1SDA100651R1 ABB TMA 320-3200 XT5 4-Pole Thermomagnetic Trip Unit

1SDA100651R1 ABB TMA 320-3200 XT5 4-Pole Thermomagnetic Trip Unit

ABB 1SDA100651R1 TMA 320-3200 is a 320 A four-pole thermomagnetic trip unit for Tmax XT5 circuit breakers with a 1600–3200 A magnetic trip range and neutral protection set to 50% of the phase rating.

SKU: 1SDA100651R1MPN: 1SDA100651R1
Price
List Price £662.95 ex VAT
Your Price (ex VAT) Save 25%
£497.21 25% OFF
You save £165.74 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £497.21
Trade pricing is personalised to your account

Manufacturer Lead Time

£497.21

Why Choose the ABB 1SDA100651R1 TMA 320-3200 XT5 4-Pole Trip Unit?

The ABB 1SDA100651R1 is a TMA thermomagnetic trip unit designed for use with ABB Tmax XT5 moulded-case circuit breakers in low-voltage AC and DC power distribution systems. Rated at 320 A, it combines thermal overload protection with magnetic short-circuit protection and is supplied in a four-pole configuration with the neutral pole set to 50% of the phase rating.

As part of the ABB Tmax XT TMA protection range, this release provides dependable circuit protection without requiring an external power supply or electronic trip-unit electronics. The thermal element responds to sustained overload conditions, while the magnetic element provides rapid operation during high-current short circuits, making the unit suitable for industrial and commercial distribution applications.

The TMA 320-3200 XT5 4p InN=50%In is specifically designed for compatible ABB XT5 breaking parts. It has a phase rated current of 320 A, an instantaneous magnetic trip setting range of 1600–3200 A, and a neutral protection level equivalent to 50% of the phase current.

Key Advantages

  • Reliable thermomagnetic protection for ABB Tmax XT5 circuit breakers.
  • 320 A rated current for low-voltage power distribution applications.
  • 1600–3200 A magnetic short-circuit trip range.
  • Four-pole configuration with protected neutral conductor.
  • Neutral protection set to 50% of the phase rating.
  • Suitable for AC and DC applications.

Key Features

  • ABB TMA thermomagnetic release.
  • 320 A phase rated current.
  • Four-pole configuration.
  • Compatible with ABB Tmax XT5 moulded-case circuit breakers.
  • Thermal protection for sustained overload conditions.
  • Magnetic protection for high-current short circuits.
  • Instantaneous trip setting from 1600–3200 A.
  • Neutral current rating of 50% of the phase rating.

Reliable Thermomagnetic Protection for Power Distribution

Thermomagnetic trip units combine two complementary protection principles. The thermal element responds to sustained overcurrents that can overheat cables and equipment, while the magnetic element reacts rapidly to severe short-circuit currents, providing dependable protection without the need for an external power source.

The ABB 1SDA100651R1 is designed to be combined with a compatible XT5 breaking part to create a complete moulded-case circuit breaker assembly. Its four-pole design and reduced neutral setting make it particularly suitable for three-phase systems where neutral conductor protection is required at a lower current threshold than the phase conductors.

Typical Applications

  • Industrial low-voltage distribution switchboards.
  • Main and sub-distribution panels.
  • Commercial building electrical distribution.
  • Manufacturing and process-industry power systems.
  • AC and DC distribution circuits.
  • Four-wire systems requiring neutral conductor protection.

Technical Specifications

Series Tmax XT / TMA
ABB order code 1SDA100651R1
Product type Thermomagnetic circuit-breaker trip unit
Compatible circuit breaker ABB Tmax XT5
Frame size XT5
Rated current 320 A
Number of poles 4
Neutral protection 50% of phase rating
Instantaneous magnetic trip range 1600–3200 A
Protection technology Thermal-magnetic
Current type AC / DC
Product net width 179 mm
Product net height 179 mm
Product net depth 223 mm
Product net weight 1.05 kg
EAN / GTIN 8056221007276
ABB product group T-Max XT 250 Range

Frequently Asked Questions

What is the ABB 1SDA100651R1?

The ABB 1SDA100651R1 is a 320 A four-pole TMA thermomagnetic trip unit designed for use with compatible ABB Tmax XT5 moulded-case circuit breakers.

What is the magnetic trip range of the ABB 1SDA100651R1?

The instantaneous magnetic short-circuit trip setting range is 1600–3200 A.

What does InN=50%In mean?

It means the neutral pole protection is rated at 50% of the phase current, so the neutral protection level is lower than the 320 A phase rating.

Can the ABB 1SDA100651R1 be used on AC and DC systems?

Yes. The TMA 320-3200 XT5 four-pole release is specified for AC and DC applications when used with a compatible ABB Tmax XT5 breaking part.

Which circuit breaker is the 1SDA100651R1 designed for?

The 1SDA100651R1 is designed to be combined with a compatible ABB Tmax XT5 breaking part to form a complete moulded-case circuit breaker assembly.

Trusted Circuit Protection from ABB

ABB Tmax XT circuit breakers and TMA thermomagnetic releases provide robust overload and short-circuit protection for industrial and commercial low-voltage distribution systems, combining dependable mechanical protection technology with the flexible Tmax XT platform.