ABB 1SDA069609R1 XT4N 160 Ekip E-LSIG is a 160 A four-pole fixed moulded case circuit breaker with front terminals, electronic LSIG protection, integrated energy metering and 36 kA ultimate breaking capacity at 400 V AC.
£1,800.10
The ABB XT4N 160 Ekip E-LSIG, order code 1SDA069609R1, is a 160 A four-pole moulded case circuit breaker (MCCB) from the ABB SACE Tmax XT range. Designed for power-distribution applications, it combines the compact XT4N platform with an advanced Ekip E-LSIG solid-state electronic trip unit for comprehensive protection and electrical measurement.
The Ekip E-LSIG release provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection. The 160 A trip unit offers adjustable protection settings, including an overload current threshold from 0.4–1 × In, allowing the protection characteristics to be coordinated with the connected distribution circuit.
With a 36 kA ultimate short-circuit breaking capacity at 400 V AC, four-pole construction, fixed mounting and front terminals, the 1SDA069609R1 is suited to demanding industrial and commercial distribution systems. The Ekip E-LSIG platform also adds integrated energy metering and advanced electrical measurements, helping combine circuit protection and power monitoring within a single MCCB.
The Ekip E-LSIG electronic release gives the ABB XT4N 160 comprehensive protection against the principal electrical fault conditions encountered in low-voltage distribution systems. Long-time protection responds to sustained overloads, short-time and instantaneous functions protect against short circuits, and the ground-fault function provides additional protection against earth-fault currents. Adjustable thresholds and delays allow the breaker response to be coordinated with the requirements of the installation.
In addition to protection, the Ekip E platform provides integrated energy metering and advanced electrical measurements. Available measurements include parameters such as energy, power, frequency, power factor, peak factor, harmonics and total harmonic distortion, while an internal bus supports compatible HMI connectivity. This combination makes the 1SDA069609R1 particularly useful where both dependable circuit protection and greater visibility of electrical-system performance are required.
| Series | SACE Tmax XT |
|---|---|
| Product group | T-Max XT 250 Range |
| Order code | 1SDA069609R1 |
| EAN | 8015644703455 |
| Product type | Moulded case circuit breaker (MCCB) |
| Application | Power distribution |
| Frame | XT4N 160 |
| Performance level | N |
| Rated current (In) | 160 A |
| Number of poles | 4 |
| Trip unit | Ekip E-LSIG electronic release |
| Protection functions | L, S, I and G |
| Overload current setting (Ir) | 0.4–1 × In |
| Overload setting range | 64–160 A |
| Overload time setting (tr) | 3–60 s |
| Short-time current setting (Isd) | 1–10 × In |
| Short-time delay setting (tsd) | 0.05–0.4 s |
| Instantaneous current setting (Ii) | 1–10 × In |
| Ground-fault current setting (Ig) | 0.2–1 × In |
| Ground-fault delay setting (tg) | 0.1–0.8 s |
| Neutral protection | Off–100% In |
| Ultimate breaking capacity (Icu) at 400 V AC | 36 kA |
| Rated operational voltage | Up to 690 V AC / 500 V DC |
| Mounting | Fixed |
| Terminal arrangement | Front terminals |
| Operation | Manual lever |
| Energy measurement | Integrated |
| Product dimensions (W × H × D) | 140 × 160 × 82.5 mm |
| Product net weight | 3.5 kg |
| Mechanical durability | 25,000 operating cycles |
| Electrical durability | 8,000 operating cycles |
| Minimum order quantity | 1 piece |
| Customs tariff number | 85362090 |
The ABB 1SDA069609R1 is an XT4N 160 four-pole fixed moulded case circuit breaker rated at 160 A, equipped with front terminals and an Ekip E-LSIG electronic trip unit for power-distribution protection and measurement.
The XT4N 160 has an ultimate short-circuit breaking capacity of 36 kA at 400 V AC, making it suitable for industrial and commercial distribution systems with substantial prospective fault currents.
The Ekip E-LSIG provides long-time overload, short-time short-circuit, instantaneous short-circuit and ground-fault protection, identified respectively as L, S, I and G functions.
Yes. The Ekip E-LSIG platform provides integrated energy metering and advanced electrical measurements, including parameters such as power, energy, frequency, power factor and harmonic-related information.
The 1SDA069609R1 is a four-pole fixed MCCB with front terminals, designed for permanent installation within compatible low-voltage switchboards and power-distribution assemblies.
ABB SACE Tmax XT circuit breakers combine dependable low-voltage circuit protection with advanced electronic trip-unit technology, providing adjustable protection, energy measurement and electrical monitoring for industrial, commercial and OEM power-distribution systems.