1SDA067520R1 ABB Ekip LS/I In=100A XT4 4p Electronic Trip Unit

1SDA067520R1 ABB Ekip LS/I In=100A XT4 4p Electronic Trip Unit

ABB 1SDA067520R1 Ekip LS/I In=100A XT4 4p is a 100 A four-pole electronic trip unit providing adjustable overload and short-circuit protection for compatible ABB Tmax XT4 moulded-case circuit breakers.

SKU: 1SDA067520R1MPN: 1SDA067520R1
Price
List Price £736.87 ex VAT
Your Price (ex VAT) Save 25%
£552.65 25% OFF
You save £184.22 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £552.65
Trade pricing is personalised to your account

Manufacturer Lead Time

£552.65

Why Choose the ABB 1SDA067520R1 Ekip LS/I In=100A XT4 4p Trip Unit?

The ABB 1SDA067520R1 is a four-pole Ekip LS/I electronic trip unit designed for use with ABB SACE Tmax XT4 moulded-case circuit breakers in low-voltage power distribution applications. Rated at 100 A, it provides configurable electronic protection against overload and short-circuit conditions.

As part of the advanced ABB SACE Tmax XT circuit breaker system, the Ekip LS/I release combines long-time overload protection with selectable short-circuit protection functions. Its microprocessor-based electronic design enables accurate protection settings and supports effective coordination within industrial and commercial electrical distribution systems.

The 1SDA067520R1 has a four-pole configuration and a rated current of 100 A. Its long-time overload protection is adjustable over a 40–100 A range, while short-circuit protection can be set over a 100–1000 A range, providing flexibility when configuring a compatible ABB Tmax XT4 circuit breaker.

Key Advantages

  • Advanced electronic LS/I protection for power distribution circuits.
  • 100 A rated current for compatible ABB Tmax XT4 circuit breakers.
  • Four-pole configuration for four-pole AC distribution systems.
  • Adjustable 40–100 A long-time overload protection range.
  • Adjustable 100–1000 A short-circuit protection range.
  • Microprocessor-based protection provides accurate and configurable circuit protection.
  • Designed specifically for integration with the ABB SACE Tmax XT4 platform.

Key Features

  • ABB Ekip LS/I electronic trip unit.
  • 100 A rated current (In).
  • 40–100 A adjustable long-time protection range.
  • 100–1000 A adjustable short-circuit protection range.
  • Four-pole construction.
  • Designed for AC applications.
  • Microprocessor-based electronic protection.
  • Long-time overload protection.
  • Short-circuit protection with configurable operating characteristics.
  • Loose electronic trip unit for combination with a compatible XT4 breaking part.
  • Designed for ABB Tmax XT4 moulded-case circuit breakers.

Reliable Electronic Protection for Power Distribution

Electronic trip units such as the ABB Ekip LS/I provide configurable protection by monitoring current and initiating circuit breaker operation when defined overload or short-circuit conditions occur. Adjustable long-time protection helps protect conductors and equipment against sustained overcurrents, while the short-circuit protection functions provide rapid response to higher fault currents.

The Ekip LS/I platform is designed for integration with ABB Tmax XT circuit breakers. Its adjustable protection settings allow electrical engineers to coordinate the trip unit with downstream equipment and installation requirements, providing flexible and dependable protection for modern industrial and commercial power distribution systems.

Typical Applications

  • Low-voltage electrical distribution panels.
  • Industrial power distribution systems.
  • Commercial electrical installations.
  • Four-pole AC distribution circuits.
  • Machine and equipment distribution boards.
  • Industrial control panel power circuits.
  • ABB Tmax XT4 moulded-case circuit breaker installations.

Technical Specifications

Series SACE Tmax XT
Product group T-Max XT 250 Range
Order code 1SDA067520R1
Product type Electronic circuit breaker trip unit
Release Ekip LS/I
Release type Microprocessor-based electronic release
Rated current (In) 100 A
Long-time overload setting range 40–100 A
Short-circuit setting range 100–1000 A
Number of poles 4
Current type AC
Circuit breaker application Power distribution
Suitable for ABB Tmax XT4
Protection functions Long-time overload and short-circuit protection (LS/I)
Reference standard IEC 60947-2
Product net weight 1 kg
Packaging dimensions (L × W × H) 150 × 110 × 100 mm
GTIN / EAN 8015644014162
Customs tariff number 85389099
Country of production Italy

Frequently Asked Questions

What is the ABB 1SDA067520R1 used for?

The ABB 1SDA067520R1 is an Ekip LS/I electronic trip unit designed for compatible ABB Tmax XT4 moulded-case circuit breakers, providing configurable overload and short-circuit protection in AC power distribution applications.

What is the rated current of the ABB Ekip LS/I 1SDA067520R1?

The trip unit has a rated current of 100 A, with adjustable long-time overload protection over a 40–100 A range.

What short-circuit protection range does the Ekip LS/I provide?

The short-circuit protection can be adjusted over a 100–1000 A range, allowing the protection characteristics to be coordinated with the electrical installation.

How many poles does the ABB 1SDA067520R1 have?

The 1SDA067520R1 has a four-pole configuration and is designed for compatible AC power distribution applications.

Which circuit breaker is the 1SDA067520R1 designed for?

The trip unit is designed for use with a compatible ABB SACE Tmax XT4 moulded-case circuit breaker breaking part.

Trusted Protection from ABB

ABB SACE Tmax XT circuit breaker systems and Ekip electronic trip units provide configurable and dependable protection for industrial and commercial low-voltage power distribution installations.