1SDA067257R1 ABB TMA 160-1600 XT2 4P InN=50% Thermomagnetic Trip Unit 160 A

1SDA067257R1 ABB TMA 160-1600 XT2 4P InN=50% Thermomagnetic Trip Unit 160 A

ABB 1SDA067257R1 TMA 160-1600 is a 160 A four-pole AC/DC thermomagnetic trip unit for Tmax XT2 circuit breakers with 112–160 A thermal adjustment, 800–1600 A instantaneous magnetic protection and InN=50% neutral protection.

SKU: 1SDA067257R1MPN: 1SDA067257R1
Price
List Price £293.36 ex VAT
Your Price (ex VAT) Save 25%
£220.02 25% OFF
You save £73.34 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £220.02
Trade pricing is personalised to your account

Manufacturer Lead Time

£220.02

Why Choose the ABB 1SDA067257R1 TMA 160-1600 Thermomagnetic Trip Unit?

The ABB 1SDA067257R1 is a TMA 160-1600 four-pole thermomagnetic trip unit designed for ABB SACE Tmax XT2 moulded-case circuit breakers. Rated at 160 A, it provides adjustable thermal overload protection together with instantaneous magnetic protection for low-voltage power distribution applications.

The TMA release combines thermal and magnetic protection in an electromechanical design suitable for AC/DC applications. Its thermal setting can be adjusted from 112–160 A, while the instantaneous magnetic short-circuit setting is adjustable from 800–1600 A, allowing protection to be matched to the characteristics of the connected circuit.

The 1SDA067257R1 is specifically configured for 4-pole ABB Tmax XT2 applications with the neutral protection set at 50% of the phase setting (InN=50%). It is supplied as a protection trip unit for combination with a compatible XT2 breaking part to form a complete moulded-case circuit breaker.

Key Advantages

  • Genuine ABB TMA thermomagnetic trip unit for Tmax XT2.
  • 160 A rated current for power distribution applications.
  • Adjustable thermal setting from 112–160 A.
  • Adjustable instantaneous magnetic protection from 800–1600 A.
  • 4-pole configuration with neutral protection at 50% of the phase setting.
  • Suitable for AC and DC circuit protection applications.

Key Features

  • ABB SACE Tmax XT thermomagnetic protection technology.
  • TMA 160-1600 trip-unit configuration.
  • 160 A nominal current.
  • 112–160 A thermal adjustment range.
  • 800–1600 A instantaneous magnetic trip range.
  • 5–10 × In magnetic setting range.
  • 4-pole configuration.
  • InN=50% neutral protection configuration.
  • Suitable for AC/DC applications.
  • Designed for ABB Tmax XT2 moulded-case circuit breakers.
  • ABB order code 1SDA067257R1.
  • GTIN / EAN 8015644011598.

Adjustable Thermomagnetic Protection with 50% Neutral Protection

Thermomagnetic trip units combine two complementary protection functions. The thermal element responds to sustained overload currents, while the magnetic element provides rapid operation during high short-circuit currents. On the ABB TMA 160-1600, the thermal setting is adjustable from 112–160 A and the instantaneous magnetic setting from 800–1600 A.

This version is designed specifically for four-pole systems with InN=50%. The neutral pole is therefore protected at 50% of the phase setting, making the 1SDA067257R1 suitable for compatible distribution applications where this neutral protection characteristic is required.

Typical Applications

  • ABB Tmax XT2 four-pole moulded-case circuit-breaker assemblies.
  • Industrial low-voltage power distribution systems.
  • Commercial electrical distribution boards.
  • Switchboards and electrical control panels.
  • Feeder and cable overload protection.
  • AC and DC power distribution applications.
  • Four-pole circuits requiring 50% neutral protection.

Technical Specifications

Series SACE Tmax XT
Order code 1SDA067257R1
Product type Thermomagnetic trip unit
Release type TMA thermomagnetic
Suitable for Tmax XT2
Application Power distribution
Rated current (In) 160 A
Thermal setting range 112–160 A
Thermal setting 0.7–1 × In
Instantaneous magnetic trip (I3) 800–1600 A
Magnetic setting range 5–10 × In
Current type AC/DC
Number of poles 4P
Neutral protection InN=50% of phase setting
Product net weight 1 kg
Package dimensions (L × W × H) 95 × 145 × 75 mm
GTIN / EAN 8015644011598
Minimum order quantity 1 piece
Product group T-Max XT 250 Range

Frequently Asked Questions

What is the ABB 1SDA067257R1 used for?

The ABB 1SDA067257R1 is a four-pole TMA thermomagnetic trip unit designed for compatible ABB Tmax XT2 moulded-case circuit breakers, providing adjustable overload and instantaneous short-circuit protection.

What is the rated current and thermal setting range of the ABB 1SDA067257R1?

The trip unit has a rated current of 160 A, with its thermal protection adjustable from 112–160 A, corresponding to 0.7–1 times the rated current.

What is the magnetic trip range of the TMA 160-1600?

The instantaneous magnetic short-circuit protection is adjustable from 800–1600 A, corresponding to 5–10 times the 160 A rated current.

What does InN=50% mean on the ABB 1SDA067257R1?

InN=50% indicates that the neutral pole protection is set at 50% of the phase setting. This distinguishes the 1SDA067257R1 from the corresponding XT2 four-pole TMA version with 100% neutral protection.

Which circuit breaker is the ABB 1SDA067257R1 designed for?

The 1SDA067257R1 is designed for compatible ABB SACE Tmax XT2 moulded-case circuit-breaker breaking parts and is configured for four-pole AC/DC applications.

Trusted ABB Circuit Protection

ABB SACE Tmax XT thermomagnetic trip units provide dedicated overload and short-circuit protection for compatible low-voltage circuit-breaker assemblies, with adjustable protection characteristics for professional power distribution applications.