1SDA107611R1 ABB TMA 630-6300 XT6 4P InN=100%In

1SDA107611R1 ABB TMA 630-6300 XT6 4P InN=100%In

ABB 1SDA107611R1 is a 630 A four-pole TMA thermomagnetic trip unit for compatible SACE Tmax XT6 circuit-breaker assemblies, providing adjustable thermal and 3150–6300 A instantaneous magnetic protection with a fully rated neutral.

SKU: 1SDA107611R1MPN: 1SDA107611R1
Price
List Price £1,348.20 ex VAT
Your Price (ex VAT) Save 25%
£1,011.15 25% OFF
You save £337.05 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,011.15
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,011.15

Why Choose the ABB 1SDA107611R1 TMA 630-6300 XT6 4P Trip Unit?

The ABB 1SDA107611R1, designated TMA 630-6300 XT6 4p InN=100%In, is a four-pole thermomagnetic trip unit designed for compatible ABB SACE Tmax XT6 circuit-breaker assemblies. Rated at 630 A, it combines adjustable thermal overload protection with adjustable magnetic short-circuit protection for low-voltage power distribution applications.

The TMA release provides a thermal adjustment range of 0.7–1 × In, corresponding to 441–630 A at its 630 A nominal rating. Instantaneous magnetic protection is adjustable from 5–10 × In, providing a short-circuit setting range of 3150–6300 A for coordination with the protected distribution circuit.

This version is specifically configured with a fully rated neutral at 100% of the phase current. The 1SDA107611R1 is supplied as a separate XT6 protection trip unit and is designed to be combined with a compatible four-pole XT6 breaking unit to form a complete moulded-case circuit breaker.

Key Advantages

  • Genuine ABB SACE Tmax XT6 thermomagnetic trip unit.
  • 630 A nominal current for high-capacity power distribution.
  • Adjustable thermal overload protection from 0.7–1 × In.
  • Adjustable instantaneous magnetic protection from 5–10 × In.
  • Magnetic short-circuit setting range of 3150–6300 A.
  • Four-pole configuration with a fully rated neutral.
  • Designed for integration with compatible ABB XT6 four-pole breaking units.

Key Features

  • ABB SACE Tmax XT6 protection unit.
  • Trip unit type: TMA thermomagnetic.
  • Nominal current: 630 A.
  • Thermal adjustment: 0.7–1 × In.
  • Thermal setting range: 441–630 A.
  • Magnetic adjustment: 5–10 × In.
  • Magnetic setting range: 3150–6300 A.
  • Number of poles: 4.
  • Neutral rating: 100% of phase rated current.
  • Suitable for compatible XT6 power circuit-breaker assemblies.

Adjustable Thermomagnetic Protection with a Fully Rated Neutral

The ABB TMA trip unit combines two established protection principles. Its thermal element protects against sustained overloads and can be adjusted between 0.7 and 1 times the 630 A nominal current, while its magnetic element provides rapid protection against high short-circuit currents with an adjustable range of 5 to 10 times the nominal current.

The defining characteristic of the 1SDA107611R1 is its InN=100%In fully rated neutral configuration. Unlike the 1SDA107610R1 reduced-neutral version, this trip unit provides neutral protection corresponding to 100% of the phase rated current. As a separate protection unit, it must be paired with a compatible four-pole XT6 breaking unit when assembling the complete circuit breaker.

Typical Applications

  • ABB SACE Tmax XT6 circuit-breaker assemblies.
  • Industrial low-voltage power distribution systems.
  • Main and sub-distribution switchboards.
  • Commercial and infrastructure electrical distribution.
  • Four-wire systems requiring a fully rated neutral.
  • Feeder and distribution circuit protection.
  • Applications requiring adjustable thermal and magnetic protection.
  • Configurable XT6 circuit breakers assembled from separate breaking and protection units.

Technical Specifications

Series SACE Tmax XT / Tmax XT 250 Range
Order code 1SDA107611R1
Product type Thermomagnetic trip unit
Compatible circuit-breaker family SACE Tmax XT6
Trip unit TMA
Protection technology Thermomagnetic
Nominal current In 630 A
Thermal protection adjustment 0.7–1 × In
Thermal protection range 441–630 A
Magnetic protection adjustment 5–10 × In
Instantaneous short-circuit setting I3 3150–6300 A
Number of poles 4
Neutral rating 100% of phase rated current
Neutral configuration Fully rated neutral
Neutral designation InN=100%In
Application Power distribution protection
Installation Combined with a compatible XT6 four-pole breaking unit
Product weight 1.3 kg
Minimum order quantity 1 piece
EAN / GTIN 8015644102647
Customs tariff number 85389099

Frequently Asked Questions

What is the ABB 1SDA107611R1?

The 1SDA107611R1 is a 630 A four-pole TMA thermomagnetic trip unit for compatible ABB SACE Tmax XT6 circuit-breaker assemblies, providing adjustable thermal and magnetic protection with a fully rated neutral.

Is the ABB 1SDA107611R1 a complete circuit breaker?

No. The 1SDA107611R1 is the thermomagnetic protection trip unit. It is designed to be combined with a compatible four-pole ABB XT6 breaking unit to form the complete moulded-case circuit breaker.

What are the adjustment ranges of the TMA 630-6300 trip unit?

The thermal protection is adjustable from 0.7–1 × In, corresponding to 441–630 A, while the instantaneous magnetic protection is adjustable from 5–10 × In, corresponding to 3150–6300 A.

What does InN=100%In mean on the ABB 1SDA107611R1?

InN=100%In means the four-pole trip unit has a fully rated neutral, with the neutral protection corresponding to 100% of the phase rated current.

Which ABB circuit-breaker family is compatible with the 1SDA107611R1?

The 1SDA107611R1 is designed for the ABB SACE Tmax XT6 platform and is intended to be combined with a compatible four-pole XT6 breaking unit.

Trusted ABB Tmax XT Protection

ABB SACE Tmax XT protection units provide configurable circuit protection for low-voltage distribution systems, with the 1SDA107611R1 delivering 630 A adjustable thermomagnetic protection and a fully rated neutral for compatible four-pole XT6 circuit-breaker assemblies.