2CSF204998R0035 ABB F3C-AR230 C 4/300 Auto Recloser 4P 300mA

2CSF204998R0035 ABB F3C-AR230 C 4/300 Auto Recloser 4P 300mA

ABB F3C-AR230 C 4/300 is an automatic reclosing unit with system check for compatible four-pole F200 RCCBs with 300 mA residual-current sensitivity, designed to restore electrical service automatically after temporary trips when no effective fault remains.

SKU: 2CSF204998R0035Alt SKU: F3CAR230C4300MPN: 2CSF204998R0035
Price
List Price £494.87 ex VAT
Your Price (ex VAT) Save 35%
£321.67 35% OFF
You save £173.20 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £321.67
Trade pricing is personalised to your account

Manufacturer Lead Time

£321.67

Why Choose the ABB F3C-AR230 C 4/300 Auto Recloser?

The ABB F3C-AR230 C 4/300 is an automatic reclosing unit with system check designed for use with compatible four-pole ABB F200 residual current circuit breakers (RCCBs). Part of ABB’s System pro M compact accessory range, it automatically manages the reclosing of an associated RCCB following an unwanted trip, helping restore electrical service without requiring immediate manual intervention.

Unlike a basic automatic reclosing mechanism, the F3C-AR230 C incorporates a system check function. Before attempting to reclose the associated RCCB, the unit checks the protected installation to confirm that an effective fault is not still present. This makes it particularly useful for unattended installations and applications where continuity of electrical service is important while maintaining controlled reclosing behaviour.

The F3C-AR230 C 4/300 is specifically configured for compatible four-pole F200 RCCBs with 300 mA residual-current sensitivity. It operates from a 230–240 V AC supply and is suitable for F200 RCCBs rated up to 100 A, or up to 63 A when used with compatible Type B devices.

Key Advantages

  • Automatic RCCB reclosing helps restore service following temporary or unwanted trips.
  • Integrated system check before reclosing verifies that an effective fault is not present.
  • Designed specifically for compatible 4P F200 RCCBs with 300 mA sensitivity.
  • Suitable for F200 RCCBs up to 100 A, or compatible Type B RCCBs up to 63 A.
  • 230–240 V AC operating supply for integration into standard electrical installations.
  • Supports continuity of service in unattended and difficult-to-access electrical installations.
  • Compact DIN-rail accessory designed for integration with ABB modular protection equipment.

Key Features

  • ABB F3C-AR230 C automatic reclosing unit.
  • System check function prior to automatic reclosing.
  • Designed for compatible four-pole F200 RCCBs.
  • Suitable for RCCBs with 300 mA residual-current sensitivity.
  • 230–240 V AC operating voltage.
  • Up to 48 automatic reclosing attempts.
  • 45-second waiting period between automatic reclosing attempts.
  • Automatic system checking can continue for up to 24 hours following a fault.
  • IP40 / IP20 protection ratings according to installation condition.
  • Plug-in terminal connection for straightforward installation.

Automatic Reclosing with System Check

The ABB F3C-AR230 C series is designed to improve continuity of service following temporary residual-current trips. When the associated RCCB trips, the unit checks the protected electrical system before initiating a reclosing operation. Reclosing is only attempted when the system check determines that an effective fault is not present, reducing the risk of automatically reconnecting a circuit while a persistent fault remains.

This functionality makes the F3C-AR230 C 4/300 particularly valuable in unattended installations, remote equipment and electrical systems where unnecessary downtime can be disruptive. The unit can perform up to 48 automatic reclosing attempts and can continue checking for conditions that permit safe reclosing for up to 24 hours following a fault.

Typical Applications

  • Unattended electrical installations requiring continuity of service.
  • Commercial and industrial electrical distribution boards.
  • Remote electrical equipment and installations that are difficult to access.
  • Building automation and infrastructure electrical systems.
  • Compatible four-pole ABB F200 RCCB installations.
  • Circuits requiring automatic restoration following temporary residual-current trips.

Technical Specifications

Series F3C-AR230 C
Product group F200 / FH200 RCCB accessories
ABB order code 2CSF204998R0035
Product type Automatic reclosing unit with system check
Compatible RCCB configuration 4P
Compatible RCCB residual-current sensitivity 300 mA
Compatible F200 rated current Up to 100 A
Compatible F200 Type B rated current Up to 63 A
Operating voltage 230–240 V AC
Operating voltage tolerance -15% / +10%
Maximum automatic reclosing attempts 48
Waiting time between reclosing attempts 45 s
Operating power consumption <26 VA
Standby power consumption <1.5 VA
Closing time <1 s
Opening time <1 s
Protection rating IP40 / IP20
Pollution degree 2
Terminal type Plug-in connection
Terminal conductor size 0.2–2.5 mm²
Terminal tightening torque 0.4 N·m
Operating temperature -25–60 °C
Dimensions (H × W × D) 104.15 × 81.5 × 58.3 mm
Weight approx. 130 g
Standard IEC/EN 63024

Frequently Asked Questions

What is the ABB F3C-AR230 C 4/300 used for?

The ABB F3C-AR230 C 4/300 is an automatic reclosing unit with system check used with compatible four-pole ABB F200 RCCBs to restore service automatically after an unwanted or temporary trip when the protected system is determined to be free from an effective fault.

Which RCCBs are compatible with the F3C-AR230 C 4/300?

The unit is designed for compatible four-pole ABB F200 RCCBs with 300 mA residual-current sensitivity, supporting F200 devices up to 100 A or compatible Type B devices up to 63 A.

How does the system check function work?

Before automatically reclosing the associated RCCB, the F3C-AR230 C checks the protected electrical system to determine whether an effective fault remains. Reclosing is attempted only when conditions permit restoration of the circuit.

What supply voltage does the ABB F3C-AR230 C 4/300 require?

The automatic reclosing unit operates from a 230–240 V AC supply.

What is the ABB order code for the F3C-AR230 C 4/300?

The ABB order code for the F3C-AR230 C 4/300 is 2CSF204998R0035.

Trusted ABB Automatic Reclosing Technology

ABB F3C-AR automatic reclosing units help maintain continuity of electrical service in unattended and critical installations, with F3C-AR230 C models adding a system check that verifies installation conditions before automatically reclosing the associated residual current circuit breaker.