ABB 1SDA100682R1 Ekip Touch Measuring LSI is a 630 A four-pole electronic trip unit for SACE Tmax XT5 circuit breakers combining long-time, short-time and instantaneous protection with integrated electrical measurement capabilities.

SKU: 1SDA100682R1MPN: 1SDA100682R1
Price
List Price £2,437.92 ex VAT
Your Price (ex VAT) Save 25%
£1,828.44 25% OFF
You save £609.48 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,828.44
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,828.44

Why Choose the ABB Ekip Touch Measuring LSI In=630 XT5 4P?

The ABB Ekip Touch Measuring LSI In=630 XT5 4p, order code 1SDA100682R1, is an advanced four-pole solid-state electronic trip unit designed for compatible ABB SACE Tmax XT5 moulded case circuit breaker breaking parts. Rated at 630 A, it combines configurable LSI circuit protection with integrated measuring capabilities for demanding low-voltage AC power distribution systems.

As part of the ABB Ekip Touch Measuring range, this release provides long-time, short-time and instantaneous protection (LSI). Overload protection is adjustable from 0.4–1 × In, while short-circuit protection can be configured from 1–10 × In with time-delay capability, supporting selective protection and coordination throughout complex electrical distribution networks.

The 1SDA100682R1 adds advanced measurement, communication readiness and digitally upgradable functionality to the protection capabilities of the Ekip Touch platform. Its four-pole configuration and 630 A rating make it particularly suitable for high-current switchboards, distribution panels and intelligent power-management installations where both dependable circuit protection and detailed electrical measurement are required.

Key Advantages

  • Advanced LSI electronic protection for ABB SACE Tmax XT5 circuit breakers.
  • 630 A rated current for demanding low-voltage distribution applications.
  • Four-pole configuration for three-phase and neutral electrical systems.
  • Integrated Measuring functionality for enhanced electrical-system monitoring.
  • Adjustable overload protection from 0.4–1 × In.
  • Adjustable short-circuit protection from 1–10 × In with time-delay capability.
  • Prepared for communication and digital functionality upgrades.

Key Features

  • ABB Ekip Touch Measuring LSI electronic protection release.
  • 630 A rated current (In).
  • Four-pole configuration.
  • Long-time (L) overload protection.
  • Short-time (S) short-circuit protection.
  • Instantaneous (I) short-circuit protection.
  • Overload adjustment range: 0.4–1 × In.
  • Short-circuit adjustment range: 1–10 × In.
  • Undelayed short-circuit release setting range: 945–6300 A.
  • Time-delay capability for coordinated overload and short-circuit protection.
  • Integrated electrical measurement functionality.
  • Prepared for communication and digital feature upgrades.
  • Designed for use with compatible ABB SACE Tmax XT5 breaking parts.

Advanced Protection and Measurement for Power Distribution

Modern electrical distribution systems increasingly require detailed operating information alongside dependable circuit protection. The ABB Ekip Touch Measuring platform combines configurable electronic protection with integrated measurement capabilities, allowing electrical conditions to be monitored while maintaining protection against overload and short-circuit faults.

When the 1SDA100682R1 is combined with a compatible four-pole XT5 breaking part, it forms part of an advanced 630 A moulded case circuit-breaker solution. Its adjustable LSI functions, measurement capability and readiness for communication and digital upgrades make it particularly suitable for intelligent switchboards and installations where protection coordination, monitoring and power-management functionality are important.

Typical Applications

  • Intelligent low-voltage switchboards.
  • Three-phase and neutral distribution systems.
  • Main and sub-distribution panels.
  • High-current cable and feeder protection.
  • Manufacturing and process plant power distribution.
  • Commercial and infrastructure electrical distribution.
  • Energy monitoring and power-management systems.
  • OEM switchgear and advanced electrical panel assemblies.

Technical Specifications

Series Ekip Touch Measuring / SACE Tmax XT5
ABB order code 1SDA100682R1
EAN 8056221007580
Product type Solid-state electronic trip unit / protection release
Application Power distribution protection and measurement
Suitable for ABB SACE Tmax XT5
Rated current (In) 630 A
Current type AC
Number of poles 4
Protection functions LSI
Long-time protection L
Short-time protection S
Instantaneous protection I
Overload adjustment range 0.4–1 × In
Short-circuit adjustment range 1–10 × In
Undelayed short-circuit release setting range 945–6300 A
Measurement functionality Integrated
Release Ekip Touch Measuring LSI
Release type EL electronic
Configuration type Loose or configurable
Associated circuit-breaker type Power distribution
Compatible circuit-breaker frame XT5
Product net width 120 mm
Product net height 160 mm
Product net depth 190 mm
Product net weight 1.85 kg
Operating ambient temperature -40 to 125 °C
Customs tariff number 85389099

Frequently Asked Questions

What is the ABB 1SDA100682R1 used for?

The ABB 1SDA100682R1 is an Ekip Touch Measuring LSI electronic trip unit designed for use with compatible four-pole ABB SACE Tmax XT5 breaking parts, providing configurable circuit protection together with integrated electrical measurement functionality.

What is the rated current of the ABB Ekip Touch Measuring LSI 1SDA100682R1?

The electronic trip unit has a rated current of 630 A and is designed in a four-pole configuration for compatible ABB SACE Tmax XT5 circuit breakers.

What does LSI mean on the ABB Ekip Touch Measuring trip unit?

LSI identifies the three principal protection functions: long-time (L) overload, short-time (S) short-circuit and instantaneous (I) short-circuit protection.

What protection adjustment ranges are available?

The overload protection is adjustable from 0.4–1 × In, while short-circuit protection can be adjusted from 1–10 × In. The undelayed short-circuit release setting range extends from 945–6300 A.

What is the difference between Ekip Touch Measuring and a standard Ekip Touch release?

The Ekip Touch Measuring version combines the advanced protection functions of the Ekip Touch platform with integrated electrical measurement capabilities and is prepared for communication and digital functionality upgrades, making it suitable for intelligent power-distribution and monitoring applications.

Advanced ABB Protection and Measurement for Modern Distribution Systems

ABB Ekip Touch Measuring trip units combine configurable electronic circuit protection with advanced measurement capabilities within the SACE Tmax XT platform, supporting intelligent low-voltage distribution systems where dependable protection, monitoring and digital integration are required.