ABB 1SDA055890R1 SACE Emax E2N 1600 is a 1600 A three-pole fixed air circuit breaker with rear horizontal terminals, a PR121/P-LSIG electronic release and 65 kA short-circuit breaking capacity at 415 V AC.
£9,314.85
The ABB 1SDA055890R1 is a SACE Emax E2N 1600 air circuit breaker designed for high-current switching and comprehensive overcurrent protection in demanding low-voltage AC power distribution systems. This three-pole fixed circuit breaker has a rated current of 1600 A and is equipped with a PR121/P-LSIG R1600 electronic overcurrent release.
The PR121/P-LSIG release provides long-time, short-time, instantaneous and earth-fault protection, helping protect distribution equipment against overloads, short circuits and earth-fault conditions. The E2N performance level provides rated ultimate and service short-circuit breaking capacities of 65 kA at 415 V AC, with substantial fault-interruption capability maintained at higher operating voltages.
The 1SDA055890R1 is a three-pole fixed (F) circuit breaker with rear horizontal (HR) terminals for integration into compatible low-voltage switchboards. It is rated for operation up to 690 V AC, while four auxiliary change-over contacts and circuit-breaker open/closed position indication support signalling, monitoring and control applications.
The ABB SACE Emax E2N 1600 provides switching and electronic protection for high-current low-voltage distribution circuits. Its PR121/P-LSIG release combines long-time protection against sustained overloads, short-time protection for fault coordination, instantaneous protection against severe short circuits and earth-fault protection for faults involving earth or protective conductors.
With a 1600 A current rating, three-pole fixed construction and 65 kA short-circuit breaking capacity at 415 V AC, the 1SDA055890R1 is well suited to main incoming and high-current feeder duties. Rear horizontal terminals support integration into suitable busbar systems, while the E2N performance level maintains strong fault-interruption capability through to 690 V AC.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA055890R1 |
| Product type | Air circuit breaker |
| Frame / sub-type | E2 |
| Short-circuit performance level | N |
| Rated current (In) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated operational current (Ie) | 1600 A |
| Number of poles | 3 |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 400/415 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 55 kA |
| Rated service short-circuit breaking capacity (Ics) at 500 V AC | 55 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 55 kA |
| Rated service short-circuit breaking capacity (Ics) at 690 V AC | 55 kA |
| Rated short-time withstand current (Icw) | 55 kA for 1 s |
| Release | PR121/P-LSIG R1600 |
| Release type | Electronic |
| Protection functions | LSIG – long-time, short-time, instantaneous and earth-fault |
| Long-time protection (L) | Overload protection |
| Overload release adjustment range | 640–1600 A |
| Short-time protection (S) | Delayed short-circuit protection |
| Short-time short-circuit adjustment range | 1600–16000 A |
| Instantaneous protection (I) | Instantaneous short-circuit protection |
| Instantaneous short-circuit adjustment range | 2400–24000 A |
| Earth-fault protection (G) | Integrated |
| Installation | Fixed |
| Terminal connection | Rear flat horizontal |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Complete device with protection unit | Yes |
| Motor drive integrated | No |
| Motor drive optional | Yes |
| Switched-off indication | Available |
| DIN rail mounting | No |
| Standard | IEC |
The ABB 1SDA055890R1 is a SACE Emax E2N 1600 three-pole fixed air circuit breaker rated at 1600 A, with rear horizontal terminals and a PR121/P-LSIG R1600 electronic overcurrent release.
The breaker is fitted with a PR121/P-LSIG R1600 electronic release, providing long-time, short-time, instantaneous and earth-fault protection.
LSIG denotes long-time, short-time, instantaneous and earth-fault protection. Together these functions provide protection against sustained overloads, delayed and severe short-circuit faults, and earth-fault conditions.
The 1SDA055890R1 is a fixed three-pole circuit breaker fitted with rear flat horizontal terminals for permanent installation within a compatible low-voltage switchboard.
The E2N 1600 has rated ultimate and service short-circuit breaking capacities of 65 kA at 400/415 V AC. At 500–690 V AC, both Icu and Ics are 55 kA.
ABB SACE Emax air circuit breakers provide robust switching and electronic protection for low-voltage power distribution, combining high short-circuit performance, comprehensive LSIG protection and dependable fixed switchboard integration for demanding industrial and infrastructure applications.