Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB F3C-AR230 C 4/300 is an automatic reclosing unit with system check for compatible four-pole F200 RCCBs with 300 mA residual-current sensitivity, designed to restore electrical service automatically after temporary trips when no effective fault remains.
£321.67
The ABB F3C-AR230 C 4/300 is an automatic reclosing unit with system check designed for use with compatible four-pole ABB F200 residual current circuit breakers (RCCBs). Part of ABB’s System pro M compact accessory range, it automatically manages the reclosing of an associated RCCB following an unwanted trip, helping restore electrical service without requiring immediate manual intervention.
Unlike a basic automatic reclosing mechanism, the F3C-AR230 C incorporates a system check function. Before attempting to reclose the associated RCCB, the unit checks the protected installation to confirm that an effective fault is not still present. This makes it particularly useful for unattended installations and applications where continuity of electrical service is important while maintaining controlled reclosing behaviour.
The F3C-AR230 C 4/300 is specifically configured for compatible four-pole F200 RCCBs with 300 mA residual-current sensitivity. It operates from a 230–240 V AC supply and is suitable for F200 RCCBs rated up to 100 A, or up to 63 A when used with compatible Type B devices.
The ABB F3C-AR230 C series is designed to improve continuity of service following temporary residual-current trips. When the associated RCCB trips, the unit checks the protected electrical system before initiating a reclosing operation. Reclosing is only attempted when the system check determines that an effective fault is not present, reducing the risk of automatically reconnecting a circuit while a persistent fault remains.
This functionality makes the F3C-AR230 C 4/300 particularly valuable in unattended installations, remote equipment and electrical systems where unnecessary downtime can be disruptive. The unit can perform up to 48 automatic reclosing attempts and can continue checking for conditions that permit safe reclosing for up to 24 hours following a fault.
| Series | F3C-AR230 C |
|---|---|
| Product group | F200 / FH200 RCCB accessories |
| ABB order code | 2CSF204998R0035 |
| Product type | Automatic reclosing unit with system check |
| Compatible RCCB configuration | 4P |
| Compatible RCCB residual-current sensitivity | 300 mA |
| Compatible F200 rated current | Up to 100 A |
| Compatible F200 Type B rated current | Up to 63 A |
| Operating voltage | 230–240 V AC |
| Operating voltage tolerance | -15% / +10% |
| Maximum automatic reclosing attempts | 48 |
| Waiting time between reclosing attempts | 45 s |
| Operating power consumption | <26 VA |
| Standby power consumption | <1.5 VA |
| Closing time | <1 s |
| Opening time | <1 s |
| Protection rating | IP40 / IP20 |
| Pollution degree | 2 |
| Terminal type | Plug-in connection |
| Terminal conductor size | 0.2–2.5 mm² |
| Terminal tightening torque | 0.4 N·m |
| Operating temperature | -25–60 °C |
| Dimensions (H × W × D) | 104.15 × 81.5 × 58.3 mm |
| Weight | approx. 130 g |
| Standard | IEC/EN 63024 |
The ABB F3C-AR230 C 4/300 is an automatic reclosing unit with system check used with compatible four-pole ABB F200 RCCBs to restore service automatically after an unwanted or temporary trip when the protected system is determined to be free from an effective fault.
The unit is designed for compatible four-pole ABB F200 RCCBs with 300 mA residual-current sensitivity, supporting F200 devices up to 100 A or compatible Type B devices up to 63 A.
Before automatically reclosing the associated RCCB, the F3C-AR230 C checks the protected electrical system to determine whether an effective fault remains. Reclosing is attempted only when conditions permit restoration of the circuit.
The automatic reclosing unit operates from a 230–240 V AC supply.
The ABB order code for the F3C-AR230 C 4/300 is 2CSF204998R0035.
ABB F3C-AR automatic reclosing units help maintain continuity of electrical service in unattended and critical installations, with F3C-AR230 C models adding a system check that verifies installation conditions before automatically reclosing the associated residual current circuit breaker.