1SDA062091R1 ABB UVR T7-T7M-X1 110–120 V AC/DC Undervoltage Release

1SDA062091R1 ABB UVR T7-T7M-X1 110–120 V AC/DC Undervoltage Release

ABB 1SDA062091R1 UVR T7-T7M-X1 110–120 V AC/DC undervoltage release for voltage-dependent tripping and control of compatible ABB Tmax T7, T7M and Emax X1 circuit-breaker applications.

SKU: 1SDA062091R1Alt SKU: T7/X1 UVRMPN: 1SDA062091R1
Price
List Price £467.79 ex VAT
Your Price (ex VAT) Save 25%
£350.84 25% OFF
You save £116.95 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £350.84
Trade pricing is personalised to your account

Manufacturer Lead Time

£350.84

Why Choose the ABB 1SDA062091R1 T7-T7M-X1 Undervoltage Release?

The ABB 1SDA062091R1 is a UVR undervoltage release designed for compatible ABB Tmax T7, T7M and Emax X1 circuit-breaker applications. Rated for a 110–120 V AC/DC control supply, it provides automatic circuit-breaker opening when the monitored supply voltage falls significantly or is lost.

As part of the ABB Tmax T4–T8 accessory range, the UVR provides an important electrical control and protection function within low-voltage switchgear. In addition to initiating opening during an undervoltage condition, an undervoltage release can prevent the compatible circuit breaker from closing until sufficient control voltage is available, supporting controlled operation of electrical distribution systems.

The UVR T7-T7M-X1 110–120 V AC/DC accepts both AC and DC control supplies across its specified voltage range. Its dedicated compatibility with ABB T7, T7M and X1 equipment makes it suitable for industrial switchboards, automated power distribution systems and installations requiring voltage-dependent circuit-breaker operation.

Key Advantages

  • Dedicated undervoltage release for ABB T7, T7M and X1 applications.
  • 110–120 V AC/DC rated voltage supports both AC and DC control systems.
  • Automatically initiates circuit-breaker opening following a significant loss of control voltage.
  • Helps prevent circuit-breaker closing when adequate control voltage is unavailable.
  • Suitable for remote tripping and voltage-monitoring applications.
  • Genuine ABB accessory designed for integration with ABB low-voltage switchgear.

Key Features

  • ABB UVR T7-T7M-X1 undervoltage release.
  • 110–120 V AC rated voltage.
  • 110–120 V DC rated voltage.
  • AC/DC current type.
  • Provides automatic opening during an undervoltage or loss-of-supply condition.
  • Can be used for safe remote tripping and voltage-dependent circuit-breaker control.
  • Compatible with ABB Tmax T7 and Emax X1 equipment.
  • Loose or configurable accessory format.
  • Designed in accordance with IEC requirements.
  • RoHS compliant for modern electrical installations.

Reliable Undervoltage Monitoring and Circuit Breaker Control

An undervoltage release monitors its electrical supply and causes the associated circuit breaker to open when voltage falls below the operating level required to keep the release energised. This provides a dependable means of disconnecting electrical loads following significant voltage loss or supply failure and can help prevent uncontrolled restarting when power is restored.

The ABB 1SDA062091R1 is designed for 110–120 V AC/DC control circuits and can also support remote tripping and voltage-dependent closing control. Its compatibility with ABB T7, T7M and X1 equipment makes it suitable for demanding industrial and commercial switchgear installations.

Typical Applications

  • Industrial low-voltage switchboards.
  • Undervoltage and power-failure protection systems.
  • Remote circuit-breaker tripping circuits.
  • Automated power distribution installations.
  • Industrial and commercial switchgear assemblies.
  • ABB Tmax T7, T7M and Emax X1 circuit-breaker applications.

Technical Specifications

Series Tmax T Accessories
ABB order code 1SDA062091R1
Product type Undervoltage release
Accessory designation UVR
Rated AC voltage 110–120 V AC
Rated DC voltage 110–120 V DC
Current type AC / DC
Compatible platforms ABB Tmax T7 / T7M / Emax X1
Function Undervoltage release / electrical tripping
Configuration type Loose or configurable
Standards IEC
RoHS compliance EU Directive 2011/65/EU and amendment 2015/863
EAN 8015644646318
ABB product group 310511-T-Max T4 - T8

Frequently Asked Questions

What is the ABB 1SDA062091R1 used for?

The ABB 1SDA062091R1 is an undervoltage release designed to initiate opening of a compatible ABB circuit breaker when its control voltage falls significantly or is lost.

What voltage is the ABB 1SDA062091R1 rated for?

The UVR T7-T7M-X1 is rated for 110–120 V AC and 110–120 V DC.

What does UVR mean on the ABB 1SDA062091R1?

UVR means undervoltage release, an electrical accessory used to trip a compatible circuit breaker following a significant reduction or loss of its control voltage.

Which ABB circuit breakers are compatible with the 1SDA062091R1?

The 1SDA062091R1 is designed for compatible ABB Tmax T7, T7M and Emax X1 circuit-breaker applications.

Can the ABB 1SDA062091R1 prevent a circuit breaker from closing?

Yes. An undervoltage release can prevent the compatible circuit breaker from closing when sufficient control voltage is not present, as well as initiating opening following an undervoltage or supply-loss condition.

Trusted by Switchboard Builders Worldwide

ABB Tmax and Emax electrical accessories provide switchboard builders and electrical professionals with integrated solutions for circuit-breaker control, remote operation and voltage-dependent protection in low-voltage power distribution systems.