holder and visual fuse-status monitoring in one compact component.
Featuring WAGO's proven Push-in CAGE CLAMP® connection technology, the 2006-1611/1000-541 provides secure spring-pressure conductor connections while simplifying installation and maintenance. Its integrated pivoting fuse holder accommodates a standard 5 × 20 mm miniature cartridge fuse, allowing convenient fuse access and replacement without removing the terminal block from the DIN rail.
A key feature of this model is its 12–30 V LED blown fuse indication, which provides a visual signal when the installed fuse has operated under suitable circuit conditions. With a 6 mm² nominal conductor cross-section, 10 A IEC rated current and compact 7.5 mm terminal width, the WAGO 2006-1611/1000-541 is particularly suited to low-voltage DC control circuits, industrial automation equipment and electrical control cabinets requiring accessible fuse protection and fault indication.
Fuse terminal blocks with integrated LED indication combine electrical circuit protection, conductor connection and visual fault identification within a single DIN rail-mounted component. When a correctly selected fuse is installed, the fuse provides overcurrent protection, while the LED indication circuit helps maintenance engineers identify an operated fuse without individually removing and testing every fuse in the assembly.
The WAGO 2006-1611/1000-541 features an integrated 12–30 V blown fuse indication circuit. When the fuse opens and the necessary voltage conditions are present, the LED illuminates to indicate the fault. This visual feedback can help reduce troubleshooting time in industrial control panels, particularly where multiple fused circuits are installed alongside one another.
The integrated LED indication circuit has a specified leakage current of approximately 2.2 mA at 24 V when the fuse has blown. This characteristic should be considered when designing circuits connected to sensitive electronic equipment, PLC inputs or other devices that may respond to small leakage currents.
The terminal block incorporates a pivoting fuse carrier for standard 5 × 20 mm miniature cartridge fuses. The holder can be opened to access the fuse for inspection or replacement, while its compact construction allows multiple fused circuits to be arranged efficiently on a standard DIN rail. Appropriate electrical isolation and safe working procedures must be followed before fuse replacement.
WAGO's Push-in CAGE CLAMP® connection technology provides reliable spring-pressure electrical contact. Suitable solid conductors and correctly ferruled fine-stranded conductors can be inserted directly within the specified push-in ranges, while other conductor types can be connected using the appropriate operating tool. This helps simplify installation while maintaining secure connections in industrial environments.
Although the terminal block's base insulation system has an 800 V IEC rating, the integrated LED indication circuit limits the intended operating application of this specific variant to its 12–30 V indication range. The complete circuit must be designed around the applicable LED-equipped terminal ratings and the characteristics of the selected fuse.
The WAGO 2006-1611/1000-541 is particularly useful for low-voltage control circuits where visual fuse failure indication is desirable. Compared with the standard WAGO 2006-1611 version without LED indication, this variant provides additional diagnostic functionality while retaining the compact TOPJOB® S terminal block format.
Tick the specs you need, then view products that match.
| Current | 10 A | |
|---|---|---|
| Voltage | 800 V | |
| Terminal Type | Fuse | |
| Colour | Grey | |
| Connection | Spring clamp | |
| Number of Levels | 1 | |
| Product Series | WAGO TOPJOB S | |
| Type of fuse holder | Swivelling | |
| Type of fuse insert | G-fuse 5x20 mm | |
| Connectable conductor cross section fine-strand with cable end sleeve | 1.5 – 6 mm² | |
| Height | 96.3 mm | |
| Operating temperature | 105 – 105 °C | |
| Flammability class of insulation material according to UL 94 | V0 | |
| Rated current In | 10 A | |
| Connectable conductor cross section fine-strand without cable end sleeve | 0.5 – 10 mm² | |
| Width | 7.5 mm | |
| Rated voltage | 800 V | |
| Material insulation body | Thermoplastic | |
| Type of electrical connection 2 | Spring clamp connection | |
| Number of levels | 1 | |
| Type of electrical connection 1 | Spring clamp connection | |
