1SDA066401R1 ABB UVR-C XT1-XT4 F/P 480-525 V AC Undervoltage Release

1SDA066401R1 ABB UVR-C XT1-XT4 F/P 480-525 V AC Undervoltage Release

ABB 1SDA066401R1 UVR-C is a wired 480–525 V AC undervoltage release designed for fixed and plug-in SACE Tmax XT1, XT2, XT3 and XT4 circuit breakers.

SKU: 1SDA066401R1MPN: 1SDA066401R1
Price
List Price £161.04 ex VAT
Your Price (ex VAT) Save 25%
£120.78 25% OFF
You save £40.26 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £120.78
Trade pricing is personalised to your account

Manufacturer Lead Time

£120.78

Why Choose the ABB 1SDA066401R1 UVR-C Undervoltage Release?

The ABB 1SDA066401R1 is a wired UVR-C undervoltage release designed for compatible ABB SACE Tmax XT moulded-case circuit breakers. As part of the ABB SACE Tmax XT accessory range, it provides undervoltage protection and control functionality for XT1, XT2, XT3 and XT4 circuit breakers in fixed and plug-in configurations.

The undervoltage release monitors its auxiliary supply and causes the associated circuit breaker to open if the supply is lost or falls sufficiently below its rated level. This functionality can help protect electrical equipment and processes against undesirable operation during significant voltage reductions, while also preventing the breaker from closing when the release is not adequately energised.

With a rated control voltage of 480–525 V AC, the 1SDA066401R1 is designed for higher-voltage AC control circuits. Its wired UVR-C configuration is intended for fixed and plug-in ABB Tmax XT1 through XT4 circuit breakers, providing an ABB-engineered accessory for industrial switchboards and low-voltage power distribution systems.

Key Advantages

  • Genuine ABB SACE Tmax XT undervoltage release.
  • 480–525 V AC rated control voltage for compatible AC control circuits.
  • Compatible with Tmax XT1, XT2, XT3 and XT4 circuit breakers.
  • Designed for fixed and plug-in breaker configurations.
  • Automatically initiates breaker opening following loss or substantial reduction of the release supply voltage.
  • Wired UVR-C configuration simplifies integration with compatible Tmax XT circuit breakers.

Key Features

  • ABB SACE Tmax XT accessory range.
  • UVR-C wired undervoltage release.
  • 480–525 V AC rated voltage.
  • Compatible with XT1, XT2, XT3 and XT4 frame sizes.
  • Suitable for fixed and plug-in circuit-breaker executions.
  • Provides automatic circuit-breaker opening under undervoltage or loss-of-supply conditions.
  • Prevents normal circuit-breaker closing when the undervoltage release is insufficiently energised.
  • Designed to applicable IEC 60947-2 and UL 489 requirements.

Reliable Undervoltage Protection for Circuit Breakers

An undervoltage release is designed to open its associated circuit breaker when the release supply disappears or falls below the required operating level. This makes the device useful in electrical systems where equipment should be disconnected following a significant supply-voltage reduction and should not automatically remain connected when adequate control voltage is unavailable.

The ABB UVR-C range is engineered as part of the Tmax XT circuit-breaker accessory system. The 1SDA066401R1 combines a 480–525 V AC operating range with a wired configuration for fixed and plug-in XT1 through XT4 breakers, making it suitable for industrial switchboards, machinery and power distribution installations.

Typical Applications

  • Industrial low-voltage switchboards and distribution panels.
  • Undervoltage protection for ABB Tmax XT circuit breakers.
  • Machine and process control systems.
  • Industrial power distribution equipment.
  • Building electrical distribution systems.
  • Automation and safety control circuits requiring breaker opening following loss of control voltage.

Technical Specifications

Series SACE Tmax XT
ABB order code 1SDA066401R1
Product type Wired undervoltage release
Accessory type Undervoltage release (UVR)
Rated control voltage 480–525 V AC
Voltage type AC
Compatible frame sizes XT1, XT2, XT3 and XT4
Breaker execution Fixed / plug-in
Standards IEC 60947-2, UL 489
EAN 8015644003111
Weight 0.12 kg

Frequently Asked Questions

What is the ABB 1SDA066401R1 used for?

The ABB 1SDA066401R1 is a wired undervoltage release used with compatible ABB Tmax XT circuit breakers to initiate opening when its control supply is lost or falls sufficiently below the required level.

What control voltage does the 1SDA066401R1 require?

The undervoltage release is rated for a 480–525 V AC control supply.

Which circuit breakers are compatible with the ABB 1SDA066401R1?

The 1SDA066401R1 is designed for ABB SACE Tmax XT1, XT2, XT3 and XT4 moulded-case circuit breakers in fixed and plug-in configurations.

What does an undervoltage release do?

An undervoltage release causes the associated circuit breaker to open when its supply voltage is lost or drops sufficiently below the required operating level, helping prevent equipment from remaining energised during severe undervoltage conditions.

Is the ABB 1SDA066401R1 a wired undervoltage release?

Yes. The 1SDA066401R1 is an UVR-C wired undervoltage release designed for fixed and plug-in ABB SACE Tmax XT1 through XT4 circuit breakers.

Trusted ABB Circuit-Breaker Accessories

ABB SACE Tmax XT accessories are engineered to extend the protection, control and operating capabilities of Tmax XT moulded-case circuit breakers, providing dependable solutions for industrial switchboards, power distribution systems and automated electrical installations.