1SDA055648R1 ABB E1B 1250 PR121/P-LI 1250 A 3-Pole Withdrawable Air Circuit Breaker Moving Part

1SDA055648R1 ABB E1B 1250 PR121/P-LI 1250 A 3-Pole Withdrawable Air Circuit Breaker Moving Part

ABB 1SDA055648R1 E1B 1250 PR121/P-LI is a 1250 A three-pole SACE Emax withdrawable air circuit breaker moving part with a PR121/P-LI R1250 electronic trip unit providing long-time overload and instantaneous short-circuit protection.

SKU: 1SDA055648R1Alt SKU: E1B1250PR121/P-LIIMPN: 1SDA055648R1
Price
List Price £10,372.11 ex VAT
Your Price (ex VAT) Save 25%
£7,779.08 25% OFF
You save £2,593.03 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £7,779.08
Trade pricing is personalised to your account

Manufacturer Lead Time

£7,779.08

Why Choose the ABB E1B 1250 PR121/P-LI Air Circuit Breaker Moving Part?

The ABB E1B 1250 PR121/P-LI, order code 1SDA055648R1, is a SACE Emax withdrawable air circuit breaker moving part designed for high-current low-voltage power distribution systems. This three-pole configuration combines a 1,250 A rated current with the PR121/P-LI R1250 electronic overcurrent release for long-time overload and instantaneous short-circuit protection.

Part of the proven ABB SACE Emax E1 series, the E1B 1250 moving part is intended for use with a compatible withdrawable circuit-breaker fixed part. Its withdrawable construction supports convenient inspection, servicing and replacement in industrial switchboards and critical power distribution assemblies.

The breaker is rated for operation up to 690 V AC and provides rated ultimate and service short-circuit breaking capacities of 42 kA at 400/415 V AC. It also provides a rated short-time withstand current of 42 kA for 1 s, supporting dependable performance in demanding distribution networks.

Key Advantages

  • High-capacity 1,250 A SACE Emax circuit-breaker moving part for low-voltage distribution.
  • PR121/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection.
  • Three-pole withdrawable configuration supports convenient maintenance and replacement.
  • 42 kA Icu and Ics at 400/415 V AC.
  • 42 kA short-time withstand current for 1 s.
  • Four auxiliary contacts with open/closed position indication support switchboard signalling and monitoring.

Key Features

  • ABB SACE Emax E1B series.
  • 1,250 A rated uninterrupted current.
  • Three-pole configuration.
  • Withdrawable moving part for a compatible SACE Emax fixed part.
  • PR121/P-LI R1250 electronic overcurrent release.
  • Long-time overload protection.
  • Instantaneous short-circuit protection.
  • 690 V AC rated operational voltage.
  • 1,000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 42 kA Icu and Ics at 400/415 V AC.
  • 42 kA Icw for 1 s and 36 kA for 3 s.
  • Four auxiliary contacts with open/closed position indication.

Electronic LI Protection in a Service-Friendly Withdrawable Design

The ABB SACE Emax E1B provides switching and overcurrent protection for high-current low-voltage distribution circuits. Its PR121/P-LI electronic release combines adjustable long-time overload protection with instantaneous short-circuit protection, helping safeguard cables, busbars and downstream electrical equipment against sustained overloads and severe fault currents.

The three-pole withdrawable moving-part configuration is particularly suited to switchboards where serviceability is important. The breaker can be withdrawn from its compatible fixed part for inspection or maintenance, while four auxiliary contacts and open/closed position indication allow its operating status to be integrated into signalling, monitoring and control systems.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Withdrawable switchgear assemblies.
  • Commercial and infrastructure electrical installations.
  • Transformer secondary distribution circuits.
  • Generator and standby power distribution.
  • Manufacturing and process plant switchgear.

Technical Specifications

Series SACE Emax E1
ABB order code 1SDA055648R1
Product group New Emax
Product type Air circuit breaker moving part
Rated current (In) 1250 A
Rated uninterrupted current (Iu) 1250 A
Rated operational current (Ie) 1250 A
Number of poles 3
Execution Withdrawable moving part
Trip unit PR121/P-LI R1250
Release type Electronic
Protection functions L-I (long-time and instantaneous)
Long-time protection setting range 0.4–1 × In
Instantaneous protection setting range 1–15 × In
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC 42 kA
Rated service short-circuit breaking capacity (Ics) at 400/415 V AC 42 kA
Rated short-time withstand current (Icw), 1 s 42 kA
Rated short-time withstand current (Icw), 3 s 36 kA
Short-circuit performance level B
Auxiliary contacts 4
Position indication Open / closed
Electrical durability at up to 440 V 10,000 cycles
Electrical durability at 500–690 V 8,000 cycles
Mechanical durability 25,000 cycles
Power loss 230 W
Product dimensions (W × H × D) 324 × 461 × 396.5 mm
Product net weight 44 kg
Standard IEC
EAN 8015644569884

Frequently Asked Questions

What is the ABB 1SDA055648R1?

The ABB 1SDA055648R1 is an E1B 1250 three-pole SACE Emax withdrawable circuit-breaker moving part rated at 1,250 A and equipped with a PR121/P-LI R1250 electronic overcurrent release.

What protection does the PR121/P-LI trip unit provide?

The PR121/P-LI electronic release provides long-time overload and instantaneous short-circuit protection.

What is the breaking capacity of the ABB E1B 1250?

The E1B 1250 has rated ultimate and service short-circuit breaking capacities of 42 kA at 400/415 V AC.

What are the protection setting ranges of the ABB 1SDA055648R1?

The long-time protection setting range is 0.4–1 × In, while the instantaneous protection setting range is 1–15 × In.

Is the ABB 1SDA055648R1 a complete withdrawable circuit breaker?

The 1SDA055648R1 is the withdrawable moving part and is designed for use with a compatible ABB SACE Emax fixed part to form the complete withdrawable circuit-breaker assembly.

Trusted Low-Voltage Protection from ABB

ABB SACE Emax air circuit breakers provide dependable protection and control for low-voltage power distribution systems, combining high-current switching capability with electronic protection and service-friendly withdrawable construction for demanding industrial, commercial and infrastructure installations.