ABB 1SDA067236R1 TMA 160-1600 XT2 3p is a 160 A three-pole thermomagnetic trip release for compatible SACE Tmax XT2 moulded-case circuit breakers with 800–1600 A instantaneous magnetic protection.
£176.05
The ABB TMA 160-1600 XT2 3p, order code 1SDA067236R1, is a three-pole thermomagnetic trip release designed for use with compatible ABB SACE Tmax XT2 moulded-case circuit breakers. As part of the advanced ABB SACE Tmax XT range, it provides dependable overload and short-circuit protection for low-voltage electrical distribution systems.
This TMA release combines thermal protection against sustained overload conditions with magnetic protection for high fault currents. It has a rated current of 160 A, while the instantaneous magnetic protection range associated with the TMA 160-1600 configuration is 800–1600 A, providing effective protection for demanding industrial distribution circuits.
Designed specifically for the XT2 frame size, the 1SDA067236R1 is a three-pole protection release that forms part of ABB's modular Tmax XT circuit-breaker system. Its compact construction and coordinated protection characteristics make it suitable for switchboards, distribution panels, machinery and infrastructure installations requiring reliable circuit protection.
Thermomagnetic releases protect electrical circuits through two complementary operating principles. The thermal element responds to sustained overload currents, while the magnetic element provides rapid operation when high short-circuit currents occur, helping protect conductors, equipment and downstream electrical systems.
The ABB TMA 160-1600 XT2 3p is engineered for the Tmax XT2 platform and is used together with a compatible XT2 breaking unit to create a coordinated moulded-case circuit-breaker assembly. Its 160 A rating makes it particularly suitable for higher-current feeders and distribution circuits within the XT2 frame range.
| Series | SACE Tmax XT |
|---|---|
| Product group | T-Max XT 250 Range |
| ABB order code | 1SDA067236R1 |
| Product type | Thermomagnetic trip release |
| Trip unit type | TMA |
| Compatible frame | XT2 |
| Rated current | 160 A |
| Instantaneous magnetic trip range | 800–1600 A |
| Number of poles | 3 |
| Standard | IEC |
| Net weight | 0.8 kg |
The ABB 1SDA067236R1 is a three-pole TMA thermomagnetic release designed for compatible ABB SACE Tmax XT2 moulded-case circuit breakers, providing overload and short-circuit protection.
The thermomagnetic release has a rated current of 160 A.
The TMA 160-1600 configuration provides an instantaneous magnetic trip range of 800–1600 A.
The 1SDA067236R1 is designed for the ABB SACE Tmax XT2 frame and is used with a compatible XT2 breaking unit.
The TMA release combines thermal overload protection with magnetic short-circuit protection, providing coordinated protection for low-voltage electrical circuits.
ABB SACE Tmax XT circuit protection products are widely used in industrial and commercial electrical installations where reliable overload and short-circuit protection, compact construction and coordinated system performance are essential.