ABB 1SDA067248R1 is a four-pole TMD thermomagnetic trip unit with a 20 A rated current, adjustable 0.7–1 × In thermal protection and fixed 300 A magnetic short-circuit protection for compatible ABB SACE Tmax XT2 moulded case circuit breakers.
£211.31
The ABB 1SDA067248R1 is a genuine four-pole TMD thermomagnetic trip unit designed for ABB SACE Tmax XT2 moulded case circuit breakers. Identified as TMD 20-300 XT2 4p, it combines thermal overload protection with magnetic short-circuit protection for compatible XT2 circuit breaker assemblies.
The trip unit has a rated current of 20 A and a fixed 300 A magnetic short-circuit protection setting. Its thermal protection is adjustable over a range of 0.7–1 × In, allowing the overload protection level to be matched to the requirements of the protected circuit.
Designed for four-pole AC/DC applications, the 1SDA067248R1 is supplied as a separate protection unit for combination with a compatible four-pole Tmax XT2 switching unit. It provides a coordinated ABB solution for overload and short-circuit protection in industrial, commercial and infrastructure low-voltage distribution systems.
A thermomagnetic trip unit combines two complementary protection principles. The thermal element responds to sustained overcurrent conditions and provides overload protection, while the magnetic element responds rapidly to high fault currents to provide short-circuit protection. On the ABB 1SDA067248R1, the thermal setting is adjustable from 0.7–1 × In, while magnetic short-circuit protection is fixed at 300 A.
The ABB 1SDA067248R1 is specifically configured for the Tmax XT2 four-pole platform with a rated current of 20 A. It is a separate trip unit intended to be combined with a compatible four-pole ABB Tmax XT2 switching unit to create the required moulded case circuit breaker protection assembly.
| Series | SACE Tmax XT |
|---|---|
| Product group | T-Max XT 250 Range |
| Order code | 1SDA067248R1 |
| EAN / GTIN | 8015644011505 |
| Product type | Thermomagnetic trip unit / release |
| Trip unit type | TMD |
| Compatible breaker frame | Tmax XT2 |
| Number of poles | 4 |
| Rated current | 20 A |
| Thermal protection adjustment | 0.7–1 × In |
| Magnetic short-circuit protection | Fixed at 300 A |
| Protection functions | Thermal overload and magnetic short-circuit protection |
| Application | AC/DC |
| Standard | IEC 60947-2 |
| Product net width | 145 mm |
| Product net height | 75 mm |
| Product net depth | 95 mm |
| Product net weight | 1 kg |
| Minimum order quantity | 1 piece |
| Customs tariff number | 85389099 |
| Country of origin | Italy |
The ABB 1SDA067248R1 is a four-pole TMD thermomagnetic trip unit with a rated current of 20 A, designed for combination with a compatible ABB SACE Tmax XT2 switching unit.
The TMD trip unit provides thermal overload protection and magnetic short-circuit protection. Its thermal setting is adjustable from 0.7–1 × In, while its magnetic short-circuit protection is fixed at 300 A.
The ABB 1SDA067248R1 has a rated current of 20 A.
The 300 denotes the 300 A fixed magnetic short-circuit protection setting of this TMD thermomagnetic release.
No. The 1SDA067248R1 is the TMD thermomagnetic trip unit and must be combined with a compatible four-pole ABB Tmax XT2 switching unit to form the required circuit breaker assembly.
ABB SACE Tmax XT trip units provide coordinated overload and short-circuit protection for compatible moulded case circuit breaker assemblies, supporting reliable low-voltage power distribution in industrial and commercial installations.