ABB 1SDA060357R1 is a 630 A four-pole PR221DS-LS/I solid-state electronic trip unit for compatible Tmax T6 moulded case circuit breakers, providing long-time, short-time and instantaneous overcurrent protection.
£1,455.00
The ABB PR221DS-LS/I In=630 T6 630 4P, order code 1SDA060357R1, is a solid-state electronic trip unit designed for compatible ABB SACE Tmax T6 moulded case circuit breakers. Part of the established ABB Tmax T6 protection system, it provides long-time, short-time and instantaneous overcurrent protection for high-current low-voltage electrical distribution applications.
Rated at 630 A, the PR221DS-LS/I continuously monitors current through the associated circuit breaker and initiates tripping when configured protection thresholds are exceeded. Its LS/I functionality combines overload protection with selective short-circuit and instantaneous fault protection, providing a flexible electronic alternative to conventional thermomagnetic releases.
This version is specifically intended for 4-pole Tmax T6 circuit breaker configurations. The combination of a 630 A rating, electronic protection technology and multiple overcurrent protection functions makes the 1SDA060357R1 suitable for industrial switchboards, feeder protection and other demanding three-phase plus neutral power distribution systems.
Electronic trip units monitor the current flowing through a circuit breaker and compare it with configured protection thresholds. The PR221DS-LS/I provides complementary long-time, short-time and instantaneous functions, allowing the associated Tmax T6 breaker to respond appropriately to sustained overloads, short-duration high currents and severe short-circuit faults.
The 630 A rating and four-pole configuration make this trip unit suitable for high-current three-phase plus neutral distribution systems. When installed in a compatible Tmax T6 assembly, it provides reliable electronic protection for feeders, switchboards and industrial power distribution equipment.
| Series | SACE Tmax T6 |
|---|---|
| Order code | 1SDA060357R1 |
| Product type | Solid-state electronic trip unit |
| Compatible frame | Tmax T6 |
| Trip unit | PR221DS-LS/I |
| Rated current (In) | 630 A |
| Number of poles | 4 |
| Protection technology | Electronic / solid-state |
| Long-time protection | L |
| Short-time protection | S |
| Instantaneous protection | I |
| Instantaneous short-circuit adjustment range | 630–6300 A |
| Suitable for power circuit breakers | Yes |
| Suitable for overload protection | Yes |
The ABB 1SDA060357R1 is a PR221DS-LS/I solid-state electronic trip unit rated at 630 A for compatible 4-pole ABB Tmax T6 moulded case circuit breaker assemblies.
The PR221DS-LS/I provides long-time, short-time and instantaneous overcurrent protection functions for compatible Tmax T6 circuit breakers.
The electronic trip unit has a rated current of 630 A.
This order code identifies the 4-pole version of the 630 A PR221DS-LS/I trip unit for the ABB Tmax T6 platform.
The instantaneous short-circuit release setting range extends from 630 to 6300 A.
The 1SDA060357R1 is designed for compatible ABB SACE Tmax T6 moulded case circuit breaker configurations.