1SDA067254R1 ABB TMA 80-800 XT2 4p Thermomagnetic Trip Unit

1SDA067254R1 ABB TMA 80-800 XT2 4p Thermomagnetic Trip Unit

ABB 1SDA067254R1 is a four-pole TMA thermomagnetic trip unit for SACE Tmax XT2 circuit breakers with an 80 A rated current and adjustable 400–800 A magnetic short-circuit protection.

SKU: 1SDA067254R1MPN: 1SDA067254R1
Price
List Price £281.75 ex VAT
Your Price (ex VAT) Save 25%
£211.31 25% OFF
You save £70.44 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £211.31
Trade pricing is personalised to your account

Manufacturer Lead Time

£211.31

Why Choose the ABB 1SDA067254R1 TMA Trip Unit?

The ABB 1SDA067254R1 is a four-pole TMA thermomagnetic trip unit designed for ABB SACE Tmax XT2 moulded-case circuit breakers. As part of the ABB Tmax XT protection range, it combines adjustable thermal overload protection with adjustable magnetic short-circuit protection for dependable AC and DC electrical distribution applications.

This TMA release has a 80 A rated current and an adjustable instantaneous magnetic protection range of 400–800 A. The thermal protection can be adjusted over the range 0.7–1 × In, while the magnetic short-circuit setting is adjustable from 5–10 × In, allowing protection to be coordinated with the requirements of the connected circuit.

Designed specifically for the four-pole Tmax XT2 frame, the 1SDA067254R1 is a loose thermomagnetic release intended to be combined with a compatible four-pole XT2 breaking unit. Its robust protection characteristics make it suitable for industrial switchboards, distribution panels and machinery power systems requiring reliable overload and short-circuit protection.

Key Advantages

  • Genuine ABB SACE Tmax XT2 thermomagnetic trip unit.
  • 80 A rated current for low-voltage distribution protection.
  • Adjustable 400–800 A magnetic short-circuit protection.
  • Adjustable 0.7–1 × In thermal overload protection.
  • Combines thermal and magnetic protection in one release.
  • Designed for four-pole ABB SACE Tmax XT2 circuit breakers.
  • Suitable for AC and DC power distribution applications.

Key Features

  • ABB SACE Tmax XT protection range.
  • TMA thermomagnetic release.
  • 80 A nominal current.
  • 400–800 A adjustable instantaneous magnetic protection.
  • 0.7–1 × In adjustable thermal setting.
  • 5–10 × In adjustable magnetic setting.
  • Four-pole configuration.
  • Compatible with the ABB Tmax XT2 frame.

Reliable Protection for Tmax XT2 Circuit Breakers

Thermomagnetic trip units protect electrical circuits using complementary thermal and magnetic operating principles. The thermal element responds to sustained overload conditions, while the magnetic element provides rapid tripping when short-circuit current reaches the selected instantaneous protection threshold.

The ABB 1SDA067254R1 provides adjustable thermal and magnetic settings, allowing the protection characteristics to be coordinated with the connected load and conductors. Engineered specifically for the Tmax XT2 platform, it provides a dependable protection solution for compatible four-pole circuit breaker assemblies.

Typical Applications

  • ABB Tmax XT2 moulded-case circuit breaker assemblies.
  • Industrial low-voltage distribution systems.
  • Four-pole electrical distribution circuits.
  • Switchboards and distribution panels.
  • Machine and equipment feeder protection.
  • AC and DC overload and short-circuit protection.

Technical Specifications

Series SACE Tmax XT
Model / order code 1SDA067254R1
Product type Thermomagnetic trip unit
Trip unit TMA
Suitable breaker Tmax XT2
Rated current 80 A
Thermal adjustment 0.7–1 × In
Magnetic adjustment 5–10 × In
Magnetic protection range 400–800 A
Number of poles 4
Current type AC / DC
Configuration Loose / configurable trip unit
Standard IEC 60947-2
EAN 8015644011567

Frequently Asked Questions

What is the ABB 1SDA067254R1 used for?

It is a TMA thermomagnetic trip unit for four-pole ABB SACE Tmax XT2 circuit breakers, providing adjustable overload and short-circuit protection.

What is the rated current of this trip unit?

The ABB 1SDA067254R1 has a 80 A rated current.

What is the magnetic protection range?

The TMA release provides adjustable instantaneous magnetic protection from 400–800 A, corresponding to 5–10 × In.

Can the thermal protection be adjusted?

Yes. The thermal protection is adjustable over a range of 0.7–1 × In, allowing the overload setting to be coordinated with the protected circuit.

Which circuit breaker is the ABB 1SDA067254R1 designed for?

It is specifically designed for compatible four-pole ABB SACE Tmax XT2 moulded-case circuit breaker assemblies.

Trusted ABB Circuit Protection

ABB SACE Tmax XT thermomagnetic releases provide dependable overload and short-circuit protection for low-voltage distribution systems, with adjustable protection settings and trip units engineered specifically for compatible Tmax XT circuit breaker frames.