Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA107608R1 is a 630 A three-pole Ekip G Dip LS/I electronic trip unit designed for generator protection with ABB SACE Tmax XT6 moulded case circuit breakers.
£859.85
The ABB 1SDA107608R1 is an electronic Ekip G Dip LS/I protection trip unit designed for use with ABB SACE Tmax XT6 moulded case circuit breakers in generator protection applications. With a rated current of 630 A and a three-pole configuration, it provides dedicated electronic protection for generators and associated low-voltage electrical distribution systems.
As part of the advanced ABB SACE Tmax XT protection system, the Ekip G Dip range is specifically designed to address the protection requirements of generators. The LS/I functionality provides long-time overload, selective short-circuit and instantaneous short-circuit protection, helping protect generators and connected electrical equipment against damaging overcurrent and fault conditions.
The 1SDA107608R1 is designed for the ABB Tmax XT6 frame and has a nominal current rating of 630 A. Its DIP-switch-based electronic adjustment provides straightforward protection configuration, making it suitable for generator installations where dependable and configurable circuit protection is required.
Generator installations require protection characteristics suited to the operating and fault-current behaviour of generating equipment. The ABB Ekip G Dip range is developed specifically for generator protection, providing electronic overcurrent functions that help safeguard generators and connected distribution equipment against overloads and short circuits.
The Ekip G Dip LS/I combines long-time, selective short-circuit and instantaneous protection functions in a configurable electronic release. When installed with a compatible ABB Tmax XT6 circuit breaker, it provides a robust protection solution for generators used in industrial plants, commercial facilities, infrastructure and standby power systems.
| Series | SACE Tmax XT / Ekip G Dip |
|---|---|
| Product group | T-Max XT 250 Range |
| Order code | 1SDA107608R1 |
| Product type | Electronic protection trip unit |
| Application | Generator protection |
| Compatible circuit breaker | ABB SACE Tmax XT6 |
| Rated current | 630 A |
| Number of poles | 3 |
| Trip unit | Ekip G Dip LS/I |
| Protection functions | L, S, I |
| Long-time protection setting | 252–630 A |
| Instantaneous protection setting | 630–6300 A |
| Adjustment method | DIP switches |
| GTIN / EAN | 8015644102616 |
| Weight | approx. 1.4 kg |
The ABB 1SDA107608R1 is an Ekip G Dip electronic trip unit designed for generator protection when used with compatible ABB SACE Tmax XT6 moulded case circuit breakers.
The Ekip G Dip LS/I trip unit has a rated current of 630 A.
The trip unit is designed for use with the ABB SACE Tmax XT6 moulded case circuit breaker platform.
The trip unit provides long-time overload (L), selective short-circuit (S) and instantaneous short-circuit (I) protection for generator applications.
Yes. ABB order code 1SDA107608R1 is the three-pole 630 A Ekip G Dip LS/I version designed for the Tmax XT6 platform.
ABB SACE Tmax XT protection solutions are widely used in industrial, commercial and infrastructure electrical systems, with Ekip G electronic trip units providing dedicated protection functionality for generator applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.