Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
TE Connectivity CC-E-VA 1SNA166737R2000 is a green ESSAILEC 15 A 400 V current test socket with make-before-break short-circuiting contacts, designed for safe measurement, calibration and testing of current-transformer secondary circuits.
£130.82
The TE Connectivity CC-E-VA 1SNA166737R2000 is a professional ESSAILEC current test socket designed for current-transformer measurement, calibration and distribution circuits. Part of the established TE Connectivity ENTRELEC ESSAILEC test block range, it provides a secure test interface for secondary current circuits used in metering, protection and electrical monitoring installations.
The CC-E-VA uses a make-before-break short-circuiting contact system engineered specifically for current-transformer applications. When a compatible plug is inserted, the circuit is automatically short-circuited before the measuring circuit is opened, and when the plug is removed the circuit closes automatically. This operating principle helps protect current-transformer secondary circuits during testing and maintenance.
Rated at 15 A and 400 V, the CC-E-VA accepts flexible conductors from 0.34–10 mm² through ring-tongue connections. Its green housing identifies it as an ESSAILEC current-circuit component, while compact dimensions of 74 × 50 × 57 mm (H × W × D) make it suitable for integration into industrial switchboards, protection panels and metering systems.
Current-transformer secondary circuits require careful handling because opening a live secondary circuit can create hazardous voltages. The ESSAILEC CC-E-VA addresses this requirement through its make-before-break arrangement, automatically establishing a short circuit during insertion of the compatible test plug before the measurement circuit is interrupted.
This operating principle makes the ESSAILEC system well suited to meter testing, relay commissioning, calibration and maintenance work. Dedicated plugs and accessories allow test equipment to be connected through an organised interface while reducing the need to disturb permanent current-transformer wiring.
Tick the specs you need, then view products that match.
| Terminal Type | Disconnect / Test | |
|---|---|---|
| Product Series | TE Essailec | |
| Colour | Green | |
| Manufacturer | TE Connectivity / ENTRELEC | |
| Series | ESSAILEC | |
| Model | CC-E-VA | |
| Part number | 1SNA166737R2000 | |
| Product type | Current test socket / mains test block | |
| Function | Current-transformer measurement, calibration and distribution | |
| Circuit type | Current | |
| Contact principle | Make before break | |
| Connection type | Ring-tongue | |
| Rated current | 15 A | |
| Rated voltage | 400 V | |
| Rated impulse withstand voltage | 4 kV | |
| Short-time withstand current | 200 A for 1 s | |
| Flexible conductor capacity | 0.34–10 mm² | |
| Pollution degree | 3 | |
| Colour | Green | |
| Body material | Polycarbonate | |
| Conductive parts | Gold-plated | |
| Height | 74 mm | |
| Width | 50 mm | |
| Depth | 57 mm | |
| Net weight | approx. 145 g | |
| Compatible lid | CPC-1 | |
| EAN | 3472591667370 |
The CC-E-VA is an ESSAILEC current test socket designed for current-transformer measurement, calibration, testing and distribution circuits.
The CC-E-VA is rated for 15 A and 400 V.
It uses a make-before-break system that automatically short-circuits the current circuit when a compatible test plug is inserted and automatically closes the circuit again when the plug is removed.
The ring-tongue connection supports flexible conductors from approximately 0.34–10 mm².
The CC-E-VA measures approximately 74 × 50 × 57 mm in height, width and depth and has a net weight of approximately 145 g.
TE Connectivity ENTRELEC ESSAILEC current test blocks provide secure make-before-break interfaces for current-transformer measurement, calibration and protection circuits, helping engineers carry out testing and maintenance while maintaining the integrity of critical secondary current circuits.