Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA067482R1 is a 160 A four-pole TMA thermomagnetic trip unit for compatible Tmax XT4 circuit breakers, featuring an adjustable 800–1600 A instantaneous short-circuit release and a fully rated 100% neutral.
£458.39
The ABB TMA 160-1600 XT4 4p InN=100% is a thermomagnetic protection trip unit designed for compatible ABB Tmax XT4 moulded-case circuit breakers. Identified by ABB order code 1SDA067482R1, it combines thermal overload protection with adjustable instantaneous magnetic short-circuit protection for low-voltage power distribution applications.
This TMA release has a rated current of 160 A and is designed for 4-pole Tmax XT4 configurations. Its undelayed short-circuit release is adjustable from 800–1600 A, enabling the instantaneous magnetic protection threshold to be selected within the specified range for the protected circuit.
The InN=100% configuration provides a fully rated neutral, making the 1SDA067482R1 particularly suitable for four-pole distribution systems where the neutral requires protection at the same rated current as the phase conductors. The release is suitable for compatible AC and DC Tmax XT4 circuit-breaker applications.
Thermomagnetic releases combine two complementary protection functions. The thermal element responds to sustained overload currents that could cause excessive heating, while the magnetic element provides rapid operation under high short-circuit current conditions. This combination provides straightforward circuit protection without requiring an electronic trip unit.
The ABB TMA 160-1600 XT4 4p InN=100% combines a 160 A rated current with an adjustable 800–1600 A instantaneous short-circuit release range. Its four-pole configuration and fully rated neutral make it particularly useful for compatible low-voltage distribution systems where protection of the neutral conductor is required at 100% of phase rated current.
| Series | Tmax XT |
|---|---|
| Product group | T-Max XT 250 Range |
| ABB order code | 1SDA067482R1 |
| GTIN / EAN | 8015644695323 |
| Product type | Thermomagnetic circuit-breaker trip unit |
| Release | TMA |
| Compatible frame | Tmax XT4 |
| Rated current | 160 A |
| Instantaneous short-circuit adjustment range | 800–1600 A |
| Number of poles | 4 |
| Neutral protection | InN=100% |
| Neutral rating | Fully rated neutral |
| Current type | AC / DC |
| Protection technology | Thermomagnetic |
| Net weight | 1.00 kg |
| Country of origin | Italy |
The ABB 1SDA067482R1 is a TMA 160-1600 thermomagnetic trip unit designed for compatible four-pole ABB Tmax XT4 moulded-case circuit-breaker assemblies.
The trip unit has a rated current of 160 A.
The undelayed magnetic short-circuit release is adjustable from 800–1600 A.
InN=100% identifies a fully rated neutral configuration, providing neutral protection at 100% of the phase rated current.
The 1SDA067482R1 is designed for a 4-pole Tmax XT4 circuit-breaker configuration.
Yes. The TMA 160-1600 XT4 4p release is suitable for compatible AC and DC circuit-breaker applications.
The TMA release combines thermal overload protection with adjustable instantaneous magnetic short-circuit protection.
No. The 1SDA067482R1 is a thermomagnetic protection trip unit designed for integration with compatible ABB Tmax XT4 circuit-breaker components.
ABB Tmax XT circuit-protection components are widely specified by panel builders, electrical engineers and industrial operators for dependable overload and short-circuit protection in low-voltage power distribution systems.