2CSF203998R0035 ABB F3C-AR230 C 4/30 Auto-Reclosing Unit 4P 30mA

2CSF203998R0035 ABB F3C-AR230 C 4/30 Auto-Reclosing Unit 4P 30mA

ABB F3C-AR230 C 4/30 is an automatic reclosing unit with preventive system checking for compatible 4-pole 30 mA F200 RCCBs up to 100 A, or Type B F200 RCCBs up to 63 A.

SKU: 2CSF203998R0035Alt SKU: F3CAR230C430MPN: 2CSF203998R0035
Price
List Price £494.87 ex VAT
Your Price (ex VAT) Save 35%
£321.67 35% OFF
You save £173.20 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £321.67
Trade pricing is personalised to your account

Manufacturer Lead Time

£321.67

Why Choose the ABB F3C-AR230 C 4/30 Auto-Reclosing Unit?

The ABB F3C-AR230 C 4/30, order code 2CSF203998R0035, is an advanced automatic reclosing unit with system checking designed for compatible 4-pole ABB F200 residual current circuit breakers. As part of the ABB F200 / FH200 RCCB product group, it can automatically restore the associated RCCB after an unwanted trip, but only after checking that there is no effective fault remaining in the protected electrical system.

This version is specifically designed for 4-pole F200 RCCBs with 30 mA residual current sensitivity. Before reclosing, the F3C-AR230 C performs an assessment of the protected system, helping prevent reconnection while a genuine earth fault remains present. It supports compatible standard F200 RCCBs up to 100 A and Type B F200 RCCBs up to 63 A.

The unit operates from a 230–240 V AC supply and is intended for compatible 4-pole 400 V RCCB installations. Its automatic system-checking and reclosing functionality can improve continuity of service in commercial, industrial and unattended installations where restoring power safely after transient residual-current events is important.

Key Advantages

  • Advanced automatic reclosing unit with system check.
  • Designed for compatible 4-pole F200 30 mA RCCBs.
  • Checks the protected system before attempting automatic reclosing.
  • Compatible with standard F200 RCCBs up to 100 A.
  • Compatible with F200 Type B RCCBs up to 63 A.
  • Supports up to 48 automatic reclosing attempts.
  • Helps improve continuity of electrical service following temporary or unwanted trips.

Key Features

  • ABB F3C-AR230 C automatic reclosing series.
  • 4-pole / 30 mA version.
  • 230–240 V AC operating supply.
  • Designed for compatible 4-pole, 400 V F200 RCCBs.
  • Automatic reclosing with preventive system assessment.
  • 48 maximum automatic reclosing attempts.
  • 45 s waiting time between automatic reclosing attempts.
  • System checking can continue for up to 24 hours after a fault.
  • Suitable for TT and TN electrical systems.
  • 1.5-module compact construction.
  • Designed in accordance with IEC/EN 63024.

Automatic Reclosing with Preventive System Checking

The ABB F3C-AR230 C range is designed to improve continuity of supply while maintaining controlled residual current protection. Following an unexpected trip, the unit checks the protected electrical system before operating the associated RCCB. Automatic reclosing takes place only when the assessment indicates that no effective fault remains in the system.

For the F3C-AR230 C 4/30, this functionality is specifically configured for compatible 4-pole 30 mA F200 RCCBs. The unit can perform up to 48 automatic reclosing attempts and can continue assessing the installation for up to 24 hours after the fault, making it particularly useful where electrical continuity and unattended recovery are important.

Typical Applications

  • Commercial and industrial electrical distribution systems.
  • Compatible 4-pole ABB F200 RCCB installations.
  • Unattended electrical installations requiring automatic supply restoration.
  • Building services and facility management systems.
  • Remote installations where manual RCCB resetting is inconvenient.
  • TT and TN distribution systems requiring system assessment before reclosing.
  • Applications using compatible 4-pole 30 mA RCCBs where continuity of service is important.

Technical Specifications

Series F3C-AR230 C
Product group F200 / FH200 RCCB
Manufacturer part number F3CAR230C430
ABB order code 2CSF203998R0035
Product type Automatic reclosing unit with system check
Compatible RCCB poles 4
Compatible RCCB residual current 30 mA
Compatible RCCB voltage 400 V
Operating supply voltage 230–240 V AC (-15% / +10%)
Compatible F200 rated current Up to 100 A
Compatible F200 Type B rated current Up to 63 A
Maximum automatic reclosing attempts 48
Waiting time between reclosing attempts 45 s
System check availability Up to 24 hours after fault
Nominal non-reclosing resistance Rd0 22 kΩ
Nominal reclosing resistance Rd 8 kΩ
Suitable earthing systems TT / TN
Power consumption during operation <26 VA
Power consumption at rest <1.5 VA
Closing time <1 s
Opening time <1 s
Number of modules 1.5
Protection rating IP40 / IP20
Pollution degree 2
Operating temperature -25 to +60 °C
Terminal type Plug-in connection
Tightening torque 0.4 N·m
Dimensions (H × W × D) 104.15 × 81.5 × 58.3 mm
Weight approx. 0.13 kg
Standard IEC/EN 63024

Frequently Asked Questions

What is the ABB F3C-AR230 C 4/30 used for?

The ABB F3C-AR230 C 4/30 is an automatic reclosing unit with system checking for compatible 4-pole 30 mA ABB F200 RCCBs, designed to assess the protected system before automatically reclosing the associated device.

Which RCCBs are compatible with the F3C-AR230 C 4/30?

The unit is designed for compatible 4-pole 30 mA ABB F200 RCCBs up to 100 A, or up to 63 A for compatible F200 Type B RCCBs.

What supply voltage does the F3C-AR230 C 4/30 require?

The automatic reclosing unit operates from a 230–240 V AC supply and is intended for compatible 4-pole 400 V RCCB applications.

Does the F3C-AR230 C 4/30 check for faults before reclosing?

Yes. The unit performs a preventive assessment of the protected system and only recloses the associated RCCB when its system check determines that there is no effective fault preventing reconnection.

How many automatic reclosing attempts can the F3C-AR230 C 4/30 make?

The unit supports up to 48 automatic reclosing attempts, with a 45 s waiting time between attempts and system checking available for up to 24 hours after a fault.

Trusted ABB Automation for Electrical Protection

ABB F3C-AR230 C automatic reclosing units combine automated RCCB operation with preventive system checking, helping improve continuity of supply while ensuring that reclosing is attempted only after assessment of the protected electrical system.