Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA054713R1 is a 320 A three-pole PR222DS/PD-LSIG solid-state electronic trip unit for SACE Tmax T5 moulded-case circuit breakers with LSIG protection and Modbus communication.
£3,392.14
The ABB 1SDA054713R1 is a PR222DS/PD-LSIG solid-state electronic trip unit designed for three-pole ABB SACE Tmax T5 moulded-case circuit breakers. Rated at 320 A, it combines comprehensive electronic circuit protection with Modbus communication for low-voltage power distribution, monitoring and industrial automation applications.
The PR222DS/PD-LSIG provides long-time overload (L), selective short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection. This combination enables the associated Tmax T5 circuit breaker to respond to sustained overloads, different levels of short-circuit current and earth-fault conditions while supporting coordinated protection throughout the electrical distribution system.
Designed for a three-pole (3P) Tmax T5 configuration, the release has a rated current of 320 A and an adjustable instantaneous short-circuit release range of 480–3840 A. Its Modbus capability makes it particularly suitable for installations combining circuit protection with remote supervision, automation and centralised power-management systems.
The ABB PR222DS/PD-LSIG continuously evaluates circuit current and provides multiple levels of electronic protection. Long-time protection responds to sustained overload conditions, short-time and instantaneous functions protect against short circuits, and the ground-fault function adds protection against earth-fault currents within the capabilities of the associated system.
Communication capability extends the release beyond conventional standalone protection by enabling integration with compatible supervision and automation systems. Combined with an ABB SACE Tmax T5 circuit breaker, the 1SDA054713R1 provides a capable solution for installations requiring 320 A LSIG protection, adjustable fault response and networked electrical monitoring.
| Series | SACE Tmax T5 |
|---|---|
| ABB order code | 1SDA054713R1 |
| Product type | Solid-state electronic circuit breaker trip unit |
| Trip unit | PR222DS/PD-LSIG |
| Suitable for | ABB SACE Tmax T5 moulded-case circuit breaker |
| Rated current (In) | 320 A |
| Number of poles | 3 |
| Protection technology | Solid-state electronic |
| Protection functions | LSIG |
| Overload protection | Long-time (L) |
| Selective short-circuit protection | Short-time (S) |
| Instantaneous short-circuit protection | Instantaneous (I) |
| Ground-fault protection | Ground fault (G) |
| Instantaneous short-circuit release setting range | 480–3840 A |
| Communication | Modbus |
| Auxiliary supply for communication | 24 V DC |
| Application | AC circuit protection |
| EAN | 8015644558277 |
The ABB 1SDA054713R1 is a PR222DS/PD-LSIG solid-state electronic trip unit rated at 320 A for compatible three-pole ABB SACE Tmax T5 moulded-case circuit breakers.
The release provides LSIG protection: long-time overload protection (L), selective short-time short-circuit protection (S), instantaneous short-circuit protection (I) and ground-fault protection (G).
The instantaneous short-circuit release setting range is 480–3840 A, providing adjustment for coordination with the protected electrical system.
Yes. The PR222DS/PD version provides Modbus communication for integration with compatible electrical supervision, monitoring and industrial automation systems.
Yes. The G function in the LSIG designation identifies ground-fault protection in addition to overload and short-circuit protection.
This specific 320 A three-pole electronic release is designed for compatible ABB SACE Tmax T5 moulded-case circuit breakers.
ABB SACE Tmax electronic protection solutions are widely used in industrial and commercial power distribution systems where coordinated overload, short-circuit and ground-fault protection combined with electrical system communication is required.
We use cookies