1SDA060348R1 ABB TMA 630-6300 T6 630A 4-Pole Thermomagnetic Trip Unit

1SDA060348R1 ABB TMA 630-6300 T6 630A 4-Pole Thermomagnetic Trip Unit

ABB 1SDA060348R1 is a TMA 630-6300 four-pole thermomagnetic trip unit for compatible Tmax T6 circuit breakers, rated at 630 A with an adjustable 3150–6300 A instantaneous magnetic trip threshold and 50% neutral protection.

SKU: 1SDA060348R1MPN: 1SDA060348R1
Price
List Price £1,746.08 ex VAT
Your Price (ex VAT) Save 25%
£1,309.56 25% OFF
You save £436.52 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,309.56
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,309.56

Why Choose the ABB TMA 630-6300 T6 630 4-Pole Thermomagnetic Trip Unit?

The ABB TMA 630-6300 T6 630 4P, order code 1SDA060348R1, is a thermomagnetic trip unit designed for compatible ABB SACE Tmax T6 moulded case circuit breakers. Part of the proven ABB Tmax T6 series, it provides thermal overload and magnetic short-circuit protection for high-current low-voltage electrical distribution applications.

The trip unit has a rated current of 630 A and combines a thermal element for sustained overload protection with an adjustable instantaneous magnetic element for short-circuit protection. Its magnetic trip threshold I3 is adjustable from 3150 to 6300 A, equivalent to approximately 5–10 times the rated current.

This version is specifically configured for 4-pole Tmax T6 circuit breaker assemblies and has a neutral protection setting corresponding to 50% of the phase rating. Its straightforward thermomagnetic operating principle provides dependable circuit protection without requiring an electronic protection release.

Key Advantages

  • Dedicated thermomagnetic trip unit for ABB Tmax T6 circuit breakers.
  • 630 A rated current for high-current distribution applications.
  • Provides both thermal overload and magnetic short-circuit protection.
  • Adjustable instantaneous magnetic threshold from 3150 to 6300 A.
  • 4-pole configuration for compatible three-phase plus neutral circuit breaker assemblies.
  • Neutral protection calibrated to 50% of the phase rating.

Key Features

  • ABB TMA 630-6300 thermomagnetic release.
  • Designed for the ABB SACE Tmax T6 platform.
  • 630 A rated current.
  • 3150–6300 A adjustable magnetic trip threshold (I3).
  • Thermal protection for sustained overload conditions.
  • Instantaneous magnetic protection against high short-circuit currents.
  • 4-pole configuration.
  • 50% neutral protection setting.
  • Suitable for compatible Tmax T6 breaking parts and circuit breaker assemblies.

Reliable Thermomagnetic Protection for Tmax T6 Circuit Breakers

Thermomagnetic trip units use two complementary protection principles. The thermal element responds to sustained overload currents that could overheat conductors and equipment, while the magnetic element reacts rapidly to severe short-circuit currents so that the associated circuit breaker can interrupt the fault.

The ABB TMA 630-6300 combines a 630 A rated current with an adjustable 3150–6300 A instantaneous magnetic threshold. In this four-pole version, the neutral protection is calibrated to 50% of the phase rating, making the trip unit suitable for compatible Tmax T6 four-pole distribution configurations.

Typical Applications

  • ABB Tmax T6 moulded case circuit breaker assemblies.
  • Industrial low-voltage distribution boards.
  • Three-phase plus neutral distribution circuits.
  • Main and feeder circuit protection.
  • Manufacturing and process plant switchgear.
  • Machinery and industrial power distribution panels.

Technical Specifications

Series SACE Tmax T6
Order code 1SDA060348R1
Product type Thermomagnetic trip unit
Compatible frame Tmax T6
Trip unit type TMA
Rated current (In) 630 A
Magnetic trip threshold (I3) 3150–6300 A
Magnetic adjustment range 5–10 × In
Number of poles 4
Neutral protection 50% of phase rating
Protection technology Thermomagnetic
Overload protection Thermal
Short-circuit protection Adjustable instantaneous magnetic
Suitable for ABB Tmax T6
Standards family IEC
EAN 8015644627560

Frequently Asked Questions

What is the ABB 1SDA060348R1?

The ABB 1SDA060348R1 is a TMA 630-6300 thermomagnetic trip unit rated at 630 A for compatible 4-pole ABB Tmax T6 circuit breaker assemblies.

What is the rated current of the ABB TMA 630-6300?

The TMA 630-6300 trip unit has a rated current of 630 A.

What is the magnetic trip range of the ABB 1SDA060348R1?

The instantaneous magnetic trip threshold I3 is adjustable from 3150 to 6300 A, corresponding to approximately 5–10 times the 630 A rated current.

What protection does the TMA 630-6300 provide?

The trip unit combines thermal overload protection with adjustable instantaneous magnetic short-circuit protection.

How many poles is the ABB 1SDA060348R1 designed for?

This order code identifies the 4-pole version of the TMA 630-6300 trip unit for compatible ABB Tmax T6 circuit breaker assemblies.

What neutral protection does this four-pole trip unit provide?

The 1SDA060348R1 version is configured with the neutral protection calibrated to 50% of the phase rating.

Trusted by Electrical Professionals Worldwide

ABB Tmax circuit breaker protection units are used by panel builders, electrical engineers and industrial operators to provide dependable overload and short-circuit protection in demanding power distribution installations.