Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA100825R1 is a 1000 A four-pole Ekip Dip LIG electronic protection trip unit designed for compatible SACE Tmax XT6 moulded-case circuit breakers.
£2,099.20
The ABB Ekip Dip LIG In=1000 XT6 4p is a solid-state electronic protection release designed for compatible SACE Tmax XT6 moulded-case circuit breakers. Identified by ABB order code 1SDA100825R1, this four-pole trip unit has a rated current of 1000 A and is intended for power distribution applications.
The Ekip Dip LIG release provides long-time, instantaneous and ground-fault protection. Its electronic protection functions address sustained overloads, high-level short-circuit faults and ground-fault conditions, providing comprehensive protection for demanding low-voltage distribution systems.
Supplied as a loose or configurable four-pole XT6 electronic release, the 1SDA100825R1 must be combined with a compatible four-pole Tmax XT6 breaking part to form a complete circuit breaker. The release provides adjustable overload protection over 0.4–1 × In and short-circuit protection over 1–10 × In, with time-delay capability for both ranges.
The ABB Ekip Dip LIG release combines three complementary protection functions for compatible Tmax XT6 circuit breakers. Long-time protection responds to sustained overload conditions, instantaneous protection provides rapid intervention during severe short circuits, and ground-fault protection provides additional response to earth-fault conditions.
With a rated current of 1000 A, adjustable overload protection from 0.4–1 × In and short-circuit protection from 1–10 × In, the 1SDA100825R1 supports configurable protection for demanding power distribution systems. As a loose electronic release, it must be combined with an appropriate four-pole XT6 breaking part to create a complete protected circuit-breaker assembly.
| Series | SACE Tmax XT6 |
|---|---|
| ABB order code | 1SDA100825R1 |
| EAN / GTIN | 8056221008792 |
| Product type | Electronic protection trip unit |
| Compatible frame | Tmax XT6 |
| Associated circuit-breaker application | Power distribution |
| Rated current | 1000 A |
| Trip unit | Ekip Dip LIG |
| Release type | Electronic |
| Protection functions | LIG |
| Long-time protection | L |
| Instantaneous protection | I |
| Ground-fault protection | G |
| Overload adjustment range | 0.4–1 × In |
| Short-circuit adjustment range | 1–10 × In |
| Number of poles | 4 |
| Current type | AC |
| Configuration | Loose or configurable |
| Standard | IEC 60947-2 |
| Product net weight | 1.6 kg |
| Installation | For compatible four-pole Tmax XT6 breaking part |
The ABB 1SDA100825R1 is a 1000 A four-pole Ekip Dip LIG electronic trip unit designed for compatible SACE Tmax XT6 moulded-case circuit breakers.
The electronic trip unit has a rated current of 1000 A.
LIG denotes long-time, instantaneous and ground-fault protection, providing electronic protection against overload, severe short-circuit and earth-fault conditions.
The release provides adjustable overload protection over 0.4–1 × In and short-circuit protection over 1–10 × In, with time-delay capability for both ranges.
No. The 1SDA100825R1 is a loose electronic trip unit that must be combined with a compatible four-pole Tmax XT6 breaking part to create a complete protected circuit-breaker assembly.
Yes. The G function of the Ekip Dip LIG release provides ground-fault protection in addition to long-time and instantaneous protection.
ABB Ekip electronic trip units and SACE Tmax XT moulded-case circuit breakers are widely used by panel builders, electrical engineers and industrial operators to provide configurable and dependable protection for demanding low-voltage power distribution systems.
We use cookies