Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA100629R1 is a 400 A three-pole TMG thermomagnetic trip unit for SACE Tmax XT5 circuit breakers, providing thermal overload and magnetic short-circuit protection for generator applications.
£394.61
The ABB 1SDA100629R1 is a TMG thermomagnetic trip unit designed for generator protection applications with three-pole ABB SACE Tmax XT5 moulded case circuit breakers. With a rated current of 400 A, it combines adjustable thermal overload protection with magnetic short-circuit protection for dependable protection of generators and associated low-voltage electrical circuits.
As part of the ABB SACE Tmax XT5 range, the TMG release provides reliable thermomagnetic protection without requiring an electronic trip unit. The thermal element can be adjusted to suit the protected load, while the magnetic element provides rapid operation under short-circuit conditions, making the release particularly suitable for generator protection and power distribution applications.
The 1SDA100629R1 is a three-pole AC/DC thermomagnetic protection release with a rated current of 400 A. Its TMG 400-2000 designation identifies the 400 A release and its generator-oriented magnetic protection characteristic, and the unit is supplied separately for combination with a compatible three-pole XT5 breaking part.
Generator circuits require dependable protection against sustained overloads and high-current short-circuit faults. The ABB TMG release combines thermal and magnetic protection in a single trip unit, enabling the circuit breaker to respond appropriately to different overcurrent conditions while providing a straightforward protection solution without electronic trip technology.
The adjustable thermal element allows overload protection to be coordinated with the generator and connected electrical system, while the magnetic element provides rapid short-circuit protection. When combined with a compatible three-pole XT5 breaking part, the 1SDA100629R1 provides a practical protection solution for generators, standby power installations and associated low-voltage distribution systems.
| Series | SACE Tmax XT5 |
|---|---|
| ABB order code | 1SDA100629R1 |
| Product type | Thermomagnetic trip unit / protection release |
| Product main type | Accessories for Tmax XT |
| Release | TMG |
| Release type | TM thermomagnetic |
| Rated current (In) | 400 A |
| Number of poles | 3P |
| Current type | AC/DC |
| Protection application | Generator protection |
| Thermal overload adjustment | 0.7–1 × In |
| Thermal overload setting range | 280–400 A |
| Configuration type | Loose or configurable |
| Suitable for | ABB SACE Tmax XT5 |
| Standard | IEC 60947-2 |
| Net weight | 1.35 kg |
| Package dimensions (L × W × H) | 225 × 120 × 180 mm |
| Package gross weight | 1.514 kg |
| Minimum order quantity | 1 piece |
| Customs tariff number | 85389099 |
| EAN / GTIN | 8056221007054 |
The ABB 1SDA100629R1 is a TMG thermomagnetic trip unit designed for use with compatible three-pole ABB SACE Tmax XT5 circuit breaker breaking parts, primarily providing overload and short-circuit protection for generator applications.
The TMG trip unit has a rated current of 400 A.
The TMG release combines thermal overload protection and magnetic short-circuit protection, providing a thermomagnetic protection solution for generator circuits.
The thermal overload protection is adjustable from 0.7–1 × In, corresponding to approximately 280–400 A for the 400 A rated trip unit.
No. The 1SDA100629R1 is a separate thermomagnetic protection trip unit designed to be combined with a compatible three-pole ABB SACE Tmax XT5 breaking part to form the required circuit breaker assembly.
ABB SACE Tmax XT circuit breaker systems are used across generator protection, industrial power distribution and infrastructure applications, providing flexible protection and dependable performance for modern low-voltage electrical installations.