1SDA100716R1 ABB Ekip Dip LIG In=400 XT5 4P Electronic Trip Unit

1SDA100716R1 ABB Ekip Dip LIG In=400 XT5 4P Electronic Trip Unit

ABB 1SDA100716R1 is a 400 A four-pole Ekip Dip LIG solid-state electronic trip unit for SACE Tmax XT5 circuit breakers, providing adjustable overload, short-circuit and ground-fault protection for low-voltage AC applications.

SKU: 1SDA100716R1MPN: 1SDA100716R1
Price
List Price £2,106.78 ex VAT
Your Price (ex VAT) Save 25%
£1,580.09 25% OFF
You save £526.70 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,580.09
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,580.09

Why Choose the ABB Ekip Dip LIG In=400 XT5 4p Trip Unit?

The ABB 1SDA100716R1 is an Ekip Dip LIG solid-state electronic trip unit designed for four-pole ABB SACE Tmax XT5 moulded case circuit breaker assemblies. Rated at 400 A, it provides configurable electronic protection for low-voltage AC power distribution circuits.

The Ekip Dip LIG release combines long-time overload, short-circuit and ground-fault protection within a compact electronic release. Its overload setting can be adjusted from 0.4-1 × In, while short-circuit protection can be adjusted from 1-10 × In, with time-delay capability available in both ranges.

The 1SDA100716R1 is supplied as a four-pole loose electronic protection release and is designed to be combined with a compatible four-pole XT5 breaking part. This modular arrangement allows an ABB SACE Tmax XT5 circuit breaker assembly to be configured with protection characteristics suited to the electrical installation.

Key Advantages

  • Electronic protection designed specifically for ABB SACE Tmax XT5 circuit breakers.
  • 400 A rated current for substantial low-voltage distribution circuits.
  • LIG protection functionality covering overload, short-circuit and ground-fault conditions.
  • Adjustable 0.4-1 × In overload protection.
  • Adjustable 1-10 × In short-circuit protection.
  • Time-delay capability within both adjustable protection ranges.
  • Four-pole configuration for compatible three-phase and neutral distribution systems.
  • Solid-state electronic technology provides accurate and repeatable protection characteristics.

Key Features

  • ABB Ekip Dip LIG electronic trip unit.
  • 400 A rated current (In).
  • Four-pole (4P) configuration.
  • Solid-state electronic release.
  • Designed for AC circuits.
  • Long-time L protection against sustained overload conditions.
  • Short-circuit I protection for high fault-current conditions.
  • Ground-fault G protection for earth-fault conditions.
  • Adjustable overload and short-circuit protection settings.
  • Loose or configurable construction for association with a compatible XT5 breaking part.
  • Designed for the ABB SACE Tmax XT5 moulded case circuit breaker platform.

Configurable LIG Protection for Power Distribution

Low-voltage distribution circuits require dependable protection against sustained overloads, short-circuit currents and earth faults. The ABB Ekip Dip LIG release combines these protection functions within a solid-state electronic trip unit, allowing key operating thresholds to be adjusted to suit the characteristics of the protected circuit.

With its 400 A rating and four-pole configuration, the 1SDA100716R1 is well suited to feeders, switchboards and distribution circuits where electronic ground-fault protection is required alongside conventional overcurrent protection. When combined with a compatible four-pole ABB SACE Tmax XT5 breaking part, it forms part of a flexible moulded case circuit breaker solution for demanding low-voltage installations.

Typical Applications

  • Low-voltage power distribution systems.
  • Industrial distribution switchboards.
  • Commercial electrical distribution panels.
  • Four-pole feeder protection.
  • Main and sub-distribution circuits.
  • Cable and distribution circuit protection.
  • Industrial plant electrical systems.
  • Applications requiring electronic ground-fault protection.

Technical Specifications

Series SACE Tmax XT
Frame size XT5
ABB order code 1SDA100716R1
Product type Solid-state electronic trip unit / protection release
Product main type Accessories for Tmax XT
Release Ekip Dip LIG
Rated current (In) 400 A
Number of poles 4P
Current type AC
Protection functions LIG
Overload adjustment 0.4-1 × In
Overload setting range 160-400 A
Short-circuit adjustment 1-10 × In
Short-circuit setting range 400-4000 A
Time-delay capability Available in both adjustable protection ranges
Configuration type Loose or configurable
Suitable for ABB SACE Tmax XT5
Standard IEC 60947
Product net weight 1.85 kg
Package width 120 mm
Package height 180 mm
Package depth / length 225 mm
Package gross weight 2.014 kg
Minimum order quantity 1 piece
Customs tariff number 85389099
EAN / GTIN 8056221007924

Frequently Asked Questions

What is the ABB 1SDA100716R1 used for?

The ABB 1SDA100716R1 is an Ekip Dip LIG solid-state electronic trip unit designed for use with compatible four-pole ABB SACE Tmax XT5 circuit breaker assemblies in low-voltage AC applications.

What is the rated current of the ABB Ekip Dip 1SDA100716R1?

The electronic trip unit has a rated current of 400 A.

What does LIG mean on the ABB Ekip Dip trip unit?

LIG identifies long-time (L), instantaneous short-circuit (I) and ground-fault (G) protection functions, providing protection against overloads, high fault currents and earth-fault conditions.

What protection adjustment ranges does the ABB 1SDA100716R1 provide?

The release provides overload adjustment from 0.4-1 × In, corresponding to 160-400 A, and short-circuit adjustment from 1-10 × In, corresponding to 400-4000 A, with time-delay capability in both ranges.

Is the ABB 1SDA100716R1 a complete circuit breaker?

No. The 1SDA100716R1 is the electronic protection trip unit. It must be combined with a compatible four-pole ABB SACE Tmax XT5 breaking part to create the required moulded case circuit breaker assembly.