1SDA100339R1 ABB Ekip Dip LIG 40 A XT4 4-Pole Trip Unit

1SDA100339R1 ABB Ekip Dip LIG 40 A XT4 4-Pole Trip Unit

ABB 1SDA100339R1 Ekip Dip LIG 40 A electronic trip unit for compatible 4-pole SACE Tmax XT4 circuit breakers, providing configurable long-time overload, instantaneous short-circuit and earth-fault protection for low-voltage AC power distribution.

SKU: 1SDA100339R1MPN: 1SDA100339R1
Price
List Price £1,481.70 ex VAT
Your Price (ex VAT) Save 25%
£1,111.28 25% OFF
You save £370.43 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,111.28
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,111.28

Why Choose the ABB 1SDA100339R1 Ekip Dip LIG 40 A XT4 4-Pole Trip Unit?

The ABB 1SDA100339R1 is an Ekip Dip LIG electronic trip unit designed for compatible SACE Tmax XT4 moulded-case circuit breakers. Rated at 40 A and configured for 4-pole applications, this solid-state release provides configurable electronic protection for low-voltage AC power distribution systems.

As part of the ABB SACE Tmax XT protection platform, the Ekip Dip LIG release provides LIG protection, comprising long-time overload, instantaneous short-circuit and earth-fault functions. Its electronic architecture enables adjustable overload protection while adding dedicated earth-fault functionality for enhanced protection of feeders, cables and electrical distribution equipment.

The 1SDA100339R1 is specifically designed for XT4 4-pole circuit-breaker configurations and has a rated current of 40 A. It is supplied as a loose or configurable electronic protection release rather than a complete moulded-case circuit breaker, allowing it to be combined with a compatible four-pole XT4 breaking part selected according to the required short-circuit performance.

Key Advantages

  • Genuine ABB Ekip Dip LIG electronic trip unit for SACE Tmax XT4 circuit breakers.
  • 40 A rated current for compatible low-voltage power-distribution applications.
  • LIG protection combines overload, instantaneous short-circuit and earth-fault protection.
  • Designed specifically for compatible 4-pole ABB SACE Tmax XT4 circuit breakers.
  • Long-time overload protection is adjustable over the 0.4–1 × In range.
  • Electronic protection provides accurate and repeatable operation compared with conventional fixed protection.
  • Modular design allows combination with an appropriate four-pole XT4 breaking part.
  • Part of ABB's flexible SACE Tmax XT circuit-breaker ecosystem.

Key Features

  • ABB Ekip Dip LIG electronic trip unit.
  • 40 A rated current (In).
  • Designed for SACE Tmax XT4 circuit breakers.
  • 4-pole configuration.
  • Long-time overload protection (L).
  • Instantaneous short-circuit protection (I).
  • Earth-fault protection (G).
  • Long-time overload adjustment from 0.4–1 × In.
  • Long-time current range of 16–40 A.
  • EL electronic release technology.
  • Designed for AC power distribution.
  • Loose or configurable assembly format.
  • Suitable for compatible four-pole XT4 breaking parts.
  • Designed in accordance with IEC 60947-2.

Configurable LIG Protection for SACE Tmax XT4

The ABB Ekip Dip LIG platform combines three important electronic protection functions within a compact release. Long-time protection responds to sustained overload conditions, instantaneous protection provides rapid interruption during severe short circuits, and the earth-fault function adds protection against ground-fault currents within the electrical distribution system.

For the 40 A 1SDA100339R1, the long-time overload threshold is adjustable from 0.4–1 × In, corresponding to approximately 16–40 A. As a separate four-pole electronic release, it can be paired with an appropriate SACE Tmax XT4 four-pole breaking part, enabling the interruption performance and electronic protection characteristics of the complete circuit breaker to be selected for the application.

Typical Applications

  • ABB SACE Tmax XT4 circuit-breaker assemblies.
  • Industrial low-voltage power distribution.
  • Commercial building electrical distribution.
  • Main and sub-distribution switchboards.
  • Manufacturing and process facilities.
  • Four-pole feeder and cable protection.
  • Power-distribution circuits requiring configurable electronic protection.
  • Applications requiring integrated earth-fault protection.

Technical Specifications

Series SACE Tmax XT / Ekip Dip
Product range T-Max XT 250 Range
Order code 1SDA100339R1
Product type Electronic circuit-breaker trip unit / protection release
ABB product classification Accessory for Tmax XT
Compatible circuit-breaker frame SACE Tmax XT4
Trip-unit rated current (In) 40 A
Number of poles 4
Current type AC
Protection functions L, I and G
Long-time overload protection L
Instantaneous short-circuit protection I
Earth-fault protection G
Long-time adjustment range 0.4–1 × In
Long-time current range 16–40 A
Release type EL electronic release
Configuration type Loose or configurable
Circuit-breaker application Power distribution
Standard IEC 60947-2
Product dimensions (W × H × D) 110 × 100 × 150 mm
Product net weight 1 kg
Package gross weight 1.1 kg
GTIN / EAN 8056221004169
Customs tariff number 85389099

Frequently Asked Questions

What is the ABB 1SDA100339R1?

The ABB 1SDA100339R1 is an Ekip Dip LIG electronic trip unit rated at 40 A for compatible 4-pole SACE Tmax XT4 moulded-case circuit breakers.

What protection functions does the ABB 1SDA100339R1 provide?

The trip unit provides LIG protection: long-time overload protection (L), instantaneous short-circuit protection (I) and earth-fault protection (G).

What is the adjustable overload range of the ABB 1SDA100339R1?

The long-time overload setting is adjustable from 0.4–1 × In, corresponding to approximately 16–40 A for this 40 A Ekip Dip LIG release.

Does the ABB 1SDA100339R1 provide earth-fault protection?

Yes. The G protection function provides electronic earth-fault protection in addition to long-time overload and instantaneous short-circuit protection.

Is the ABB 1SDA100339R1 a complete circuit breaker?

No. The 1SDA100339R1 is a 4-pole electronic trip unit / protection release designed for a compatible SACE Tmax XT4 circuit breaker and must be combined with an appropriate four-pole XT4 breaking part to form a complete circuit-breaker assembly.