Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
£2.42
The WAGO 2002-2672 is a compact double-deck disconnect terminal block with a pivoting knife disconnect, designed for reliable neutral and line conductor connections in industrial electrical control panels, automation cabinets and machinery installations. Part of the WAGO TOPJOB® S 2002 series, this grey terminal block combines a continuous lower-level feed-through connection with an upper-level disconnect function, providing two circuit functions within a single DIN rail terminal position.
Featuring an N/L configuration, the WAGO 2002-2672 provides four conductor connection points across two levels. The lower level is designated for neutral conductor feed-through, while the upper level provides a line conductor circuit incorporating a manually operated pivoting knife disconnect. This arrangement allows the line connection to be opened for testing, commissioning or maintenance while the separate neutral feed-through connection remains continuous.
With Push-in CAGE CLAMP® spring pressure connection technology, a 2.5 mm² nominal conductor cross-section, 400 V IEC rated voltage, 16 A rated current and a compact 5.2 mm width, the WAGO 2002-2672 provides an efficient solution for industrial control and auxiliary circuits requiring accessible functional disconnection.
The WAGO 2002-2672 is designed for industrial electrical installations requiring a continuous neutral conductor connection alongside a separately disconnectable line conductor circuit. Its compact double-deck construction accommodates both functions within a single terminal position, reducing the need for separate single-level terminals and supporting more efficient DIN rail layouts.
The lower level provides a continuous neutral feed-through connection, joining its two conductor termination points without a switching mechanism. The upper level incorporates a pivoting knife disconnect, allowing the line circuit to be opened when required for functional testing, commissioning or fault investigation.
When the pivoting knife disconnect is closed, the two upper-level conductor terminals are electrically connected. Opening the disconnect separates the upper circuit into two independent potentials, while the lower neutral connection remains continuous. This arrangement enables technicians to interrupt the designated line connection without mechanically disturbing the separate neutral feed-through circuit.
The terminal block uses WAGO Push-in CAGE CLAMP® technology, which applies spring pressure to maintain secure electrical contact with correctly prepared copper conductors. Suitable solid conductors and appropriately ferruled fine-stranded conductors can be inserted directly within the manufacturer's specified push-in ranges, helping reduce installation time during control panel manufacture.
With a 400 V IEC rated voltage, 16 A rated current and 6 kV impulse withstand voltage, the WAGO 2002-2672 supports a range of industrial control and auxiliary circuit applications. Its 5.2 mm width makes it especially useful where multiple disconnect terminals must be installed within a limited DIN rail space.
The pivoting knife disconnect is intended for functional circuit separation and testing in accordance with WAGO's installation instructions. It must not be used as a substitute for a suitably rated main isolator, protective switching device or approved lockable isolation arrangement where these are required. Hazardous-area installations must also comply with the applicable Ex certification conditions and installation standards.
Tick the specs you need, then view products that match.
| Current | 16 A | |
|---|---|---|
| Voltage | 400 V | |
| Terminal Type | Disconnect / Test | |
| Colour | Grey | |
| Connection | Spring clamp | |
| Number of Connection Points | 4 | |
| Number of Levels | 2 | |
| Product Series | WAGO TOPJOB S | |
| Connectable conductor cross section fine-strand with cable end sleeve | 0.75 – 2.5 mm² | |
| Number of clamp positions per level | 2 | |
| Height | 93 mm | |
| Operating temperature | 105 – 105 °C | |
| Flammability class of insulation material according to UL 94 | V0 | |
| Rated current In | 16 A | |
| Connectable conductor cross section fine-strand without cable end sleeve | 0.25 – 4 mm² | |
| Rated voltage | 400 V | |
| Width | 5.2 mm | |
| Number of levels | 2 | |
| Material insulation body | Thermoplastic | |
| Type of electrical connection 2 | Spring clamp connection | |
| Type of electrical connection 1 | Spring clamp connection | |
| Closing plate required | Yes | |
| Colour | Grey | |
| Connectable conductor cross section multi-wired | 0.25 – 2.5 mm² | |
| Connectable conductor cross section solid-core | 0.75 – 4 mm² | |
| Type of cross disconnection | None | |
| Depth | 51.7 mm | |
| Type of slitting | None | |
| Mounting method | DIN rail (top hat rail) 35 mm | |
| Manufacturer | WAGO | |
| Product series | TOPJOB® S 2002 | |
| Manufacturer part number | 2002-2672 | |
| Product type | Double-deck disconnect terminal block | |
| Terminal configuration | Through/disconnect | |
