Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA105231R1 is a ROCOF protection software package for compatible SACE Emax 2 circuit breakers, providing configurable ANSI 81R rate-of-change-of-frequency protection through the Ekip protection system.
£1,235.61
The ABB 1SDA105231R1 is a ROCOF (Rate of Change of Frequency) protection software package for ABB SACE Emax 2 air circuit breakers. Designed to extend compatible Ekip electronic trip units with dedicated frequency-rate protection, the package provides an additional protection function for electrical networks where rapid changes in system frequency must be detected.
ROCOF protection monitors the rate at which electrical system frequency changes and can initiate a trip when the measured frequency variation exceeds the configured threshold for the specified operating time. This functionality is identified by ANSI protection code 81R and is particularly relevant to power systems where rapid frequency disturbances can indicate abnormal network conditions, generation imbalance or loss of mains.
The 1SDA105231R1 package is specifically identified by ABB as ROCOF Protection for Emax 2. For factory-configured applications, the software functionality is specified with the compatible Emax 2 circuit breaker and Ekip trip unit, adding advanced frequency protection without requiring a separate conventional protection relay for the ROCOF function.
ROCOF protection evaluates how quickly system frequency changes rather than responding only to an absolute overfrequency or underfrequency threshold. When the frequency variation exceeds the configured ROCOF threshold for longer than the selected operating time, the protection can issue a trip command through the compatible Ekip protection system.
This functionality can help identify rapidly developing disturbances in generation and distribution networks, including conditions associated with sudden generation-load imbalance or separation from the main electrical network. Integrating ROCOF protection within the ABB Emax 2 and Ekip architecture provides advanced network protection directly through the circuit-breaker protection system.
| Order code | 1SDA105231R1 |
|---|---|
| Product name | ROCOF Protection for Emax 2 |
| Product type | Software protection package |
| Product main type | SW Packages for Emax 2 |
| Protection function | Rate of Change of Frequency (ROCOF) |
| ANSI protection code | 81R |
| ROCOF threshold range | 0.4–10 Hz/s |
| ROCOF threshold adjustment step | 0.2 Hz/s |
| Operating-time range | 0.06–300 s |
| Operating-time adjustment step | 0.01 s |
| Suitable circuit-breaker frames | E1.2, E2.2, E4.2 and E6.2 |
| Suitable product class | SACE Emax 2 |
| Configuration type | Loose or configurable |
| EAN | 8015644073237 |
| Minimum order quantity | 1 piece |
| ABB product group | Emax2 Air Circuit Breaker |
The ABB 1SDA105231R1 is a ROCOF protection software package for compatible ABB SACE Emax 2 circuit breakers and Ekip electronic trip units.
ROCOF protection monitors the rate of change of electrical system frequency and can initiate a trip when the frequency changes faster than the configured threshold for the selected operating time.
ROCOF protection is identified by ANSI device function 81R.
The ROCOF protection threshold can be configured from 0.4–10 Hz/s, with adjustment in 0.2 Hz/s steps.
The ROCOF operating time can be configured from 0.06–300 s, with an adjustment step of 0.01 s.
ABB identifies this ROCOF software package for compatible SACE Emax 2 E1.2, E2.2, E4.2 and E6.2 circuit breakers.
Yes. The ROCOF protection functionality can manage positive and negative rates of frequency change, with its behaviour configured through the compatible Ekip protection system.
ABB SACE Emax 2 protection technologies combine circuit-breaker functionality with advanced electronic protection and monitoring capabilities, supporting reliable power distribution in industrial, commercial, infrastructure and generation applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.