1SDA067234R1 ABB TMA 100-1000 XT2 3P Thermomagnetic Trip Unit 100 A

1SDA067234R1 ABB TMA 100-1000 XT2 3P Thermomagnetic Trip Unit 100 A

ABB 1SDA067234R1 TMA 100-1000 is a 100 A three-pole AC/DC thermomagnetic trip unit for Tmax XT2 circuit breakers with adjustable 500–1000 A instantaneous magnetic short-circuit protection.

SKU: 1SDA067234R1MPN: 1SDA067234R1
Price
List Price £230.01 ex VAT
Your Price (ex VAT) Save 25%
£172.51 25% OFF
You save £57.50 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £172.51
Trade pricing is personalised to your account

Manufacturer Lead Time

£172.51

Why Choose the ABB 1SDA067234R1 TMA 100-1000 Thermomagnetic Trip Unit?

The ABB 1SDA067234R1 is a TMA 100-1000 three-pole thermomagnetic trip unit designed for ABB SACE Tmax XT2 moulded-case circuit breakers used in power distribution applications. With a rated current of 100 A, it provides thermal overload protection together with adjustable instantaneous magnetic protection against short-circuit currents.

As part of the ABB SACE Tmax XT protection system, the TMA release combines thermal and magnetic protection in a compact electromechanical design. The thermal element provides overload protection, while the magnetic element offers an adjustable instantaneous trip setting from 500–1000 A.

The 1SDA067234R1 is a 3-pole AC/DC thermomagnetic release specifically designed for the ABB Tmax XT2 platform. It has a rated current of 100 A and is intended for combination with a compatible XT2 breaking part to create a complete moulded-case circuit-breaker assembly.

Key Advantages

  • Genuine ABB TMA thermomagnetic trip unit for Tmax XT2.
  • 100 A rated current for power distribution protection.
  • Thermal protection against sustained overload conditions.
  • 500–1000 A adjustable instantaneous magnetic trip range.
  • Suitable for AC and DC applications.
  • Three-pole configuration for compatible ABB Tmax XT2 circuit breakers.

Key Features

  • ABB SACE Tmax XT thermomagnetic protection technology.
  • TMA 100-1000 trip-unit configuration.
  • 100 A rated current.
  • 500–1000 A instantaneous magnetic trip setting.
  • Thermal overload protection.
  • 3-pole configuration.
  • Suitable for AC/DC circuits.
  • Designed for Tmax XT2 moulded-case circuit breakers.
  • Associated with circuit-breaker applications to IEC 60947-2.
  • ABB order code 1SDA067234R1.

Reliable Thermomagnetic Protection for Power Distribution

Thermomagnetic trip units combine two complementary circuit-protection functions. The thermal element responds to sustained overload conditions, helping protect cables and distribution equipment from excessive current over time, while the magnetic element provides rapid operation when high short-circuit currents occur.

The ABB TMA 100-1000 has a rated current of 100 A together with adjustable instantaneous magnetic protection from 500–1000 A. This corresponds to 5–10 times the rated current, allowing the instantaneous protection threshold to be matched to the requirements of the electrical installation.

Typical Applications

  • ABB Tmax XT2 moulded-case circuit-breaker assemblies.
  • Industrial low-voltage power distribution.
  • Electrical distribution boards and switchboards.
  • Cable and feeder overload protection.
  • Commercial electrical distribution systems.
  • AC and DC power distribution applications.

Technical Specifications

Series SACE Tmax XT
Order code 1SDA067234R1
Product type Thermomagnetic trip unit
Release type TMA thermomagnetic
Suitable for Tmax XT2
Application Power distribution
Rated current (In) 100 A
Instantaneous magnetic trip (I3) 500–1000 A
Magnetic setting range 5–10 × In
Current type AC/DC
Number of poles 3P
Standard IEC 60947-2
Product net width 145 mm
Product net height 75 mm
Product net depth 95 mm
Product net weight 0.8 kg
EAN 8015644011369
Minimum order quantity 1 piece
Product group T-Max XT 250 Range

Frequently Asked Questions

What is the ABB 1SDA067234R1 used for?

The ABB 1SDA067234R1 is a three-pole TMA thermomagnetic trip unit used with compatible ABB Tmax XT2 moulded-case circuit breakers to provide overload and short-circuit protection in power distribution systems.

What is the rated current of the ABB 1SDA067234R1?

The TMA 100-1000 trip unit has a rated current of 100 A.

What is the magnetic trip range of the TMA 100-1000?

The instantaneous magnetic short-circuit protection is adjustable from 500–1000 A, corresponding to 5–10 times the 100 A rated current.

Which circuit breaker is the ABB 1SDA067234R1 designed for?

The trip unit is designed for compatible ABB SACE Tmax XT2 moulded-case circuit-breaker breaking parts and is supplied in a three-pole configuration.

Can the ABB 1SDA067234R1 be used on AC and DC circuits?

Yes. ABB specifies the TMA 100-1000 XT2 3p thermomagnetic release for AC/DC applications.

Trusted ABB Circuit Protection

ABB SACE Tmax XT thermomagnetic trip units provide overload and short-circuit protection for low-voltage power distribution systems, with dedicated releases designed to integrate with compatible Tmax XT circuit-breaker breaking parts.