Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA102709R1 is a 400 A three-pole Ekip Dip LS/I solid-state electronic trip unit with adjustable overload and short-circuit protection for compatible SACE Tmax XT5 UL/CSA circuit breakers.
£462.95
The ABB Ekip Dip LS/I In=400 XT5 3p UL/CSA, order code 1SDA102709R1, is a solid-state electronic protection trip unit designed for compatible ABB SACE Tmax XT5 moulded case circuit breakers. Rated at 400 A, this three-pole AC release provides configurable protection for industrial and commercial low-voltage power-distribution systems.
The Ekip Dip LS/I protection architecture provides long-time overload protection together with short-circuit protection that can be configured for short-time or instantaneous operation. This allows the trip unit to protect distribution circuits while supporting appropriate coordination with other protective devices within the electrical installation.
Designed specifically for the ABB SACE Tmax XT5 platform, the 1SDA102709R1 has an adjustable long-time current setting from 160–400 A and a short-circuit setting range extending from 400–4000 A. Its UL/CSA configuration makes it suitable for compatible North American circuit-breaker assemblies and other installations requiring UL/CSA-approved equipment.
Electronic trip units continuously evaluate current flowing through the protected circuit and initiate circuit-breaker operation when configured protection thresholds are exceeded. The ABB Ekip Dip LS/I provides adjustable overload and short-circuit protection, allowing the protection characteristics of a compatible XT5 circuit breaker to be matched more closely to the requirements of the electrical installation.
With a 400 A rated current, adjustable long-time protection from 160–400 A and short-circuit settings extending to 4000 A, the 1SDA102709R1 provides flexible protection for industrial distribution circuits, switchboards and other demanding three-phase power systems.
| Series | SACE Tmax XT |
|---|---|
| ABB order code | 1SDA102709R1 |
| Product type | Solid-state electronic protection trip unit |
| Compatible breaker frame | XT5 |
| Trip unit | Ekip Dip LS/I |
| Rated current (In) | 400 A |
| Long-time current setting range | 160–400 A |
| Short-circuit setting range | 400–4000 A |
| Number of poles | 3 |
| Application | AC circuit protection |
| Configuration | Loose trip unit |
| Compliance | UL / CSA |
| EAN / GTIN | 8056221023979 |
The ABB 1SDA102709R1 is a 400 A Ekip Dip LS/I electronic trip unit designed to provide overload and short-circuit protection when installed with a compatible ABB SACE Tmax XT5 circuit breaker.
The trip unit has a rated current of 400 A.
The Ekip Dip LS/I trip unit provides an adjustable long-time current setting from 160–400 A.
The 1SDA102709R1 provides a short-circuit protection setting range extending from 400–4000 A.
The trip unit is designed for compatible ABB SACE Tmax XT5 moulded case circuit breakers and has a three-pole UL/CSA configuration.
ABB Ekip electronic trip units provide configurable overload and short-circuit protection for SACE Tmax XT circuit breakers, supporting dependable and coordinated protection in demanding low-voltage power-distribution systems.