Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB S3C-UA 110 is a 110 V AC/DC undervoltage release with positive-safety tripping and LED event indication for compatible ABB modular circuit protection devices.
£56.28
The ABB S3C-UA 110 is an undervoltage release designed for compatible ABB modular circuit protection devices. Operating at a rated voltage of 110 V AC/DC, it trips the associated protection device when the control voltage falls below the specified operating range, helping protect connected equipment during significant supply-voltage reductions.
The S3C-UA 110 provides positive-safety operation, meaning the associated protection device trips when the control voltage is disconnected. This operating principle also allows the accessory to be incorporated into appropriately designed emergency-stop circuits using an external control button.
An integrated LED indication function identifies when an undervoltage event has occurred. The S3C-UA family is suitable for compatible ABB MCBs, RCCBs, RCBOs and switch-disconnectors, with interface modules available for selected additional device ranges.
An undervoltage release mechanically trips its associated protection device when the monitored control supply falls below an acceptable level. ABB specifies the S3C-UA operating region between approximately 70% and 35% of rated voltage, helping prevent continued operation under significant undervoltage conditions.
The ABB S3C-UA 110 also provides positive-safety behaviour by tripping when the control voltage is removed completely. Combined with its 110 V AC/DC rating and LED event indication, this makes it suitable for industrial control, distribution and appropriately designed emergency-stop circuits.
| Series | S3C-UA |
|---|---|
| Order code | 2CDS200985R0044 |
| EAN | 4053546159431 |
| Product type | Undervoltage release |
| Rated voltage | 110 V AC/DC |
| Frequency | 50–60 Hz |
| Release range | 0.35–0.70 × Un |
| DC consumption | approx. 0.94 VA |
| AC consumption | approx. 1.73 VA |
| Terminal capacity | 1 × 0.75–2.5 mm² or 2 × up to 1.5 mm² each |
| Tightening torque | 0.8 Nm |
| Protection degree | IPXXB / IP2X |
| Dimensions (H × D × W) | 85 × 71.1 × 17.4 mm |
| Mounting position | Any |
| Standard | IEC/EN 60947-1 |
| Conducted emissions | CISPR 11 Class A compliant |
| Weight | approx. 0.09 kg |
| Pack quantity | 1 piece |
| Product group | MCB Accessories |
The S3C-UA 110 is an undervoltage release that trips a compatible ABB protection device when its control voltage falls below the specified operating range or is disconnected.
The ABB S3C-UA 110 has a rated voltage of 110 V AC/DC, with AC operation at 50–60 Hz.
ABB specifies the undervoltage release region between approximately 35% and 70% of the rated voltage.
Yes. The S3C-UA series incorporates an LED function to indicate that an undervoltage event has occurred.
Yes. Its positive-safety operating principle allows the S3C-UA 110 to be incorporated into an appropriately designed emergency-stop circuit using a suitable external control button.