| Potential designation | N/L | |
| Disconnect mechanism | Pivoting knife disconnect | |
| Upper-level function | Line conductor disconnect | |
| Lower-level function | Neutral conductor feed-through | |
| Number of conductor connection points | 4 | |
| Connection points per level | 2 | |
| Total number of electrical potentials | 3 | |
| Internal connection between levels | No | |
| Connection technology | Push-in CAGE CLAMP® | |
| Connection method | Spring pressure connection | |
| Wiring direction | Front-entry wiring | |
| Nominal conductor cross-section | 2.5 mm² | |
| Solid conductor range | 0.25–4 mm² | |
| Fine-stranded conductor range | 0.25–4 mm² | |
| Solid conductor push-in range | 0.75–4 mm² | |
| Fine-stranded conductor with ferrule, push-in minimum | 0.75 mm² | |
| Conductor size range | 22–12 AWG | |
| Conductor material | Copper | |
| Rated voltage (IEC) | 400 V | |
| Rated current (IEC) | 16 A | |
| Rated impulse withstand voltage | 6 kV | |
| Overvoltage category | III | |
| Pollution degree | 3 | |
| Rated voltage (UL, Use Group B) | 300 V | |
| Rated current (UL, Use Group B) | 15 A | |
| Rated voltage (UL, Use Group C) | 300 V | |
| Rated current (UL, Use Group C) | 15 A | |
| Rated voltage (CSA, Use Groups B/C) | 600 V | |
| Rated current (CSA, Use Groups B/C) | 15 A | |
| ATEX certification reference | KIWA 17 ATEX 0030 U | |
| IECEx certification reference | KIWA 17.0014U | |
| Hazardous-area designation | Ex ec IIC Gc | |
| Ex rated voltage | 440 V | |
| Ex rated current | 14 A | |
| Conductor stripping length | 10–12 mm | |
| Compatible DIN rails | 35 × 7.5 mm / 35 × 15 mm | |
| Terminal width | 5.2 mm | |
| Terminal depth | 93 mm | |
| Height above DIN rail | 56.4 mm | |
| Depth from upper edge of DIN rail | 51.7 mm | |
| Housing colour | Grey | |
| Insulation material | Polyamide 66 (PA66) | |
| Flammability classification | UL 94 V-0 | |
| Continuous operating temperature range | −60 to +105 °C | |
| Processing temperature range | −35 to +85 °C | |
| Marking positions | Centre and side marking | |
| Compatible marking systems | WMB, WMB Inline and marking strips | |
| Compatible end and intermediate plate | WAGO 2002-2691, grey | |
| Packaging unit | 50 pieces | |
| Country of origin | Germany | |
| GTIN / EAN | 4050821403883 |
The WAGO 2002-2672 is a double-deck disconnect terminal block used in industrial electrical control panels and automation systems where a continuous neutral feed-through connection and a separately disconnectable line circuit are required.
The pivoting knife disconnect is fitted to the upper level. When closed, it connects the two upper-level conductor terminals. When opened, it interrupts the upper-level line connection while leaving the lower-level neutral feed-through circuit continuous.
The N/L configuration identifies the lower level as the neutral feed-through circuit and the upper level as the line circuit with a pivoting knife disconnect. The two levels remain electrically separate.
The terminal block provides four conductor connection points, with two connection points on the upper level and two on the lower level.
The WAGO 2002-2672 has a 400 V IEC rated voltage, 16 A IEC rated current and 6 kV rated impulse withstand voltage.
The terminal block has a 2.5 mm² nominal conductor cross-section and accepts suitable solid and fine-stranded copper conductors within a 0.25–4 mm² range, depending on conductor construction and termination method.
No. The pivoting knife disconnect operates on the upper-level line circuit only. The lower-level neutral feed-through connection remains continuous when the disconnect is opened.
Both products are TOPJOB® S double-deck terminal blocks with a pivoting knife disconnect. The 2002-2671 has an L/L configuration, while the 2002-2672 has an N/L configuration, providing a neutral feed-through circuit on the lower level and a disconnectable line circuit on the upper level.
The WAGO 2002-2672 has documented Ex ec IIC Gc certification references for specified applications. Hazardous-area installations must comply with the applicable certification conditions, electrical ratings and relevant installation standards.
The terminal block is designed for standard 35 × 7.5 mm and 35 × 15 mm DIN rails used in industrial electrical cabinets and control panel assemblies.
No. The pivoting knife disconnect provides functional circuit separation for suitable testing and maintenance applications. It is not a substitute for a properly rated main isolator, protective switching device or approved lockable isolation arrangement where required.
WAGO TOPJOB® S terminal blocks are established components in industrial electrical installations where dependable spring pressure connections, organised wiring and accessible circuit testing are essential. The WAGO 2002-2672 combines a continuous neutral feed-through connection, an upper-level pivoting knife disconnect and Push-in CAGE CLAMP® technology to support reliable, space-efficient control panel construction and convenient functional circuit disconnection.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.