| Colour | Grey | |
| Closing plate required | Yes | |
| Connectable conductor cross section multi-wired | 0.5 – 6 mm² | |
| Connectable conductor cross section solid-core | 1 – 10 mm² | |
| Depth | 59 mm | |
| Supply voltage for defect-indication | 12 – 30 V | |
| Voltage type for defect indication | AC | |
| Mounting method | DIN rail (top hat rail) 35 mm | |
| Type of indication element for defect indication | LED | |
| Manufacturer | WAGO | |
| Series | TOPJOB® S 2006 Series | |
| Model | 2006-1611/1000-541 | |
| Product type | Fuse terminal block with LED indication | |
| Terminal configuration | 2-conductor, single-level | |
| Fuse holder type | Pivoting fuse carrier | |
| Fuse compatibility | 5 × 20 mm miniature cartridge fuse | |
| Blown fuse indication | Integrated LED | |
| LED indication voltage | 12–30 V | |
| Rated current (IEC) | 10 A | |
| Base terminal rated voltage (IEC) | 800 V | |
| Rated voltage with LED indication (IEC) | 30 V | |
| Base terminal rated impulse voltage | 8 kV | |
| Rated impulse voltage with LED indication | 0.8 kV | |
| Overvoltage category | III | |
| Pollution degree | 3 | |
| LED leakage current with blown fuse | Approx. 2.2 mA at 24 V | |
| Nominal conductor cross-section | 6 mm² | |
| Solid conductor range | 0.5–10 mm² | |
| Fine-stranded conductor range | 0.5–10 mm² | |
| Fine-stranded conductor with insulated ferrule | 0.5–6 mm² | |
| Solid conductor push-in range | 2.5–10 mm² | |
| Fine-stranded conductor with ferrule, push-in | 2.5–6 mm² | |
| Conductor size range | 20–8 AWG, depending on conductor type | |
| Connection technology | Push-in CAGE CLAMP® | |
| Number of clamping points | 2 | |
| Number of potentials | 1 | |
| Number of jumper slots | 2 | |
| Wiring direction | Front-entry wiring | |
| Actuation type | Operating tool | |
| Stripping length | 13–15 mm | |
| Conductor material | Copper | |
| Insulation material | Polyamide (PA66) | |
| Flammability rating | UL 94 V-0 | |
| Depth from upper edge of DIN rail | 59 mm | |
| Dimensions (W × H × D) | 7.5 × 96.3 × 59 mm | |
| Weight | Approx. 25 g | |
| Mounting type | DIN rail mounting | |
| Compatible DIN rails | 35 × 7.5 mm and 35 × 15 mm | |
| Maximum fuse power loss for overload and short-circuit protection | 1.6 W | |
| Maximum fuse power loss for short-circuit-only protection | 2.5 W | |
| Applicable IEC standard | IEC/EN 60947-7-3 | |
| UL approval standard | UL 1059 | |
| UL rated voltage | 30 V | |
| UL rated current | 15 A | |
| RoHS compliance | Compliant with applicable exemptions | |
| Country of origin | Germany | |
| Standard packaging unit | 25 pieces | |
| GTIN / EAN | 4045454823962 |
The WAGO 2006-1611/1000-541 is a 2-conductor fuse terminal block designed for low-voltage industrial electrical circuits. It combines a pivoting fuse holder, Push-in CAGE CLAMP® connections and integrated LED blown fuse indication to provide accessible circuit protection and visual fault identification.
The integrated LED blown fuse indicator is designed for a 12–30 V operating range, making this variant particularly suitable for 24 V DC industrial control circuits. The LED-equipped configuration has a 30 V IEC rated voltage, despite the higher base insulation rating of the terminal block.
The terminal block accepts standard 5 × 20 mm miniature cartridge fuses. The fuse must be selected according to the circuit's operating current, voltage, required protection characteristics and permitted fuse power dissipation.
The standard WAGO 2006-1611 is a fuse terminal block without blown fuse indication. The 2006-1611/1000-541 adds an integrated 12–30 V LED blown fuse indicator, allowing an operated fuse to be identified visually under suitable circuit conditions.
The WAGO 2006-1611/1000-541 has a 6 mm² nominal conductor cross-section and supports conductor sizes from 0.5–10 mm², depending on conductor construction and termination method. It mounts on standard 35 × 7.5 mm and 35 × 15 mm DIN rails and uses WAGO Push-in CAGE CLAMP® connection technology.
WAGO TOPJOB® S fuse terminal blocks provide reliable conductor connections, accessible fuse protection and efficient electrical panel integration. The WAGO 2006-1611/1000-541 adds integrated 12–30 V LED blown fuse indication to the established 2006 series design, helping automation engineers and electrical panel builders improve fault identification, simplify maintenance and maintain organised low-voltage industrial control systems.