Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA100811R1 is a three-pole Ekip G Dip LS/I electronic generator-protection trip unit rated at 1000 A for compatible Tmax XT6 circuit breakers, providing adjustable long-time overload and short-circuit protection for low-voltage generator applications.
£895.63
The ABB Ekip G Dip LS/I In=1000 XT6 3p 1SDA100811R1 is a three-pole electronic generator-protection trip unit designed for compatible ABB SACE Tmax XT6 moulded case circuit breakers. Rated at 1000 A, it provides adjustable overload and short-circuit protection specifically suited to demanding low-voltage generator and power distribution applications.
The Ekip G Dip LS/I combines long-time overload protection (L) with short-time / instantaneous short-circuit protection (S/I). For this 1000 A version, the long-time current setting covers approximately 400–1000 A, while the short-circuit protection range extends from approximately 1000–10000 A, providing substantial flexibility when coordinating protection with generator characteristics and the wider electrical network.
Designed specifically for the ABB Tmax XT6 three-pole platform, the 1SDA100811R1 is supplied as a separate protection release and is used in combination with a compatible three-pole XT6 breaking part. Its generator-oriented protection characteristics make it suitable for generator incomers, standby generating sets, prime-power systems and other installations where reliable protection must account for generator-specific fault-current behaviour.
Generator-fed electrical systems have different protection requirements from conventional utility-fed networks because generator fault currents can be limited and may decay rapidly following a short circuit. The ABB Ekip G Dip range is designed specifically for generator applications, allowing the circuit breaker protection characteristics to be coordinated with the electrical behaviour of the generating set and downstream distribution network.
For the 1SDA100811R1, the 1000 A rated current is complemented by an approximate long-time setting range of 400–1000 A and short-circuit settings extending from approximately 1000–10000 A. Combined with an appropriate ABB XT6 breaking part, this provides a configurable generator-protection solution for high-current three-phase generating and distribution systems.
| Series | SACE Tmax XT |
|---|---|
| Compatible frame | XT6 |
| ABB order code | 1SDA100811R1 |
| EAN / GTIN | 8056221008655 |
| Product type | Electronic circuit breaker trip unit / protection release |
| Trip-unit technology | Ekip G Dip electronic |
| Protection functions | LS/I |
| Protection application | Generator protection |
| Rated current (In) | 1000 A |
| Number of poles | 3 |
| Long-time protection | L |
| Long-time current setting range | approximately 400–1000 A |
| Short-time / instantaneous protection | S/I |
| Short-circuit current setting range | approximately 1000–10000 A |
| Compatible circuit breaker platform | ABB SACE Tmax XT6 |
| Suitable for circuit breakers | Yes |
| Suitable for switch-disconnectors | No |
| Suitable for motor-protection switches | No |
| Suitable for overload relay applications | Yes |
| Applicable circuit breaker standard | IEC / EN 60947-2 |
| Customs tariff number | 85389099 |
The ABB 1SDA100811R1 is a three-pole Ekip G Dip LS/I electronic generator-protection trip unit rated at 1000 A for use with compatible ABB SACE Tmax XT6 moulded case circuit breaker breaking parts.
The Ekip G Dip is specifically designed for generator protection, providing overload and short-circuit protection for generating sets and associated low-voltage circuits when installed in a compatible ABB Tmax XT6 circuit breaker.
The release provides long-time overload protection (L) together with short-time / instantaneous short-circuit protection (S/I), enabling protection to be coordinated with the characteristics of generator-fed electrical systems.
The 1000 A release provides an approximate long-time current setting range of 400–1000 A and a short-circuit setting range of 1000–10000 A.
No. The 1SDA100811R1 is a separate electronic protection trip unit and must be combined with a compatible three-pole ABB Tmax XT6 breaking part to form a complete generator-protection moulded case circuit breaker.
ABB SACE Tmax XT Ekip G protection units provide dedicated electronic protection for generator applications, combining adjustable overload and short-circuit protection with the modular flexibility of the Tmax XT circuit breaker platform for dependable low-voltage generation systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.