1SDA067350R1 ABB Ekip LSIG In=160A XT2 4p InN=100% Electronic Trip Unit

1SDA067350R1 ABB Ekip LSIG In=160A XT2 4p InN=100% Electronic Trip Unit

ABB 1SDA067350R1 is a four-pole Ekip LSIG electronic trip unit for SACE Tmax XT2 circuit breakers with a 160 A rated current, long-time, short-time, instantaneous and ground-fault protection, and a 100% rated neutral.

SKU: 1SDA067350R1MPN: 1SDA067350R1
Price
List Price £1,577.25 ex VAT
Your Price (ex VAT) Save 25%
£1,182.94 25% OFF
You save £394.31 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,182.94
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,182.94

Why Choose the ABB 1SDA067350R1 Ekip LSIG Trip Unit?

The ABB 1SDA067350R1 is a four-pole Ekip LSIG electronic trip unit designed for ABB SACE Tmax XT2 moulded-case circuit breakers. Part of the ABB Tmax XT protection range, it provides comprehensive electronic protection for low-voltage power distribution circuits.

This Ekip release has a 160 A rated current and combines long-time (L), short-time (S), instantaneous (I) and ground-fault (G) protection functions. The LSIG protection package supports selective circuit protection and coordination across a wide range of industrial and commercial distribution applications.

Designed specifically for the four-pole Tmax XT2 frame, the 1SDA067350R1 features InN = 100%, providing a neutral current rating equal to the phase rated current. This makes it particularly suitable for four-wire distribution systems where comprehensive phase, neutral and ground-fault protection is required.

Key Advantages

  • Genuine ABB SACE Tmax XT2 Ekip electronic trip unit.
  • 160 A rated current for low-voltage distribution applications.
  • Comprehensive LSIG protection functions.
  • Long-time protection against sustained overload conditions.
  • Short-time and instantaneous protection against short-circuit faults.
  • Integrated ground-fault protection.
  • 100% rated neutral (InN = 100%) for four-wire systems.

Key Features

  • ABB SACE Tmax XT protection range.
  • Ekip LSIG electronic release.
  • 160 A rated current.
  • L – Long-time overload protection.
  • S – Short-time short-circuit protection.
  • I – Instantaneous short-circuit protection.
  • G – Ground-fault protection.
  • Four-pole configuration with InN = 100%.

Comprehensive LSIG Protection for Tmax XT2

LSIG protection combines four essential circuit-protection functions within one electronic trip unit. Long-time protection responds to sustained overloads, short-time protection supports selective response to short-circuit conditions, instantaneous protection provides rapid interruption of severe faults, and ground-fault protection detects potentially damaging earth-fault currents.

The ABB 1SDA067350R1 combines these functions with a 160 A rating, four-pole configuration and 100% rated neutral. It is therefore well suited to compatible Tmax XT2 distribution systems requiring comprehensive electronic protection and full-current neutral capability.

Typical Applications

  • ABB SACE Tmax XT2 moulded-case circuit breaker assemblies.
  • Industrial low-voltage distribution systems.
  • Commercial switchboards and distribution panels.
  • Four-wire electrical distribution circuits.
  • Systems requiring ground-fault protection.
  • Installations requiring 100% neutral current capability.

Technical Specifications

Series SACE Tmax XT
ABB order code 1SDA067350R1
Product group T-Max XT 250 Range
Product type Electronic trip unit
Trip unit Ekip LSIG
Suitable breaker Tmax XT2
Rated current 160 A
Protection functions L, S, I, G
Long-time protection L
Short-time protection S
Instantaneous protection I
Ground-fault protection G
Number of poles 4
Neutral setting InN = 100%
Neutral rated current 160 A
Release technology Electronic

Frequently Asked Questions

What is the ABB 1SDA067350R1?

It is a four-pole Ekip LSIG electronic trip unit rated at 160 A for compatible ABB SACE Tmax XT2 circuit breakers.

What protection functions does the Ekip LSIG provide?

LSIG provides long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection.

What is the rated current of the ABB 1SDA067350R1?

The trip unit has a rated current of 160 A.

What does InN = 100% mean?

InN = 100% means the neutral is rated at 100% of the phase rated current, giving this trip unit a 160 A neutral current rating.

Which circuit breaker is the ABB 1SDA067350R1 designed for?

It is designed for compatible four-pole ABB SACE Tmax XT2 moulded-case circuit breaker assemblies.

Trusted ABB Electronic Circuit Protection