ABB 1SDA067228R1 is a three-pole TMD thermomagnetic trip unit for SACE Tmax XT2 circuit breakers with a 25 A rated current, adjustable thermal overload protection and a 300 A fixed magnetic short-circuit threshold.
£172.51
The ABB 1SDA067228R1 is a three-pole TMD thermomagnetic trip unit designed for ABB SACE Tmax XT2 moulded-case circuit breakers. As part of the ABB Tmax XT protection range, it provides thermal overload and magnetic short-circuit protection for AC and DC power distribution applications.
This TMD release has a 25 A rated current with an adjustable thermal protection setting and a 300 A fixed magnetic short-circuit threshold. The thermal element responds to sustained overload conditions, while the magnetic element provides rapid operation during high-current short circuits.
Designed specifically for the three-pole Tmax XT2 frame, the 1SDA067228R1 is a loose or configurable trip unit intended to be combined with a compatible XT2 breaking part. Its matched design provides dependable circuit protection for industrial switchboards, distribution panels and machinery power systems.
Thermomagnetic trip units protect electrical circuits using two complementary operating principles. The thermal element responds to sustained overloads and can be adjusted to suit the protected circuit, while the magnetic element provides rapid tripping when a severe short-circuit current occurs.
The ABB 1SDA067228R1 is engineered for the Tmax XT2 platform and provides a straightforward protection solution where conventional thermomagnetic operation is required. Its three-pole configuration and AC/DC suitability make it appropriate for a broad range of industrial and commercial power distribution installations.
| Series | SACE Tmax XT |
|---|---|
| Model / order code | 1SDA067228R1 |
| Product type | Thermomagnetic trip unit |
| Trip unit | TMD |
| Suitable breaker | Tmax XT2 |
| Rated current | 25 A |
| Thermal adjustment | 0.7–1 × In |
| Magnetic protection threshold | 300 A |
| Number of poles | 3 |
| Current type | AC / DC |
| Configuration | Loose / configurable |
| Standard | IEC 60947-2 |
| Net weight | 0.8 kg |
| EAN | 8015644695088 |
It is a TMD thermomagnetic trip unit for three-pole ABB SACE Tmax XT2 circuit breakers, providing overload and short-circuit protection in AC and DC distribution systems.
The ABB 1SDA067228R1 has a 25 A rated current.
The TMD release provides a 300 A fixed magnetic short-circuit protection threshold.
Yes. The thermal protection is adjustable over a range of 0.7–1 × In, allowing the overload setting to be matched to the protected circuit.
It is specifically designed for compatible three-pole ABB SACE Tmax XT2 moulded-case circuit breaker assemblies.
ABB SACE Tmax XT thermomagnetic releases provide coordinated overload and short-circuit protection for low-voltage distribution systems, with trip units engineered specifically for compatible Tmax XT circuit breaker frames.