Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA067326R1 is a three-pole Ekip M-I electronic trip unit for SACE Tmax XT2 circuit breakers with a 52 A rated current and adjustable 312–728 A instantaneous short-circuit protection for AC motor applications.
£479.75
The ABB 1SDA067326R1 is a three-pole Ekip M-I electronic trip unit designed for ABB SACE Tmax XT2 moulded-case circuit breakers. As part of the ABB Tmax XT motor protection range, this solid-state release provides instantaneous short-circuit protection for AC motor circuits.
The Ekip M-I release has a 52 A rated current and an adjustable instantaneous short-circuit protection range of 312–728 A. This corresponds to approximately 6–14 × In, providing the high instantaneous protection range required for motor circuits while accommodating normal motor starting currents.
Designed specifically for the three-pole Tmax XT2 frame, the 1SDA067326R1 is a loose or configurable electronic release for integration with a compatible XT2 circuit breaker assembly. Its motor-protection configuration makes it suitable for industrial machinery, motor feeders and other installations where dedicated short-circuit protection is required alongside separate overload protection.
Motor circuits can experience high starting currents that require protection characteristics different from those used for conventional distribution loads. The ABB Ekip M-I release provides adjustable instantaneous short-circuit protection designed to distinguish normal motor starting conditions from damaging high-current faults.
With its 52 A rated current and 312–728 A instantaneous setting range, the ABB 1SDA067326R1 provides dedicated short-circuit protection for compatible XT2 motor-protection assemblies. Overload protection can be coordinated separately as part of the complete motor protection system.
| Series | SACE Tmax XT |
|---|---|
| Model / order code | 1SDA067326R1 |
| Product type | Electronic trip unit |
| Trip unit | Ekip M-I |
| Suitable breaker | Tmax XT2 |
| Rated current | 52 A |
| Protection function | Instantaneous short-circuit protection |
| Instantaneous adjustment range | 312–728 A |
| Number of poles | 3 |
| Release type | Electronic / solid-state |
| Current type | AC |
| Circuit breaker application | Motor protection |
| Configuration | Loose / configurable |
| Standard | IEC 60947-2 |
| Package dimensions (W × H × D) | 110 × 100 × 150 mm |
| Net weight | 1 kg |
| EAN | 8015644012236 |
It is a three-pole Ekip M-I electronic trip unit for ABB SACE Tmax XT2 circuit breakers, designed to provide instantaneous short-circuit protection for AC motor circuits.
The ABB 1SDA067326R1 has a 52 A rated current.
The instantaneous short-circuit protection is adjustable from 312–728 A, corresponding to approximately 6–14 times the 52 A rated current.
It is designed for compatible three-pole ABB SACE Tmax XT2 moulded-case circuit breaker assemblies.
Yes. The Ekip M-I release is intended for motor protection and provides adjustable instantaneous short-circuit protection for compatible AC motor circuits.
ABB SACE Tmax XT Ekip M electronic releases provide dedicated protection characteristics for motor applications, helping protect industrial motor circuits against damaging short-circuit currents while accommodating normal motor starting conditions.
We use cookies