Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA067362R1 is a 25 A three-pole Ekip G-LS/I microprocessor electronic trip unit for ABB SACE Tmax XT2 circuit breakers with adjustable overload and short-circuit protection for generator applications.
£327.26
The ABB 1SDA067362R1 is an Ekip G-LS/I three-pole electronic trip unit designed for ABB SACE Tmax XT2 moulded-case circuit breakers. Rated at 25 A, it provides electronic overload and short-circuit protection specifically suited to generator protection and low-voltage AC distribution applications.
The Ekip G-LS/I release provides long-time overload protection (L) together with short-time and instantaneous short-circuit protection (S/I). The overload setting is adjustable across 0.4–1 × In, corresponding to approximately 10–25 A for this 25 A version, while the short-circuit protection range extends across 1–10 × In.
Designed specifically for the ABB SACE Tmax XT2 platform, the 1SDA067362R1 uses microprocessor-based solid-state protection technology. Its protection characteristics are particularly useful for generator applications, where adjustable overload and short-circuit settings can help coordinate the circuit breaker with the operating characteristics of the generating set.
Generator protection requires circuit-breaker characteristics that can accommodate the electrical behaviour and fault-current capability of generating sets. The ABB Ekip G-LS/I release provides adjustable long-time overload and short-circuit protection, allowing the protection settings to be coordinated with the generator and downstream electrical system.
For the 25 A 1SDA067362R1, the overload protection can be adjusted across 0.4–1 × In, corresponding to approximately 10–25 A, while the short-circuit protection range extends across 1–10 × In. This flexibility makes the release particularly suitable for compatible Tmax XT2 generator protection assemblies.
| Series | SACE Tmax XT |
|---|---|
| Order code | 1SDA067362R1 |
| Product type | Electronic circuit-breaker trip unit |
| Release type | Ekip G-LS/I |
| Release technology | Microprocessor / solid-state electronic |
| Suitable for | Tmax XT2 |
| Primary application | Generator protection |
| Rated current (In) | 25 A |
| Overload adjustment range | 0.4–1 × In |
| Overload current range | 10–25 A |
| Short-circuit protection range | 1–10 × In |
| Protection functions | L, S/I |
| Current type | AC |
| Number of poles | 3P |
| Product net weight | 1 kg |
| Package dimensions (L × W × H) | 150 × 110 × 100 mm |
| EAN | 8015644012595 |
| Minimum order quantity | 1 piece |
| Product group | T-Max XT 250 Range |
The ABB 1SDA067362R1 is a 25 A three-pole Ekip G-LS/I electronic trip unit designed for compatible ABB Tmax XT2 moulded-case circuit breakers and is particularly suited to generator protection applications.
The ABB Ekip G-LS/I 1SDA067362R1 has a rated current of 25 A.
The Ekip G-LS/I provides long-time overload protection (L) together with short-time and instantaneous short-circuit protection (S/I), with adjustable settings suited to generator protection applications.
The overload protection is adjustable across 0.4–1 × In. With a rated current of 25 A, this corresponds to an adjustment range of approximately 10–25 A.
The 1SDA067362R1 is designed for compatible ABB SACE Tmax XT2 moulded-case circuit-breaker breaking parts and is configured as a three-pole AC electronic release.
ABB SACE Tmax XT Ekip G electronic trip units provide adjustable electronic protection for compatible generator circuit-breaker assemblies, supporting coordinated overload and short-circuit protection in professional standby, generation and power distribution systems.
We use cookies